Industrial inverter for 3-phase induction motors (217 pages)
Summary of Contents for Toshiba RAV-GM1601ATP-E/TR
Page 1
TCTC-E20-LC001-6 Engineering Data Book Digital Inverter R32 6.0HP Light Commercial System Outdoor Units Indoor Units 4-way cassette type RAV-GM1601ATP-E / TR RAV-HM561UTP-E / TR RAV-GM1601ATJP-E RAV-HM801UTP-E / TR RAV-GM1601AT8P-E / TR RAV-HM1601UTP-E / TR RAV-GM1601AT8JP-E Compact 4-way cassette type RAV-HM561MUTP-E / TR Slim duct type RAV-HM561SDT-E / TR Standard ducted type...
Page 2
Engineering Data Book Digital Inverter R32, 6.0 HP Contents 1. Line up ..................1-1. Single Line-up ................1-2. Combination Pattern ..............2. Indoor Unit ..................4-way Cassette Type ............2-2 . Compact 4-way Type ..............2-3 ..
Page 3
Engineering Data Book Digital Inverter R32, 6.0 HP 1. Line up 1-1. Single Line-up Outdoor unit RAV-GM1601ATP-E / TR RAV-GM1601ATJP-E Model name RAV-GM1601AT8P-E / TR RAV-GM1601AT8JP-E Appearance 6 HP Indoor unit Capacity Type (kW equivalent) ** 4-way Cassette RAV-HM**01UTP Compact 4-way RAV-HM**01MUTP Slim Duct RAV-HM**01SDT...
Page 4
Engineering Data Book Digital Inverter R32, 6.0 HP 1-2. Combination Patterns Outdoor Unit Indoor Unit Capacity Phase Range (HP) Model name System 4-way Cassette Compact 4-way Slim duct Standard Duct Ceiling Hi-wall RAV-GM1601AT(J)P* RAV-HM1601UTP* RAV-HM1601BTP* RAV-HM1601CTP* Single system RAV-HM801UTP* RAV-HM801BTP* RAV-HM801CTP* RAV-HM801KRTP* Twin system...
Page 5
Engineering Data Book Digital Inverter R32, 6.0 HP 2. Indoor Units 2-1. 4-way Cassette Type 2-1-1. Specifications 2-1-2. Dimension 2-1-3. Wiring Diagrams 2-1-4. Sensible Capacity Table 2-1-5. Part Load Performance 2-1-6. Air Throw Distance Chart 2-1-7. Sound Characteristic (NC Curve) Accessories...
Page 6
Engineering Data Book Digital Inverter R32, 6.0 HP 2-1-1. Specifications 4-way Cassette Type Model Indoor unit RAV-HM1601UTP-E / TR RAV-HM1601UTP-E / TR Outdoor unit RAV-GM1601AT(J)P-E / ATP-TR RAV-GM1601AT8(J)P-E / AT8P-TR Cooling capacity (kW) 14.0 < 3.0 - 16.0 > 14.0 < 3.0 - 16.0 > Heating capacity (kW) 16.0 <...
Page 7
Engineering Data Book Digital Inverter R32, 6.0 HP 4-way Cassette Type Twin system : Single phase model Model Indoor unit 1 RAV-HM801UTP-E / TR Indoor unit 2 RAV-HM801UTP-E / TR Outdoor unit RAV-GM1601AT P-E / ATP-TR Cooling capacity 14.0 < 3.0 - 16.0 > (kW) Heating capacity 16.0 <...
Page 8
Engineering Data Book Digital Inverter R32, 6.0 HP 4-way Cassette Type Twin system : Three phase model Model Indoor unit 1 RAV-HM801UTP-E / TR Indoor unit 2 RAV-HM801UTP-E / TR Outdoor unit RAV-GM1601AT8 P-E / AT8P-TR Cooling capacity 14.0 < 3.0 - 16.0 > (kW) Heating capacity 16.0 <...
Page 9
Engineering Data Book Digital Inverter R32, 6.0 HP 4-way Cassette Type Triple system : Single phase model Model Indoor unit 1 RAV-HM561UTP-E / TR Indoor unit 2 RAV-HM561UTP-E / TR Indoor unit 3 RAV-HM561UTP-E / TR Outdoor unit RAV-GM1601AT P-E / ATP-TR Cooling capacity 14.0 <...
Page 10
Engineering Data Book Digital Inverter R32, 6.0 HP 4-way Cassette Type Triple system : Three phase model Model Indoor unit 1 RAV-HM561UTP-E / TR Indoor unit 2 RAV-HM561UTP-E / TR Indoor unit 3 RAV-HM561UTP-E / TR Outdoor unit RAV-GM1601AT8(J)P-E / AT8P-TR Cooling capacity (kW) 14.0 <...
Page 11
Engineering Data Book Digital Inverter R32, 6.0 HP 2-1-2. Dimension RAV-HM561UTP-E / TR Standard panel (RBC-U32PGP-E) 1000 or more 860 to 910 Ceiling open dimension An obstacle 1000 or more y r a for equipping and se rvice T ake-in port of wiring Bottom face of ceiling Indoor unit Bottom face of ceiling...
Page 12
Engineering Data Book Digital Inverter R32, 6.0 HP RAV-HM801UTP-E / TR Standard panel (RBC-U32PGP-E) 860 to 910 Ceiling open dimension 1000 or more An obstacle 1000 or more y r a for equipping and se rvice T ake-in port of wiring Bottom face of ceiling Indoor unit Bottom face of ceiling...
