No.
Part name
Replacement of
9
temperature sensor
for servicing only
Common service
parts of sensor TO,
TS, TE, TGa, TGb,
TGc, TGd
(without TD)
These are parts for
servicing sensors.
Please check that
the accessories
shown in the right
table are packed.
Procedure
1) Cut the sensor 100 mm longer than old
one.
2) Cut the protective tube after pulling out
it (200 mm).
3) Move the protective tube toward the
thermal sensor side and tear the tip of
lead wire in two then strip the covering
part.
4) Pass the stripped part through the
thermal constringent tube.
5) Cut the old sensor 100 mm length on
the connector side, and recycle that
connector.
6) Tear the lead wire in two on the con-
nector side and strip the covering part.
7) Twist the leads on the connector and
sensor sides, and solder them.
8) Move the thermal constringent tubes
toward the soldered parts and heat
them with the dryer and constring
them.
9) Wind the attached color tape round the
both terminals of the protective tube
when colored protective tube is used.
10) Fix the sensor again.
1) Store the joint part of the sensor and the connector in the electric parts
box.
2) Never joint them near the thermal sensor part. Otherwise it would cause
insulation inferiority because of dew drops.
3) When replacing the sensor using the colored protective tube, wind the
color tape matching the color of that tube.
Parts name
1
Sensor
2
Sensor Spring (A)
3
Sensor Spring (B)
4
Thermal constringent tube
5
Color tape
6
Terminal
– 120 –
Remarks
Thermal
Connector
sensor part
200
Thermal
constringent tube
Cutting here
100
Soldered part
Winding the color tape
NOTE
Q'ty
1
Length : 3m
1
For spare
1
For spare
3
Including one spare
1
9 colors
3
Cutting here
100
Cutting here
Dryer
Remarks