Summary of Contents for Mitsubishi Electric MSZ-LN-VGW Series
Page 1
Revision D: • MUZ-LN25/35/50VG2- have been added. OBH767 REVISED EDITION-C is void. OUTDOOR UNIT No. OBH767 SERVICE MANUAL REVISED EDITION-D utilized Models MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG MUZ-LN25VG2 MUZ-LN35VG2 MUZ-LN50VG2 Indoor unit service manual MSZ-LN•VGW/V/B/R Series (OBH766) CONTENTS 1. TECHNICAL CHANGES ······························2 2.
Page 2
Use the specified refrigerant only Never use any refrigerant other than that specified. Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Page 3
SERVICING PRECAUTIONS FOR UNITS USING REFRIGERANT R32 Servicing precautions for units using refrigerant R32 WARNING This unit uses a flammable refrigerant. If refrigerant leaks and comes in contact with fire or heating part, it will create harmful gas and there is risk of fire. Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
Page 4
5. Detection of Flammable Refrigerants Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used. 6. Leak Detection Methods Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable refrigerants, the sensitivity may not be adequate, or may need re-calibration.
Page 5
PART NAMES AND FUNCTIONS MUZ-LN25VG MUZ-LN25VG2 MUZ-LN35VG MUZ-LN35VG2 Air inlet (Back and side) Piping Air outlet Drain hose Drain outlet MUZ-LN50VG MUZ-LN50VG2 MUZ-LN60VG Air inlet Air inlet (Back and side) (Back and side) Piping Piping Air outlet Drain hose Drain hose Air outlet Drain outlet Drain outlet...
Page 8
Specifications and rated conditions of main electric parts Model MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG Item (C62, C63) 600 µF/ 620 µF 420 V Smoothing capacitor (C61, C62, C63) 600 µF/ 620 µF 420 V (DB61) 15 A 600 V 25 A 600 V Diode module (DB65) 25A 600V...
Page 9
NOISE CRITERIA CURVES MUZ-LN25VG MUZ-LN25VG2 FUNCTION SPL(dB(A)) LINE FUNCTION SPL(dB(A)) LINE COOLING COOLING HEATING HEATING NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 NC-20 NC-20 NC-10 NC-10 1000 2000 4000 8000 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz MUZ-LN35VG MUZ-LN35VG2...
Page 10
MUZ-LN50VG MUZ-LN50VG2 FUNCTION SPL(dB(A)) LINE COOLING HEATING NC-70 NC-60 NC-50 NC-40 NC-30 NC-20 NC-10 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz MUZ-LN60VG FUNCTION SPL(dB(A)) LINE COOLING HEATING NC-70 NC-60 NC-50 Test conditions NC-40 Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C NC-30 OUTDOOR UNIT NC-20...
Page 11
OUTLINES AND DIMENSIONS MUZ-LN25VG MUZ-LN35VG Unit: mm MUZ-LN25VG2 MUZ-LN35VG2 OBH767D...
Page 12
MUZ-LN50VG Unit: mm MUZ-LN50VG2 OBH767D...
Page 13
MUZ-LN60VG Unit: mm REQUIRED SPACE *1. 500 mm or more when front and sides of the unit are clear 417.5 Air in Air in Air out 2-holes 10 21 *2. When any 2 sides of left, right and rear of the unit are clear Service panel Liquid refrigerant pipe joint Refrigerant pipe (flared)
Page 19
PERFORMANCE CURVES MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG MUZ-LN25VG2 MUZ-LN35VG2 MUZ-LN50VG2 The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi- tions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
Page 20
9-1. CAPACITY AND INPUT CURVES Cooling capacity (at Rated frequency) 10.4 11.4 Indoor intake air Wet-bulb 10.5 temperature( ) Outdoor intake air Dry-bulb temperature(°C) Total input (Cooling : at Rated frequency Indoor intake air Wet-bulb temperature( ) Outdoor intake air Dry-bulb temperature (°C) Heating capacity (at Rated frequency) 14.5...
Page 21
9-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR MUZ-LN25VG Correction of Cooling input Correction of Heating capacity Correction of Heating input Correction of Cooling capacity The operational frequency The operational frequency The operational frequency The operational frequency of compressor (Hz) of compressor (Hz) of compressor (Hz) of compressor (Hz)
Page 22
MUZ-LN50VG MUZ-LN50VG2 Correction of Heating input Correction of Cooling capacity Correction of Cooling input Correction of Heating capacity The operational frequency The operational frequency The operational frequency The operational frequency of compressor (Hz) of compressor (Hz) of compressor (Hz) of compressor (Hz) MUZ-LN60VG Correction of Cooling input Correction of Heating capacity...
