7-7-3. Check Code Clearing Function
(1)Clearing from the main remote controller
<RBC-AMT*>
Check code clearing in outdoor unit
Check code of the outdoor unit currently detected is cleared by the unit of one refrigerant circuit system to which the
indoor units operated by the remote controller is connected. (Check code of the indoor unit is not cleared.)
For clearing check codes, the service monitor function of the remote controller is used.
<Method>
1
Change the mode to service monitor mode by pushing
seconds or more.
2
Using
buttons, set CODE No. to "FF".
3
The display in Section A in the following figure is counted with interval of 5 seconds as
"0005"
"0004"
When the count arrives "0000", the check code is cleared.
* However, counting from "0005" is repeated on the display.
4
When
button is pushed, the status returns to the normal status.