Page 13
Engineering Data Book Digital Inverter R32, 6.0 HP RAV-HM1601UTP-E / TR Standard panel (RBC-U32PGP-E) 1000 or more 860 to 910 Ceiling open dimension An obstacle 1000 or more The space that is necessary for equipping and service Take-in port of wiring Bottom face of ceiling Indoor unit Bottom face of ceiling...
Page 14
Engineering Data Book Digital Inverter R32, 6.0 HP RAV-HM561UTP-E / TR Smart design panel (RBC-U33P-E) 1000 or more 860 to 910 Ceilng open dimension An obstacle 1000 or more The space that is necessary for equipping and service Take-in port of wiring Bottom face of ceiling Bottom face of ceiling Indoor unit...
Page 15
Engineering Data Book Digital Inverter R32, 6.0 HP RAV-HM801UTP-E / TR Smart design panel (RBC-U33P-E) 1000 or more 860 to 910 Ceilng open dimension An obstacle 1000 or more The space that is necessary for equipping and service Take-in port of wiring Bottom face of ceiling Bottom face of ceiling Indoor unit...
Page 16
Engineering Data Book Digital Inverter R32, 6.0 HP RAV-HM1601UTP-E / TR Smart design panel (RBC-U33P-E) 1000 or more 860 to 910 Ceilng open dimension An obstacle 1000 or more The space that is necessary for equipping and service Take-in port of wiring Bottom face of ceiling Refrigerant pipe connecting port Drain pipe...
Page 17
Engineering Data Book Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Light Comercial SPI R32 2-1-3. Wiring Diagrams RAV-HM561UTP-E / TR, RAV-HM801UTP-E / TR, RAV-HM1601UTP-E / TR...
Page 18
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Engineering Data Book Light Comercial SPI R32 2- 1-4. Sensible Capacity Table RAV-HM1601UTP-E / TR : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR indoor air temp. outdoor 14.0CWB 15.0CWB...
Page 19
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-1-5. Part Load Performance Indoor Unit : RAV-HM1601UTP-E / TR Outdoor unit : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR Cooling Heating Capacity(W) Power consumption (W) Capacity(W) Power consumption (W) MINIMUM...
Page 20
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Twin system Indoor Unit : RAV-HM801UTP-E / TR (x2) Outdoor unit : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR Cooling Heating Capacity(W) Power consumption (W) Capacity(W) Power consumption (W) MINIMUM...
Page 21
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Triple system Indoor Unit : RAV-HM561UTP-E (x3) Outdoor unit : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR Cooling Heating Capacity(W) Power consumption (W) Capacity(W) Power consumption (W) MINIMUM 3000 3000...
Page 22
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2- 1-6. Air Throw Distance Chart RAV-HM561UTP-E / TR 2.8 m 0.7m/s 0.5m/s 0.3m/s Horizontal distance (m) RAV-HM801UTP-E / TR 3.0 m 0.7m/s 0.5m/s 0.3m/s Horizontal distance (m)
Page 23
Engineering Data Book Digital Inverter R32, 6.0 HP RAV-HM1601UTP-E/ TR 0.7m/s 0.5m/s 0.3m/s Horizonal distance (m) RAV-HM1601UTP-E / TR (High ceiling) 0.7m/s 0.5m/s 0.3m/s Horizontal distance (m)
Page 24
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-1-7. Sound characteristics (NC curve) 1.5m 1.5m RAV-HM561UTP-E / TR Sound pressure level (dB(A)) Sound pressure level (dB(A)) NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30...
Page 25
Engineering Data Book Digital Inverter R32, 6.0 HP RAV-HM1601UTP-E / TR Fan tap Sound pressure level (dB(A)) NC-70 NC-60 NC-50 NC-40 NC-30 NC-20 Approximate threshold of hearing for continuous noise 1000 2000 4000 8000 Octave band center frequency(Hz)
Page 26
Engineering Data Book Digital Inverter R32, 6.0 HP Accessories Optional parts for 4-Way Cassette type RBC-U32PGP-E Ceiling panel RBC-U33P-E Ceiling panel (smart design) RBC-U33PB-E Optional parts list Type Model name Qty/unit Note Ceiling panel RBC-U32PGP-E White (2.5GY9.0/0.5) Ceiling panel (Smart design) RBC-U33P-E White (5PB9/1) Ceiling panel (Smart design)
Page 27
Engineering Data Book Digital Inverter R32, 6.0 HP Appendix 1. Fresh-air chamber (TCB-GFC1602UE) Unit : mm Refrigerant pipe connecting port (Liquid) Refrigerant pipe Drain pipe connecting port connecting port (Gas) Ceiling bottom surface 1000 or more 1000 or more Space required for installation...
Page 28
Engineering Data Book Digital Inverter R32, 6.0 HP 2. Fresh-air inlet box (TCB-GB1602UE) Accessories Installation (The following parts are included.) (Fig. 1) Name Remark Shield plate for box (6) Heat insulating (Remove) material B Outside air introduction port Outside air (5) Heat insulating material A introduction port...
Page 29
Engineering Data Book Digital Inverter R32, 6.0 HP 3. Auxiliary fresh air flange (TCB-FF101URE2) Installation Duct fan 1. Using the knockout of the indoor unit main body, as a In order to take fresh air, provide the duct fan marker, cut off the flange with the heat insulator separately.
Page 30
Engineering Data Book Digital Inverter R32, 6.0 HP 4. Fresh Air Intake Usage Fresh air is taken by using Fresh-air chamber and Fresh-air inlet box. And also is subsidiarily taken by using Auxiliary fresh air flange through the knock-out hole of the indoor unit body. Caution 1.