Page 23
9-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation Dry-bulb temperature (°C) Relative humidity (%) Both indoor and outdoor unit are under the same temperature/ humidity condition. Operation: TEST RUN OPERATION (Refer to 8-3.) Outdoor low pressure MUZ-LN25VG MUZ-LN25VG2 (kgf/cm [Gauge])(MPa [Gauge]) (kgf/cm...
Page 25
PERFORMANCE DATA COOL operation a t Rated frequency MUZ-LN25VG CAPACITY: 2.5 kW SHF: 0.97 INPUT: 485 W OUTDOOR DB (°C) INDOOR INDOOR DB (°C) WB (°C) INPUT INPUT INPUT INPUT 2.94 2.32 0.79 2.81 2.22 0.79 2.70 2.13 0.79 2.60 2.05 0.79 3.06...
Page 26
PERFORMANCE DATA COOL operation a t Rated frequency MUZ-LN25VG CAPACITY: 2.5 kW SHF: 0.97 INPUT: 485 W OUTDOOR DB (°C) INDOOR INDOOR DB (°C) WB (°C) INPUT INPUT INPUT 2.45 1.94 0.79 2.25 1.78 0.79 2.08 1.64 0.79 2.58 1.73 0.67 2.40 1.61...
Page 27
PERFORMANCE DATA COOL operation a t Rated frequency MUZ-LN25VG2 CAPACITY: 2.5 kW SHF: 0.97 INPUT: 485 W OUTDOOR DB (°C) INDOOR INDOOR DB (°C) WB (°C) INPUT INPUT INPUT INPUT 2.94 2.32 0.79 2.81 2.22 0.79 2.70 2.13 0.79 2.60 2.05 0.79 3.06...
Page 28
PERFORMANCE DATA COOL operation a t Rated frequency MUZ-LN25VG2 CAPACITY: 2.5 kW SHF: 0.97 INPUT: 485 W OUTDOOR DB (°C) INDOOR INDOOR DB (°C) WB (°C) INPUT INPUT INPUT 2.45 1.94 0.79 2.25 1.78 0.79 2.08 1.64 0.79 2.58 1.73 0.67 2.40 1.61...
Page 29
PERFORMANCE DATA COOL operation a t Rated frequency MUZ-LN35VG CAPACITY: 3.5 kW SHF: 0.90 INPUT: 820 W OUTDOOR DB (°C) INDOOR INDOOR DB (°C) WB (°C) INPUT INPUT INPUT INPUT 4.11 2.96 0.72 3.94 2.84 0.72 3.78 2.72 0.72 3.64 2.62 0.72 4.29...
Page 30
PERFORMANCE DATA COOL operation a t Rated frequency MUZ-LN35VG CAPACITY: 3.5 kW SHF: 0.90 INPUT: 820 W OUTDOOR DB (°C) INDOOR INDOOR DB (°C) WB (°C) INPUT INPUT INPUT 3.43 2.47 0.72 3.15 2.27 0.72 2.91 2.09 0.72 3.61 2.16 0.60 3.36 2.02...
Page 31
PERFORMANCE DATA COOL operation a t Rated frequency MUZ-LN35VG2 CAPACITY: 3.5 kW SHF: 0.90 INPUT: 820 W OUTDOOR DB (°C) INDOOR INDOOR DB (°C) WB (°C) INPUT INPUT INPUT INPUT 4.11 2.96 0.72 3.94 2.84 0.72 3.78 2.72 0.72 3.64 2.62 0.72 4.29...
Page 32
PERFORMANCE DATA COOL operation a t Rated frequency MUZ-LN35VG2 CAPACITY: 3.5 kW SHF: 0.90 INPUT: 820 W OUTDOOR DB (°C) INDOOR INDOOR DB (°C) WB (°C) INPUT INPUT INPUT 3.43 2.47 0.72 3.15 2.27 0.72 2.91 2.09 0.72 3.61 2.16 0.60 3.36 2.02...
Page 33
PERFORMANCE DATA COOL operation a t Rated frequency MUZ-LN50VG MUZ-LN50VG2 CAPACITY: 5.0 kW SHF: 0.77 INPUT: 1380 W OUTDOOR DB (°C) INDOOR INDOOR DB (°C) WB (°C) INPUT INPUT INPUT INPUT 5.88 3.47 0.59 1104 5.63 3.32 0.59 1159 5.40 3.19 0.59 1214...
