List Of Check Codes (Outdoor Unit) - Toshiba MMY-MUP0801HT8JP Service Manual

Air conditioner (multi type) super modular multi system-u smms-u
Table of Contents

Advertisement

List of Check Codes (Outdoor Unit)

(Check code detected by outdoor interface - typical examples)
If "HELLO" is displayed on the oudoor 7-segment for 1 minute or more, turn off the power supply once and
then turn on the power supply again after passage of 30 seconds or more. When the same symptom appears,
it is considered there is a possibility of I/F board trouble.
Check code
Outdoor 7-segment display
Sub-code
Number of indoor units from which
E06
signal is received normally
E07
E08 Duplicated indoor address
01: Indoor-outdoor communication
E12
02: Outdoor-outdoor
communication
E15
00: Capacity over
E16
01: Number of units connected
00: No header unit
E19
02: Two or more header units
01: Connection of outdoor unit from
other refrigerant line
E20
02: Connection of indoor unit from
other refrigerant line
E23
E25
Address of outdoor unit from which
E26
signal is not received normally
E28
Detected outdoor unit No.
P.C.board
Compressor Fan Motor
1
2
1
2
01
O
02
O
03
O
O
E31
08
O
09
O
O
0A
O
O
0B
O
O
O
10
O
Circle (O): Trouble P.C. board
80 : Communication trouble between
MCU and Sub MCU
F04
F05
01: TE1 sensor
02: TE2 sensor
F06
03: TE3 sensor
01: TL1 sensor
02: TL2 sensor
F07
03: TL3 sensor
F08
01: TG1 sensor
F0
9
02: TG2 sensor
03: TG3 sensor
Display of receiving unit
Central
Indicator light block
control or
main remote
Operation Timer Ready
controller
display
E06
(E04)
(E08)
E12
E15
E16
E19
E20
E23
E25
E26
E28
P.C.board
Compressor Fan Motor
1
2
1
2
11
O
O
12
O
O
13
O
O
O
E31
18
O
O
19
O
O
O
1A
O
O
O
1B
O
O
O
O
F04
F05
F06
F07
F08
F09
: Lighting,
ALT.: Flashing is alternately when there are two flashing LED
SIM: Simultaneous flashing when there are two flashing LED
Typical problem site
Flash
Signal lack of indoor unit
Indoor-outdoor
communication circuit
trouble
Duplicated indoor address
Automatic address starting
trouble
Indoor unit not found
during automatic address
setting
Too many indoor units
connected/capacity over
Trouble in number of
outdoor header units
Connection to other
refrigerant line found
during automatic address
setting
Outdoor-outdoor
communication
transmission trouble
Duplicated follower
outdoor address
Signal lack of outdoor unit
Outdoor follower unit
trouble
P.C. board communication
trouble
Sub MCU
communication trouble
Outdoor discharge
ALT
temperature sensor (TD1)
trouble
Outdoor discharge
ALT
temperature sensor (TD2)
trouble
Outdoor heat exchanger
liquid side temperature
ALT
sensor (TE1, TE2, TE3)
trouble
Outdoor liquid temperature
sensor (TL1,TL2,TL3)
ALT
trouble
Outdoor outside air
ALT
temperature sensor (TO)
trouble
Outdoor heat exchanger
gas side temperature
ALT
sensor (TG1, TG2, TG3)
trouble
- 172 -
: Flashing,
: Goes off
Description of problem
• Indoor unit initially communicating normally fails
to return signal (reduction in number of indoor
units connected).
In TU2C-LINK communication system, if the
termination resistance is not set in any of the
indoor units
Signal cannot be transmitted to indoor units
(
indoor units left without communication from
outdoor unit).
More than one indoor unit are assigned same
address (also detected at indoor unit end).
• Indoor automatic address setting is started while
automatic address setting for equipment in other
refrigerant line is in progress.
• Outdoor automatic address setting is started
while automatic address setting for indoor units
is in progress.
Indoor unit fails to communicate while automatic
address setting for indoor units is in progress.
Combined capacity of indoor units is too large.
The maximum combined of indoor units shown in
the specification table.
There is no or more than one outdoor header unit
in one refrigerant line.
Indoor unit from other refrigerant line is detected
while indoor automatic address setting is in
progress.
Signal cannot be transmitted to other outdoor
units.
There is duplication in outdoor addresses set
manually.
Follower outdoor unit initially communicating
normally fails to do so (reduction in number of
follower outdoor units connected).
O
utdoor header unit detects trouble relating to
follower outdoor unit (detail displayed on follower
outdoor unit).
There is no communication between P.C. boards
in inverter box.
Outdoor discharge temperature sensor (TD1) has
been open/short-circuited.
Outdoor discharge temperature sensor (TD2) has
been open/short-circuited.
Outdoor heat exchanger liquid side temperature
sensors (TE1, TE2, TE3) have been open/
short-circuited.
Outdoor liquid temperature sensor (TL1,TL2,TL3)
has been open/short-circuited.
Outdoor air temperature sensor (TO) has been
open/short-circuited.
Outdoor heat exchanger gas side temperature
sensors (TG1, TG2, TG3) have been open/
short-circuited.