Page 31
Engineering Data Book Digital Inverter R32, 6.0 HP 5. Spacer for height adjustment (TCB-SP1602UE) Unit : mm Refrigerant pipe connecting port (Liquid) Drain pipe connecting port Refrigerant pipe connecting port (Gas) Ceiling bottom surface Material : Styrene foam Color : Moon white Space required for installation...
Page 32
Engineering Data Book Digital Inverter R32, 6.0 HP 6. Air discharge direction kit (TCB-BC1602UE) Limited models only Wind shield A 3-way air flow Wind shield C Available only for Available only for Available for all models Available for all models 110 to 160 56 to 80 type type...
Page 33
Engineering Data Book Digital Inverter R32, 6.0 HP 2-2. Compact 4-way Type 2-2-1. Specifications 2-2-2. Dimension 2-2-3. Wiring Diagrams 2-2-4. Sensible Capacity Table 2-2-5. Part Load Performance 2-2-6. Air Throw Distance Chart 2-2-7. Sound Characteristics (NC Curve) Accessories...
Page 34
Engineering Data Book Digital Inverter R32, 6.0 HP 2-2-1. Specifications Compact 4-way Type Triple system : Single phase model Indoor unit 1 RAV-HM561MUTP-E / TR Indoor unit 2 RAV-HM561MUTP-E / TR Model Indoor unit 3 RAV-HM561MUTP-E / TR Outdoor unit RAV-GM1601AT(J)P-E / ATP-TR Cooling capacity (kW)
Page 35
Engineering Data Book Digital Inverter R32, 6.0 HP Compact 4-way Type Triple system : Three phase model Indoor unit 1 RAV-HM561MUTP-E / TR Indoor unit 2 RAV-HM561MUTP-E / TR Model Indoor unit 3 RAV-HM561MUTP-E / TR Outdoor unit RAV-GM1601AT8(J)P-E / ATP-TR Cooling capacity (kW) 14.0 <...
Page 36
Engineering Data Book Digital Inverter R32, 6.0 HP 2-2-2. Dimension RAV-HM561MUTP-E / TR...
Page 37
Engineering Data Book Digital Inverter R32, 6.0 HP 2-2-3. Wiring Diagrams RAV-HM561MUTP-E / TR...
Page 38
Engineering Data Book Digital Inverter R32, 6.0 HP 2- 2-4. Sensible Capacity Table RAV-HM561MUTP-E / TR (Triple) ; RAV-GP160AT(J)P-E / ATP-TR, RAV-GP1601AT8(J)P-E / AT8P-TR Specification of product at standard condition. Standard Condition 5.00 Indoor Total Cooling Capacity (TC) 27.0 C DB / 19.0 C WB Outdoor Sensible Heat Capacity (SHC)
Page 39
Engineering Data Book Digital Inverter R32, 6.0 HP 2-2-5. Part Load Performance Combination Indoor Unit : RAV-HM561MUTP-E / TR (x3) Outdoor unit : RAV-GM1601AT(J)P-E / ATP-TR, RA V-GM1601AT8(J)P-E / AT8P-TR Cooling Heating Capacity(W) Power consumption (W) Capacity(W) Power consumption (W) MINIMUM 3000 3000...
Page 40
Engineering Data Book Digital Inverter R32, 6.0 HP 2-2-6. Air Throw Distance Chart RAV-HM561MUTP-E / TR RAV-HM561MUT-E / TR (High Ceiling mode 1)
Page 41
Engineering Data Book Digital Inverter R32, 6.0 HP RAV-HM561MUT-E / TR (High Ceiling mode 3)
Page 42
Engineering Data Book Digital Inverter R32, 6.0 HP 2-2-7. Sound characteristics (NC curve) RAV-HM561MUTP-E/TR Cooling Specification (dB) Fan tap Sound pressure level (dB(A)) NC-70 NC-60 NC-50 NC-40 NC-30 NC-20 Minimum 20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000 Octave band center frequency (Hz) Heating Specification (dB)...
Page 43
Engineering Data Book Digital Inverter R32, 6.0 HP Accessoreis Compact 4way panel RBC-UM21P-E Auxiliary fresh air flange (White) RBC-UM21PB-E Compact 4way panel (Black) Type Model Name Qty/unit 1.1 Compact 4way panel (White) RBC-UM21P-E 1.2 Compact 4way panel (Black) RBC-UM21PB-E Auxiliary fresh air flange TCB-FF101URE2 Wireless RC (White) RBC-AXU31UMP-E...
Page 44
Engineering Data Book Digital Inverter R32, 6.0 HP Appendix 1.Ceiling Panel 1.1 Compact 4way panel (white) : RBC-UM21P-E Refrigerant piping Drain piping corner Electrical control box Panel xed screw Hanging section Engraved mark of tentative “REF. PIPE SIDE” hanging hook 4 direction-free for air inlet grille Engraved mark “DRAIN SIDE”...
Page 45
Engineering Data Book Digital Inverter R32, 6.0 HP 1.2 Compact 4way panel (Black) : RBC-UM21PB-E Refrigerant piping Drain piping corner Electrical control box Panel xed screw Hanging section Engraved mark of tentative “REF. PIPE SIDE” hanging hook 4 direction-free for air inlet grille Engraved mark “DRAIN SIDE”...
Page 46
Engineering Data Book Digital Inverter R32, 6.0 HP 2.Auxiliary fresh air flange : TCB-FF101URE2 Installation Duct fan 1. Using the knockout of the indoor unit main body, as a In order to take fresh air, provide the duct fan marker, cut off the flange with the heat insulator separately.