Page 34
PERFORMANCE DATA COOL operation a t Rated frequency MUZ-LN50VG MUZ-LN50VG2 CAPACITY: 5.0 kW SHF: 0.77 INPUT: 1380 W OUTDOOR DB (°C) INDOOR INDOOR DB (°C) WB (°C) INPUT INPUT INPUT 4.90 2.89 0.59 1352 4.50 2.66 0.59 1435 4.15 2.45 0.59 1490 5.15...
Page 35
PERFORMANCE DATA COOL operation a t Rated frequency MUZ-LN60VG CAPACITY: 6.1 kW SHF: 0.75 INPUT: 1790 W OUTDOOR DB (°C) INDOOR INDOOR DB (°C) WB (°C) INPUT INPUT INPUT INPUT 7.17 4.09 0.57 1432 6.86 3.91 0.57 1504 6.59 3.76 0.57 1575 6.34...
Page 36
PERFORMANCE DATA COOL operation a t Rated frequency MUZ-LN60VG CAPACITY: 6.1 kW SHF: 0.75 INPUT: 1790 W OUTDOOR DB (°C) INDOOR INDOOR DB (°C) WB (°C) INPUT INPUT INPUT 5.98 3.41 0.57 1754 5.49 3.13 0.57 1862 5.06 2.89 0.57 1933 6.28 2.83...
Page 37
PERFORMANCE DATA HEAT operation at Rated frequency MUZ-LN25VG CAPACITY: 3.2 kW INPUT: 580 W OUTDOOR WB (°C) INDOOR DB (°C) INPUT INPUT INPUT INPUT INPUT INPUT INPUT INPUT 1.60 2.02 2.43 2.85 3.26 3.68 4.06 4.48 1.50 1.92 2.30 2.72 3.10 3.52 3.90...
Page 38
ACTUATOR CONTROL MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG MUZ-LN25VG2 MUZ-LN35VG2 MUZ-LN50VG2 10-1. OUTDOOR FAN MOTOR CONTROL The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running. 5 seconds 15 seconds Compressor...
Page 39
SERVICE FUNCTIONS MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG MUZ-LN25VG2 MUZ-LN35VG2 MUZ-LN50VG2 11-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature <JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to 12-6.1) Defrost finish temperature (°C) Jumper wire MUZ-LN25/35/50VG MUZ-LN60VG...
Page 40
TROUBLESHOOTING MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG MUZ-LN25VG2 MUZ-LN35VG2 MUZ-LN50VG2 12-1. CAUTIONS ON TROUBLESHOOTING 1. Before troubleshooting, check the following 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for miswiring. 2. Take care of the following during servicing 1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
Page 41
12-2. FAILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (12-3.) disappears, the memorized failure details can be recalled. 1.
Page 42
2. Flow chart of the detailed outdoor unit failure mode recall function Operational procedure The outdoor unit might be abnormal. Check if outdoor unit is abnormal according to the following procedures. Make sure that the remote controller is set to the failure mode recall function. 1.
Page 43
NOTE: Blinking patterns of this mode differ from the ones of 3. Outdoor unit failure recall mode table TROUBLESHOOTING CHECK TABLE (12-3.). Indoor/outdoor Outdoor unit POWER lamp Abnormal point LED indication unit failure Condition Remedy failure mode (Indoor unit) (Failure mode/protection) (Outdoor P.C. board) mode recall recall function function None (Normal) —...
Page 44
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (12-3.). Indoor/outdoor Outdoor unit POWER lamp Abnormal point LED indication unit failure Condition Remedy failure mode (Indoor unit) (Failure mode/protection) (Outdoor P.C. board) mode recall recall function function 10-time blink Discharge temperature Temperature of discharge temperature • Refer to 12-5. "Check 2.5 seconds thermistor has been 50°C or less for of LEV".
Page 45
12-3. TROUBLESHOOTING CHECK TABLE Abnormal point/ Con- Symptom LED indication Condition Remedy dition Outdoor unit 1-time blink every Outdoor power sys- Overcurrent protection cut-out operates 3 consecutive times • Reconnect connector of compres- does not op- 2.5 seconds within 1 minute after the compressor gets started. sor.
Page 46
Abnormal point/ Con- Symptom LED indication Condition Remedy dition Outdoor unit 7-time blink Low discharge tem- Temperature of discharge temperature thermistor has been • Refer to 12-5. "Check of LEV". operates. 2.5 seconds OFF perature protection 50°C or less for 20 minutes. •...
