"L10: Outdoor capacity not set" check code is displayed on the 7-segment display.
Perform a model change by the following flow.
By completing this procedure, it is restored to the state before a model setup and a setup of the
outdoor DN code (O.DN) exchanging. (The data of the model setup and the outdoor DN code (O.DN)
is automatically backed up by the inverter P.C. board.)
SW01:15
SW02:2
SW03:1
(7seg. "re_C1")
Push SW05 for
about 5 seconds.
(7seg. "re_do")
7seg. "reErr" →
7seg. "re_C1"
Setup complete
Arrangement of a switch
(14) Set SW01:1, SW02 : 1, SW03 : 1. Check the operation.
SW01:15
SW02:2
SW03:2
(7seg. "re_C2")
Push SW05 for
about 5 seconds.
(7seg. "re_do")
7seg. "reErr" →
7seg. "re_C2"
Setup complete
- 296 -
SW01:15
SW02:2
SW03:4
(7seg. "re_F1")
Push SW05 for
about 5 seconds.
(7seg. "re_do")
7seg. "reErr" →
7seg. "re_F1"
Setup complete
Please perform the model
change by manual operation.
(Refer to "Outdoor DN setup"
SW01:15
SW02:2
SW03:5
(7seg. "re_F2")
Push SW05 for
about 5 seconds.
(7seg. "re_do")
7seg. "reErr" →
7seg. "re_F2"
Setup complete
of a service manual.)