Page 47
Engineering Data Book Digital Inverter R32, 6.0 HP Caution The fresh air shall be conditioned by a heat reclaim ventilator or similar. Ensure the fresh air volume is determined so that mixed suction air and fresh air can maintain the operating temperature.
Page 48
Engineering Data Book Digital Inverter R32, 6.0 HP Branching duct (design guide) Cover method Piping side Branching Duct Install the cover Drain pump side Dimension Be sure to cover the air discharge port...
Page 49
Engineering Data Book Digital Inverter R32, 6.0 HP 3.Remote controller 3.1 Wireless RC (White / Black) : RBC-AXU31UMP-E / RBC-AXU31UMPB-E Auto louver button (SWING) Press this button to swing the louver. (A receiving beep is heard.) Press the SWING button to stop the louver swinging.
Page 50
Engineering Data Book Digital Inverter R32, 6.0 HP Louvers position A position of the individual louvers (four directions) can be locked. SET DATA 0001 0002 0003 0004 0005 * When (4) or (5) is selected, dew drop may occur during cooling mode. Refrigerant Drain pipe pipe...
Page 51
Engineering Data Book Digital Inverter R32, 6.0 HP 3.3 Wired remote controller : RBC-AMTU31-E Operations Changing the fan speed Push the button to select a fan speed. • Each time you push the button, fan speed and its indication change in the following order: (“...
Page 52
Engineering Data Book Digital Inverter R32, 6.0 HP 3.4 Premium wired remote controller with/without bluetooth : RBC-AWSU52-E / RBC-AMSU52-E Operating LED Lights while operating. Temperature sensor Model name label * The screens shown here are examples. The content that is displayed may differ, depending on the environment settings being used.
Page 53
Engineering Data Book Light Comercial SPI R32 Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-3. Slim Duct Type 2-3-1. Specifications 2-3-2. Dimension 2-3-3. Wiring Diagrams 2-3-4. Sensible Capacity Table 2-3-5. Part Load Performance 2-3-6.
Page 54
Engineering Data Book Digital Inverter R32, 6.0 HP 2-3-1. Specifications Slim Duct Type Tripple system : Single phase model Model Indoor unit 1 RAV-HM561SDT-E / TR Indoor unit 2 RAV-HM561SDT-E / TR Indoor unit 3 RAV-HM561SDT-E / TR Outdoor unit RAV-GM1601AT(J)P-E / ATP-TR Cooling capacity (kW)
Page 55
Engineering Data Book Digital Inverter R32, 6.0 HP Slim Duct Type Tripple system : Three phase model Model Indoor unit 1 RAV-HM561SDT-E / TR Indoor unit 2 RAV-HM561SDT-E / TR Indoor unit 2 RAV-HM561SDT-E / TR Outdoor unit RAV-GM1601AT8(J)P-E / AT8P-TR Cooling capacity (kW) 14.0 <...
Page 56
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-3-2. Dimension RAV-HM561SDT-E / TR...
Page 57
Engineering Data Book Digital Inverter R32, 6.0 HP 2-3-3. Wiring Diagrams RAV-HM561SDT-E / TR...
Page 58
Engineering Data Book Engineering Data Book Engineering Data Book Light Comercial SPI R32 Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2- 3-4. Sensible Capacity Table RAV-HM561SDT-E / TR (Triple) : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR indoor air temp. outdoor 14.0CWB 15.0CWB...
Page 59
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-3-5. Part Load Performance Combination Indoor Unit : RAV-HM561SDT-E / TR (x3) Outdoor unit : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR Cooling Heating Capacity(W) Power consumption (W) Capacity(W) Power consumption (W)
Page 60
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Fan Static Characteristics 2-3-6. RAV-HM561SDT-E/TR Standard air volume : 780m³/h High (50Pa) Upper limit of external static pressure(50Pa) Lower limit of external static pressure (50Pa) High (35Pa) Upper limit of...
Page 61
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-3-7. Sound characteristics (NC curve) RAV-HM561SDT-E / TR [Measuring location] Under air intake Duct Air outlet Center 1.5m Air inlet Microphone [External static pressure 10Pa] [External static pressure 20Pa] Fan tap Fan tap...
Page 62
Engineering Data Book Digital Inverter R32, 6.0 HP 2-4. Duct type 2-4-1. Specifications 2-4-2. Dimension 2-4-3. Wiring Diagrams 2-4-4. Sensible Capacity Table 2-4-5. Part Load Performance 2-4-6. Fan Static Characteristics 2-4-7. Sound Characteristics (NC Curve) Accessories...
Page 63
Engineering Data Book Digital Inverter R32, 6.0 HP 2-4-1. Specifications Standard Duct Type Model Indoor unit RAV-HM1601BTP-E / TR RAV-HM1601BTP-E / TR Outdoor unit RAV-GM1601AT(J)P-E / ATP-TR RAV-GM1601AT8(J)P-E / AT8P-TR Cooling capacity (kW) 14.0 < 3.0 - 16.0 > 14.0 < 3.0 - 16.0 > Heating capacity (kW) 16.0 <...
Page 64
Engineering Data Book Digital Inverter R32, 6.0 HP Standard Duct Type Twin system : Single phase model Model Indoor unit 1 RAV-HM801BTP-E / TR Indoor unit 2 RAV-HM801BTP-E / TR Outdoor unit RAV-GM1601AT(J)P-E / ATP-TR Cooling capacity (kW) 14.0 < 3.0 - 16.0 > Heating capacity (kW) 16.0 <...
