No. Part name
Compressor
2. Compressor attachment
and
1) Detachment of the reverse order of removal.
compressor
lead
NOTE
(continued)
• Also ensure to replace the compressor lead after
replacing the compressor. (Compressor lead
replacement code: 43160658)
At this time please ensure to wind the compressor lead 4
times around the ferrite core.
(Ensure to position the ferrite core the same as when
before removed.)
• Install the sound insulation board (inner and outer)
through the space between the compressor and the
piping, and between the pipes and separate plate as
shown on the right.
• Fix in place with commercially available heat-resistant
code clamps through the pipe cover so that the TD
sensor lead does not come in direct contact with the
discharge pipe.
3. Vacuum
1) Connect the vacuum pump to the charge port of the
liquid and gas pipe valves and the check joint on the
high pressure side, and then operate the vacuum
pump.
2) Vacuum until the vacuum low pressure gauge reaches
1 (mmHg).
NOTE
Fully open the electronic control valve before the vacuum
process. If closed the vacuum pipe between the liquid pipe
valve and electronic control valve of the outdoor unit may
not be able to be drawn through.
Method for forcibly fully opening the electronic control valve
• Turn on the power supply breaker.
• Ensure that D805 of the LED indication of the outdoor
unit is lit up. If D805 is not lit up (off or flashing) then
push and hold down SW01 and SW02 at the same time
for at least 5 seconds and check that D805 lights up.
• Push and hold SW01 down for at least 5 seconds or to
confirm that D804 is slowly flashing (once/second).
• Push SW01 several times until the LED indications
(D800 to D804) become the following.
• Push SW02 and D805 will start rapidly flashing.
D800
: Go ON,
• Push and hold SW02 down for at least 5 seconds and
D804 will start slowly flashing. Once D805 lights up the
PMV will start to open.
After 30 seconds turn off the power breaker.
4. Refrigerant encapsulation
1) Add the amount of refrigerant determined by the pipe
length using the charge port of the valve.
Procedure
D801
D802
D803
: Go OFF,
: flash (5 times/sec.)
– 108 –
Wind the compressor lead
4 times around the ferrite core
Compressor lead
Excess compressor leads and
compressor case thermostat
leads should be positioned
between the inside and outside
of the soundproofing board.
The soundproof
The soundproof
The soundproof
board (outer ring)
board (outer ring)
board (outer ring)
should match this
should match this
should match this
position
position
position
Pass the soundproof board (inner ring)
through the compressor, the discharge
pipe, and the suction pipe and overlap
it in this position.
Do not leave any gap between the
soundproof board (top) and the
soundproof board (outer ring).
Soundproof
Soundproof
Soundproof
board (top)
board (top)
board (top)
Soundproof
Soundproof
Soundproof
D804
board (outer ring
board (outer ring
board (outer ring
LED display board
Inverter cover
Remarks
Ferrite core
LED indication
SW01
SW02

Advertisement

Table of Contents
loading

Table of Contents