Page 47
12-4. TROUBLESHOOTING CRITERION OF MAIN PARTS MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG MUZ-LN25VG2 MUZ-LN35VG2 MUZ-LN50VG2 Part name Check method and criterion Figure Defrost thermistor (RT61) Measure the resistance with a tester. Refer to 12-6. “Test point diagram and voltage”, 1. “Inverter P.C. Fin temperature board”, for the chart of thermistor.
Page 48
12-5. TROUBLESHOOTING FLOW A How to check inverter/compressor Disconnect the connector between the compressor and the power module (IC700). Check the voltage between terminals. See 12-5. “Check of open phase”. Are the voltages balanced? Replace the inverter P.C. board. See 12-5. “Check of compressor”.
Page 49
D Check of compressor winding ● Disconnect the connector between the compressor and the power module (IC700), and measure the resistance between the compressor terminals. <<Measurement point>> At 3 points BLK-WHT * Measure the resistance between the lead wires at 3 points. BLK-RED WHT-RED <<Judgement>> Refer to 12-4. 0 [Ω] ················Abnormal [short] Infinite [Ω] ·······Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement.
Page 50
G Check of outdoor thermistors Disconnect the connector of thermistor in the inverter P.C. board (see below table), and measure the resistance of thermistor. Replace the thermistor except RT64. Is the resistance of thermistor normal? When RT64 is abnormal, replace the inverter P.C. (Refer to 12-6.1.) board.
Page 51
H Check of R.V. coil MUZ-LN25/35/50VG MUZ-LN25/35/50VG2 * First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 12-4. * In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector although no signal is being transmitted to R.V.
Page 52
I Check of outdoor fan motor Disconnect the connectors CN931 and CN932 from the inverter P.C. board. Check the connection between the connector CN931 and CN932. Is the resistance between each ter- minal of outdoor fan motor normal? (Refer to 12-4.) Disconnect CN932 from the inverter P.C.
Page 53
J Check of power supply Disconnect the connector between the compressor and the power module (IC700). Turn ON power supply and Rectify indoor/outdoor press the emergency operation switch. connecting wire. Replace the indoor Is there voltage 230 V AC Does POWER lamp on the indoor between the indoor terminal electronic control P.C.
Page 54
MSZ-LN25/35VG K Check of LEV (Expansion valve) MSZ-LN50/60VG Turn ON the power supply. <Preparation of the remote controller> While pressing both Operation select button and TEMP button on the remote controller at the same time, press RESET button. First, release RESET button. Hold down the other 2 buttons for another 3 seconds.
Page 55
L Check of inverter P.C. board Check the outdoor fan motor. (Refer to 12-5. .) Is the fuse (F901) blown on the in- verter P.C. board? Check the connection of the connectors (CN931, CN932) of the outdoor fan motor. If the connection is poor, make it correct. Operate the outdoor unit by starting EMERGENCY OPERATION.
Page 56
M How to check miswiring and serial signal error Turn the power supply OFF. Is there rated voltage in the power supply? Check the power supply. Check for incorrect indoor-outdoor connecting wiring. Was the indoor unit ever connected to the Multi (MXZ) series and operated (turned on)? The connection information to the Multi series is stored in the indoor unit.
Page 57
N Check of the outdoor refrigerant circuit The operation has stopped to prevent the diesel explosion caused by air trapped in the refrigerant circuit. Close the stop Has the operation stopped during pump down? valve, and disconnect the power plug or turn the breaker OFF. CAUTION: Do not start the operation again to prevent hazards.
Page 58
O Electromagnetic noise enters into TV sets or radios Is the unit earthed? Earth the unit. Is the distance between the antennas Extend the distance between the antennas and and the indoor unit within 3 m, or is the the indoor unit, and/or the antennas and the distance between the antennas and the outdoor unit.
Page 59
12-6. TEST POINT DIAGRAM AND VOLTAGE 1. Inverter P.C. board MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN50VG2 Smoothing Smoothing Smoothing R.V. coil capacitor capacitor (CN721) capacitor DB61 Back side of unit (C63) (C62) (C61) 230 V AC 260 - 370 V DC Fuse (F701) (LN50) T3.15AL250V 230 VAC...
Page 60
MUZ-LN25VG2 MUZ-LN35VG2 R.V.coil Smoothing Smoothing (CN721) DB61 capacitor capacitor Back side of unit 230 V AC 260 - 370 V DC (C63) (C62) 230 V AC Fuse (F901) Fuse (F801) Fuse (F701) T3.15AL250V T3.15AL250V T3.15AL250V Fuse (F61) Fuse (F62) 25 A 250V 15 A 250 V Output to drive...