Page 65
Engineering Data Book Digital Inverter R32, 6.0 HP Standard Duct Type Twin system : Three phase model RAV-HM801BTP-E / TR Model Indoor unit 1 RAV-HM801BTP-E / TR Indoor unit 2 RAV-GM1601A8(J)P-E / AT8P-TR Outdoor unit 14.0 < 3.0 - 16.0 > (kW) Cooling capacity 16.0 <...
Page 66
Engineering Data Book Digital Inverter R32, 6.0 HP Standard Duct Type Triple system : Single phase model RAV-HM561BTP-E / TR Model Indoor unit 1 RAV-HM561BTP-E / TR Indoor unit 2 RAV-HM561BTP-E / TR Indoor unit 3 RAV-GM1601AT(J)P-E / ATP-TR Outdoor unit 14.0 <...
Page 67
Engineering Data Book Digital Inverter R32, 6.0 HP Standard Duct Type Triple system : Three phase model Model Indoor unit 1 RAV-HM561BTP-E / TR Indoor unit 2 RAV-HM561BTP-E / TR Indoor unit 3 RAV-HM561BTP-E / TR Outdoor unit RAV-GM1601AT8(J)P-E / AT8P-TR Cooling capacity (kW) 14.0 <...
Page 68
Engineering Data Book Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Light Comercial SPI R32 2-4-2. Dimension RAV-HM561BTP-E / TR, RAV-HM801BTP-E / TR, RAV-HM1601BTP-E / TR HM56 type HM80 type HM160 type HM56 type HM80 type HM160 type...
Page 69
Engineering Data Book Engineering Data Book Engineering Data Book Light Comercial SPI R32 Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP HM56 type HM80 type HM160 type...
Page 70
Engineering Data Book Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Light Comercial SPI R32 2-4-3. Wiring Diagrams RAV-HM561BTP-E / TR, RAV-HM801BTP-E / TR, RAV-HM1601BTP-E / TR...
Page 71
Engineering Data Book Digital Inverter R32, 6.0 HP 2- 4-4. Sensible Capacity Table RAV-HM1601BTP-E / TR : RAV-GP1601AT(J)P-E / ATP-TR, RAV-GP1601AT8(J)P-E / AT8P-TR indoor air temp. outdoor 14.0CWB 15.0CWB 16.0CWB 17.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB unit 20.0CDB 21.5CDB 23.0CDB 24.5CDB 26.0CDB 27.0CDB...
Page 72
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Engineering Data Book Light Comercial SPI R32 2-4-5. Part load performance Indoor Unit : RAV-HM1601BTP-E / TR Outdoor unit : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR Cooling Heating Capacity(W)
Page 73
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Engineering Data Book Light Comercial SPI R32 Twin system Indoor Unit : RAV-HM801BTP-E / TR (x2) Outdoor unit : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR Cooling Heating Capacity(W)
Page 74
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Engineering Data Book Light Comercial SPI R32 Triple system Indoor Unit : RAV-HM561BTP-E / TR (x3) Outdoor unit : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR Cooling Heating Capacity(W)
Page 75
Engineering Data Book Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Light Comercial SPI R32 Fan Static Characteristics 2-4-6. RAV-HM561BTP-E / TR Standard air volume: 800 m³/h Lower limit of High tap(120Pa) Upper limit of external static external static...
Page 76
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP RAV-HM1601BTP-E / TR Standard air volume: 2100 m³/h Upper limit of Lower limit of external static external static High tap(120Pa) pressure (120Pa) pressure (120Pa) High tap(100Pa) High tap(80Pa) Upper limit of...
Page 77
Engineering Data Book Engineering Data Book Light Comercial SPI R32 Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-4-7. Sound characteristics (NC curve) RAV-HM561BTP-E / TR External static pressure 30Pa External static pressure 40Pa Sound pressure level (dB(A)) Sound pressure level (dB(A)) NC-50 NC-50...
Page 78
Engineering Data Book Light Comercial SPI R32 Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP RAV-HM561BTP-E / TR External static pressure 80Pa External static pressure 100Pa Sound pressure level (dB(A)) Sound pressure level (dB(A)) NC-50 NC-50 NC-40...
Page 79
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Engineering Data Book Light Comercial SPI R32 RAV-HM801BTP-E / TR External static pressure 30Pa External static pressure 40Pa Sound pressure level (dB(A)) Sound pressure level (dB(A)) NC-50 NC-50 NC-40...
Page 80
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP RAV-HM801BTP-E / TR External static pressure 80Pa External static pressure 100Pa Sound pressure level (dB(A)) Sound pressure level (dB(A)) NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 NC-20 NC-20...
Page 81
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Engineering Data Book Light Comercial SPI R32 RAV-HM1601BTP-E / TR External static pressure 30Pa External static pressure 40Pa Sound pressure level (dB(A)) Sound pressure level (dB(A)) NC-50 NC-50 NC-40...
Page 82
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Engineering Data Book Light Comercial SPI R32 RAV-HM1601BTP-E / TR External static pressure 80Pa External static pressure 100Pa Sound pressure level (dB(A)) Sound pressure level (dB(A)) NC-50 NC-50 NC-40...
Page 83
Engineering Data Book Digital Inverter R32, 6.0 HP Accessories Option Parts Model Name Applicable FCU Auxiliary fresh air flange TCB-FF151US-E For Duct type Zoning duct flange TCB-SF56C6BPE For Duct type TCB-SF80C6BPE For Duct type TCB-SF160C6BPE For Duct type Auxiliary fresh air ange TCB-FF151US-E...
Page 84
Engineering Data Book Digital Inverter R32, 6.0 HP Appendix Zoning duct flange Zoning duct flange Zoning duct flange Remove the square flange for duct Remove the square Remove the square flange for duct Remove the screws. flange for duct Remove the screws. Remove the screws.
Page 85
Engineering Data Book Digital Inverter R32, 6.0 HP Auxiliary fresh air flange (TCB-FF151US-E) Arrange a flexible duct (locally procured). It is necessary to install auxiliary fresh air flange. INSTALLATION PROCEDURE 1 Using the knockout of the indoor unit, as a marker, cut off the steel plate with cutting pliers or cutter. 2 Install the auxiliary fresh air flange to the indoor unit with attached 4 fixing screws.
Page 86
Engineering Data Book Digital Inverter R32, 6.0 HP 2-5. Ceiling Type 2-5-1. Specifications 2-5-2. Dimension 2-5-3. Wiring Diagrams 2-5-4. Sensible Capacity Table 2-5-5. Part Load Performance 2-5-6. Air Throw Distance Chart 2-5-7. Sound Characteristics (NC Curve) Accessories...
Page 87
Engineering Data Book Digital Inverter R32, 6.0 HP 2-5-1. Specifications Ceiling Type Model Indoor unit RAV-HM1601CTP-E / TR RAV-HM1601CTP-E / TR Outdoor unit RAV-GM1601AT(J)P-E / ATP-TR RAV-GM1601AT8(J)P-E/ AT8P-TR Cooling capacity (kW) 14.0 < 3.0 - 16.0 > 14.0 < 3.0 - 16.0 > Heating capacity (kW) 16.0 <...
Page 88
Engineering Data Book Digital Inverter R32, 6.0 HP Ceilling Type Twin system : Single phase model Model Indoor unit 1 RAV-HM801CTP-E / TR RAV-HM801CTP-E / TR Indoor unit 2 Outdoor unit RAV-GM1601AT(J)P-E / ATP-TR Cooling capacity 14.0 < 3.0 - 16.0 > (kW) Heating capacity 16.0 <...
Page 89
Engineering Data Book Digital Inverter R32, 6.0 HP Ceiling Type Twin system : Three phase model RAV-HM801CTP-E / TR Model Indoor unit 1 RAV-HM801CTP-E / TR Indoor unit 2 RAV-GM1601AT8(J)P-E / AT8P-TR Outdoor unit 14.0 < 3.0 - 16.0 > Cooling capacity (kW) 16.0 <...
Page 90
Engineering Data Book Digital Inverter R32, 6.0 HP Ceiling Type Triple system : Single phase model Model Indoor unit 1 RAV-HM561CTP-E / TR Indoor unit 2 RAV-HM561CTP-E / TR Indoor unit 3 RAV-HM561CTP-E / TR Outdoor unit RAV-GM1601AT(J)P-E / ATP-TR Cooling capacity (kW) 14.0 <...
Page 91
Engineering Data Book Digital Inverter R32, 6.0 HP Ceiling Type Triple system : Three phase model Model Indoor unit 1 RAV-HM561CTP-E / TR Indoor unit 2 RAV-HM561CTP-E / TR Indoor unit 3 RAV-HM561CTP-E / TR Outdoor unit RAV-GM1601AT8(J)P-E / AT8P-TR Cooling capacity (kW) 14.0 <...
Page 92
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Engineering Data Book Light Comercial SPI R32 2-5-2. Dimension RAV-HM561CTP-E / TR...
Page 93
Engineering Data Book Engineering Data Book Engineering Data Book Light Comercial SPI R32 Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP RAV-HM801CTP-E / TR...
Page 94
Engineering Data Book Engineering Data Book Engineering Data Book Light Comercial SPI R32 Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP RAV-HM1601CTP-E / TR...
Page 95
Engineering Data Book Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Light Comercial SPI R32 2-5-3. Wiring Diagrams RAV-HM561CTP-E / TR, RAV-HM801CTP-E / TR, RAV-HM1601CTP-E / TR...
Page 96
Engineering Data Book Digital Inverter R32, 6.0 HP 2- 5-4. Sensible Capacity Table RAV-HM1601CTP-E / TR : RAV-GP1601AT(J)P-E / ATP-TR, RAV-GP1601AT8(J)P-E / AT8P-TR indoor air temp. outdoor 14.0CWB 15.0CWB 16.0CWB 17.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB unit air temp. 20.0CDB 21.5CDB 23.0CDB 24.5CDB...
Page 97
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-5-5. Part load performance Indoor unit : RAV-HM1601CTP-E / TR Outdoor unit : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR Cooling Heating Capacity(W) Power consumption (W) Capacity(W) Power consumption (W) MINIMUM...
Page 98
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Twin system Indoor unit : RAV-HM801CTP-E / TR (x2) Outdoor unit : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR Cooling Heating Capacity(W) Power consumption (W) Capacity(W) Power consumption (W) MINIMUM...
Page 99
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Triple system Indoor unit : RAV-HM561CTP-E / TR (x3) Outdoor unit : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR Cooling Heating Capacity(W) Power consumption (W) Capacity(W) Power consumption (W) MINIMUM...
Page 100
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-5-6. Air Throw Distance Chart RAV-HM561CTP-E / TR Cooling (Louver position : F2) 3.0m/s 2.5m/s 2.0m/s 1.5m/s 0.5m/s 1.0m/s 0.5m/s Fan tap H initial rate : 3.2 m/s Horizontal distance (m) Heating...