Page 61
MUZ-LN60VG Jumper wire for pre-heat control setting (JK) LEV (CN724) Jumper wire for changing defrost setting (JS) Ambient temperature thermistor/RT65 (CN672) Heater (CN601) Outdoor heat exchanger 230 V AC temperature thermistor R.V. coil (CN602) /RT68 (CN671) 230 V AC Discharge temperature thermistor/RT62 (CN671) Defrost thermistor...
Page 62
DISASSEMBLY INSTRUCTIONS <"Terminal with locking mechanism" Detaching points> The terminal which has the locking mechanism can be detached as shown below. There are 2 types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
Page 63
OPERATING PROCEDURE PHOTOS/FIGURES 2. Removing the inverter assembly and inverter P.C. Photo 4 Screw of the P.B. support board and the separator (1) Remove the cabinet and panels (refer to section 1). Screws of Screw of the heat sink (2) Disconnect the lead wire to the reactor and the following con- the terminal block support and the separator nectors:...
Page 64
OPERATING PROCEDURE PHOTOS/FIGURES 3. Removing R. V. coil Photo 7 (1) Remove the cabinet and panels (refer to section 1). Outdoor heat (2) Disconnect the following connectors: exchanger tempera- <Inverter P.C. board> ture thermistor CN721 (R.V. coil) (3) Remove the R.V. coil. Ambient tem- perature thermistor (Position refer to...
Page 65
OPERATING PROCEDURE PHOTOS/FIGURES 6. Removing the compressor and 4-way valve Photo 9 (1) Remove the cabinet and panels (refer to section 1). Discharge pipe Suction pipe brazed part brazed part (2) Remove the inverter assembly (refer to section 2). (3) Recover gas from the refrigerant circuit. NOTE: Recover gas from the pipes until the pressure gauge shows 0 kg/cm...
Page 66
13-2. MUZ-LN50VG MUZ-LN50VG2 NOTE: Turn OFF the power supply before disassembly. OPERATING PROCEDURE PHOTOS/FIGURES 1. Removing the cabinet Photo 1 Screws of the top panel (1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover.
Page 67
OPERATING PROCEDURE PHOTOS/FIGURES 2. Removing the inverter assembly and inverter P.C. Photo 3 Screw of the P.B. support board and the separator (1) Remove the cabinet and panels (refer to section 1). (2) Disconnect the lead wire to the reactor and the following con- Screw of the heat sink nectors: support and the separator...
Page 68
OPERATING PROCEDURE PHOTOS/FIGURES 3. Removing R. V. coil Photo 6 (1) Remove the cabinet and panels (refer to section 1). Screw of the R.V. coil (2) Disconnect the following connectors: <Inverter P.C. board> CN721 (R.V. coil) (3) Remove the R.V. coil. Discharge temperature thermistor Outdoor heat Photo 7...
Page 69
OPERATING PROCEDURE PHOTOS/FIGURES 6. Removing the compressor and 4-way valve Photo 9 (1) Remove the cabinet and panels (refer to section 1). Discharge pipe Suction pipe (2) Remove the inverter assembly (refer to section 2). brazed part brazed part (3) Recover gas from the refrigerant circuit. NOTE: Recover gas from the pipes until the pressure gauge shows 0 kg/cm...
Page 70
13-3. MUZ-LN60VG NOTE: Turn OFF the power supply before disassembly. OPERATING PROCEDURE PHOTOS/FIGURES 1. Removing the cabinet Photo 1 (1) Remove the screws of the service panel. Screws of the top panel (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover.
Page 71
OPERATING PROCEDURE PHOTOS/FIGURES 2. Removing the inverter assembly and inverter P.C. Photo 3 Screws of the relay panel board Inverter P.C board (1) Remove the cabinet and the service panel (refer to section 1). (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C.
Page 72
OPERATING PROCEDURE PHOTOS/FIGURES 3. Removing R.V. coil Photo 5 Screw of (1) Remove the cabinet and panels. (Refer to 1.) the R.V. coil (2) Disconnect the following connector: <Inverter P.C. board> CN602 (R.V. coil) (3) Remove the R.V. coil. Brazed parts of 4-way valve 4.
Page 73
OPERATING PROCEDURE PHOTOS/FIGURES 5. Removing outdoor fan motor Photo 7 (1) Remove the top panel, cabinet and service panel (refer to Propeller fan section1). (2) Disconnect the following connectors: <Inverter P.C. board> Propeller fan CN931, CN932 (Fan motor) (3) Remove the propeller fan nut. (4) Remove the propeller fan.