Page 101
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP RAV-HM801CTP-E / TR Cooling (Louver position : F2) 3.0m/s 2.0m/s 2.5m/s 1.5m/s 0.5m/s 1.0m/s 0.5m/s Fan tap H initial rate : 3.8 m/s Horizontal distance (m) Heating (Louver position : F5) 3.0m/s...
Page 102
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP RAV-HM1601CTP-E / TR Cooling (Louver position : F2) 3.0m/s 2.5m/s 2.0m/s 1.5m/s 0.5m/s 1.0m/s Fan tap H 0.5m/s initial rate : 4.2 m/s Horizontal distance (m) Heating (Louver position : F5) 3.0m/s...
Page 103
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-5-7. Sound Characteristics (NC curve) RAV-HM561CTP-E / TR Sound pressure level (dB(A)) NC-70 NC-60 NC-50 NC-40 NC-30 NC-20 Approximate threshold of hearing for continuous noise 1000 2000 4000...
Page 104
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP RAV-HM1601CTP-E / TR Sound pressure level (dB(A)) NC-70 NC-60 NC-50 NC-40 NC-30 Approximate threshold of NC-20 hearing for continuous noise 500 1000 2000 4000 8000 Octave band frequency (Hz)
Page 105
Engineering Data Book Digital Inverter R32, 6.0 HP Accessories 8. Air speed distribution 40VK0__*S-8S-TEE ( *03 / 05 ) l l o t i k RBC-AXU31C-E All Model Drain pump kit TCB-DP31CE ntibacterial glass is built into Drain pump kit All Model High wind : 3.8m/s Elbow piping kit...
Page 106
Engineering Data Book Digital Inverter R32, 6.0 HP Appendix 8. Air speed distribution Drain pump kit : TCB-DP31CE Attached with screw 40VK0__*S-8S-TEE ( *03 / 05 ) (Drain pump kit bracket) Drain pump kit High wind : 3.8m/s Mid wind : 2.8m/s Low wind : 2.5m/s High Attached with screw...
Page 107
Engineering Data Book Digital Inverter R32, 6.0 HP Option Connecting Kit : TCB-PCUC2E 8. Air speed distribution (1) Application control kit 40VK0__*S-8S-TEE ( *03 / 05 ) (3) Card edge spacer Cord clamp High wind : 3.8m/s (accessories) Mid wind : 2.8m/s Low wind : 2.5m/s High Horizontal throw (m)
Page 108
Engineering Data Book Digital Inverter R32, 6.0 HP Engineering Data Book Super Digital Inverter Auxiliary outside air flange : TCB-FF101URE2 8. Air speed distribution Name Q’ty 40VK0__*S-8S-TEE ( *03 / 05 ) Auxiliary fresh air flange 100 mm High wind : 3.8m/s Mid wind : 2.8m/s Low wind : 2.5m/s High...
Page 109
Engineering Data Book Light Comercial SPI R32 Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-6. High Wall Type 2-6-1. Specifications 2-6-2. Dimension 2-6-3. Wiring Diagrams 2-6-4. Sensible Capacity Table 2-6-5. Part Load Performance 2-6-6.
Page 110
Engineering Data Book Digital Inverter R32, 6.0 HP 2-6-1. Specifications High Wall Type Twin system : Single phase model Model Indoor unit 1 RAV-HM801KRTP-E / TR Indoor unit 2 RAV-HM801KRTP-E / TR Outdoor unit RAV-GM1601AT(J)P-E / ATP-TR Cooling capacity (kW) 14.0 <...
Page 111
Engineering Data Book Digital Inverter R32, 6.0 HP High Wall Type Twin system : Three phase model RAV-HM801KRTP-E / TR Model Indoor unit 1 RAV-HM801KRTP-E / TR Indoor unit 2 RAV-GM1601AT8(J)P-E / AT8P-TR Outdoor unit 14.0 < 3.0 - 16.0 > Cooling capacity (kW) 16.0 <...
Page 112
Engineering Data Book Digital Inverter R32, 6.0 HP High Wall Type Triple system : Single phase model RAV-HM561KRTP-E / TR Model Indoor unit 1 RAV-HM561KRTP-E / TR Indoor unit 2 RAV-HM561KRTP-E / TR Indoor unit 2 Outdoor unit RAV-GM1601AT(J)P-E / ATP-TR Cooling capacity 14.0 <...
Page 113
Engineering Data Book Digital Inverter R32, 6.0 HP High Wall Type Triple system : Three phase model RAV-HM561KRTP-E / TR Model Indoor unit 1 RAV-HM561KRTP-E / TR Indoor unit 2 RAV-HM561KRTP-E / TR Indoor unit 3 RAV-GM1601AT8(J)P-E / AT8P-TR Outdoor unit 14.0 <...
Page 114
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-6-2. Dimension RAV-HM561KRTP-E / TR, RAV-HM801KRTP-E / TR 1050 Air Inlet Air Filter Front Panel Grille Inlet Heat Exchanger Air Outlet Knock Out System Knock Out System Wireless remote controller 50 71.5...
Page 115
Engineering Data Book Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Light Comercial SPI R32 2-6-3. Wiring Diagrams RAV-HM561KRTP-E / TR, RAV-HM801KRTP-E / TR...
Page 116
Engineering Data Book Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Light Comercial SPI R32 2- 6-4. Sensible Capacity Table RAV-HM801KRTP-E / TR (Twin) : RAV-GP1601AT(J)P-E / ATP-TR, RAV-GP1601AT8(J)P-E / AT8P-TR indoor air temp. outdoor 14.0CWB 15.0CWB...
Page 117
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-6-5. Part Load Performance Twin system Indoor Unit : RAV-HM801KRTP-E / TR (x2) Outdoor unit : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR Cooling Heating Capacity(W) Power consumption (W) Capacity(W)
Page 118
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Triple system Indoor Unit : RAV-HM561KRTP-E / TR (x3) Outdoor unit : RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR Cooling Heating Capacity(W) Power consumption (W) Capacity(W) Power consumption (W) MINIMUM...
Page 119
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2- 6-6. Air Throw Distance Chart RAV-HM561KRTP-E / TR Cooling Heating...
Page 120
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP RAV-HM801KRTP-E / TR Cooling Heating...
Page 121
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 2-6-7. Sound characteristics (NC curve) RAV-HM561KRTP-E / TR Specification (dB) ~ ~ ~ ~ ~ ~ ~ ~ (Hz) Specification (dB) ~ ~ ~ ~...
Page 122
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP RAV-HM801KRTP-E / TR Specification (dB) ~ ~ ~ ~ ~ ~ ~ ~ (Hz) Specification (dB) ~ ~ ~ ~ ~ ~ ~ ~ (Hz)...
Page 123
Engineering Data Book Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Light Comercial SPI R32 3. Outdoor Unit 3-1. Specifications 3-2. Dimension 3-3. Wiring Diagrams 3-4. Refrigerant Cycle Diagram 3-5. Sound Characteristic 3-6.
Page 124
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 3-1 Specification Model name Outdoor unit RAV-GM1601AT(J)P-E / ATP-TR 1 phase 220-240v, 50Hz Power supply 1 phase 220v, 60Hz (Power exclusive to outdoor is required.) Type Hermetic compressor Compressor...
Page 125
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP RAV-GM1601AT8P-E Model name Outdoor unit RAV-GM1601AT8JP-E 3 phase 380-415V 50Hz Power supply (Power exclusive to outdoor is required.) Type Hermetic compressor Compressor Motor (kW) 3.75 Pole Refrigerant charged...
Page 126
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Model name Outdoor unit RAV-GM1601AT8P-TR 3 phase 380-415V 50Hz Power supply (Power exclusive to outdoor is required.) Type Hermetic compressor Compressor Motor (kW) 3.75 Pole Refrigerant charged (kg)
Page 127
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP 3-2. Dimension RAV-GM1601AT(J)P-E / ATP-TR, RAV-GM1601AT8(J)P-E / AT8P-TR...
Page 128
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Light Comercial SPI R32 3-3. Wiring diagrams RAV-GM1601AT(J)P- E / ATP-TR, RAV-GM1601AT8(J)P- E / AT8P-TR...
Page 129
Engineering Data Book Digital Inverter R32, 6.0 HP 3-4. Refrigerant cycle diagram Indoor unit Single type ( combination of 1 indoor unit and 1 out door unit ) (Indoor unit) Distributor (Strainer incorporated) TCJ sensor Strainer Air heat exchanger TC sensor Heating Cooling Refrigerant pipe...
Page 130
Engineering Data Book Digital Inverter R32, 6.0 HP < Indoor unit to be connected to RAV-GM1601ATP* Single type Distributor (Indoor unit) (Combination of one indoor unit and (Strainer one outdoor unit) TCJ sensor incorporated) Air heat exchanger TC sensor Refrigerant pipe Refrigerant pipe at liquid side at gas side...
Page 131
Engineering Data Book Engineering Data Book Light Comercial SPI R32 Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Outdoor unit RAV-GM1601AT Ball valve Packed valve Outer dia. Ø15.88 Outer dia. Ø9.52 Pressure Strainer TŌ sensor switch TS sensor (Pulse Motor Valve)
Page 132
Engineering Data Book Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Light Comercial SPI R32 3-5. Sound characteristics (NC curve) RAV-GM1601AT(J)P- E / ATP-TR, RAV-GM1601AT8(J)P- E / AT8P-TR Cooling NC - Curve NC- 70 NC- 60 NC- 50...
Page 133
Engineering Data Book Digital Inverter R32, 6.0 HP 3-6. Connecting pipe length and lift difference between indoor units vs. capacity correction value Cooling...
Page 134
Engineering Data Book Engineering Data Book Digital Inverter R32, 6.0 HP Digital Inverter R32, 6.0 HP Charging additional refrigerant Figure of Single Figure of Simultaneous twin Figure of Simultaneous triple Indoor Unit Indoor Unit Indoor Unit Indoor Unit Indoor Unit Indoor Unit Distributor Outdoor Unit...
Page 135
Engineering Data Book Digital Inverter R32, 6.0 HP 4. Optional Accessories 4-way Co mpac Slim Standard Ceiling High Cassette t 4-way duct duct wall series 1 series 1 series 1 series 1 series 1 series 1 Accessory Parts List Wired Remo te Co ntro ller RB C-A M S51 E-EN,ES RB C-A M S55E-EN, ES RB C-A M S41 E...
Page 136
Engineering Data Book Digital Inverter R32, 6.0 HP 4.2 Controller Parts name Model name Used with ON-OFF controller TCB-CC163TLE2 Wired remote controller/Central remote controller Central controller BMS-CM1280TLE All indoor units 4 way cassette type / Compact 4-way cassette type / Ducted type 1:1 model connection interface TCB-PCNT30TLE2 Slim Duct type / Ceiling type / High wall type...