Page 3
PRODUCT USE AND WARRANTY RESTRICTION The Toshiba products listed in this document are intended for usage in general electronics applications (computer, personal equipment, office equipment, measuring equipment, industrial robotics, domestic appliances, etc.). These Toshiba products are neither intended nor warranted for usage in equipment that requires extraordinarily high quality and/or reliability or where a malfunction or failure may cause loss of human life or bodily injury (Unintended Usage).
Page 4
T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 5
Please complete the following information and retain for your records. Job Number: _____________________________________________________________ Model Number: ___________________________________________________________ Serial Number: ___________________________________________________________ Application: ______________________________________________________________ Shipment Date: ___________________________________________________________ Installation Date: __________________________________________________________ Inspected By: _____________________________________________________________ T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 6
Toshiba is a registered trademark of the Toshiba Corporation. All other product or trade references appearing in this manual are registered trademarks of their respective owners.
Page 7
TOSHIBA INTERNATIONAL CORPORATION CUSTOMER SUPPORT CENTER Toshiba International Corporation’s Customer Support Center can be contacted to obtain help in resolving any Uninterruptible Power System (UPS) problems that you may experience or to provide application information. Customer Support Center 8 a.m. to 5 p.m. (CST) – Monday through Friday USA Toll Free (877) 867-8773 –...
CONNECTION TO MAINS AND LOADS (1000VA TO 3000VA) ... 26 12.4 CONNECTION TO MATCHING EXTERNAL BATTERY CABINET 27 COMPUTER AND ALARM CONNECTIONS......28 13.1 EPO PORT (EMERGENCY POWER OFF) ........29 T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 9
PHYSICAL ..................43 16.10 WARRANTY ..................43 INSTRUCTIONS IMPORTANTES CONCERNANT ....44 L' ÉLIMINATION DES BATTERIES EST RÈGLEMENTÈE. CONSULTER LES CODES LOCAUX À CET EFFET.INSTRUCTIONS DE SÉCURITÉS IMPORTANTES .................. 44 T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 10
Figure 7 3000VA Rackmount Rear Panel View ........... 25 Figure 8 Example of Installation of Plug & Play Product ........26 Figure 9 Connecting External Battery Cabinet ............ 27 Figure 10 Control Panel Layout ................31 T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001 viii...
The word DANGER preceded by the safety alert symbol indicates that an imminently hazardous situation exists that, if not avoided, will result in death or serious injury to personnel. DANGER T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 12
Electrical Hazard Symbol A symbol which indicates a hazard of injury from electrical shock or burn. It is comprised of an equilateral triangle enclosing a lightning bolt. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 13
Labels attached to the equipment are there to provide useful information or to indicate an imminently hazardous situation that may result in serious injury, severe property and equipment damage, or death if the instructions are not followed. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Have read the entire operation manual. Be trained and authorized to safely energize, de-energize, ground, lockout and tag circuits and equipment, and clear faults in accordance with established safety practices. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 15
WARNING Misuse of this equipment could result in injury and equipment damage. In no event will Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that may result from the misuse of this equipment. CAUTION Do not dispose of the batteries in a fire.
Page 16
Contact with any part of a grounded battery can result in electrical shock. The likelihood of shock will be reduced if such grounds are removed prior to installation or maintenance. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 17
Do not apply for uses in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment, ANSI/NFPA 75. This UPS is not applicable for motors, hair dryers, speakers, and fluorescent lamps. Do not disconnect battery connector under load. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 18
Before conducting any maintenance, repair or shipment, first ensure that all components turned off completely and disconnected. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 19
Please do not discard the UPS or UPS batteries as the UPS may have valve regulated, lead–acid batteries. Please recycle batteries. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Units labeled with a CE mark comply with the following standards and directives: .Harmonic Standards: EN 62040-1, EN62040-2 .EU Directives: 2014/30/EU (EMC), 2014/35/EU (LVD) The EC Declaration of Conformity is available upon request for products with a CE mark. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
In order to prevent power line problems reaching critical systems causing damage to software, hardware and causing equipment to malfunction, the UPS helps by maintaining constant voltage, isolating critical load output if needed, and cleaning the utility AC power. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
DC power is converted to AC in the inverter passing it on to the load. Power is maintained from the battery during a power failure. The converter increases voltage appropriately for the inverter. Figure 1: Block diagram T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Backup time needed defines the battery size needed. If load is less than the UPS nominal power rating then actual backup time is longer. The following options are available: External Battery Cabinets Connectivity options (dry contact card, network monitoring card) T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
All such operations are to be performed exactly as instructed in this manual. The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operator. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Please contact your local or state environmental agency for details on disposal of electrical components and packaging in your particular area. It is illegal to dump lead-acid batteries in landfills or dispose of improperly. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 26
Please help our Earth by contacting the environmental protection agencies in your area, the battery manufacturer, or call Toshiba toll-free at (877) 867-8773 for more information about recycling. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
4. A separate ground cable should be run inside the conduit with the input power, output power, and control circuits. CAUTION THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
CHARGE LED has gone out before opening the door of the UPS once the UPS power has been turned off. 8. Do not attempt to disassemble, modify, or repair the UPS. Call your Toshiba sales representative for repair information.
The UPS could be damaged if the unit is not fully discharged before the breaker is reset. MAINTENANCE NOTE The T1000 Series UPS is not designed for field-level service. All repairs will be done at the Depot-level. 12 INSTALLATION 12.1...
Section 12 of the manual provided with that option. The connections can be referred to on the rear panel. The installation is now complete. Figure 8 Example of Installation of Plug & Play Product T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
This UPS may be provided with maximum two extension battery cabinets. Figure 9 Connecting External Battery Cabinet T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
USB compliant hardware and operating system will be necessary including installation of a UPS driver. The serial port cannot be used when using the USB port. The USB cable is standard and can be bought separately. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
The load group status can be viewed from the LCD display and can be changed if necessary. These load segments are usually handled with the UPS management software. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
(b). If not pressed within 10 seconds, it will return to original status. 3. “ ” is a Function button . Each function can be enabled by pressing this button. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Press any of the buttons on the front panel to turn the alarm. Status of the UPS, measurements and alarms are all displayed on the LCD screen. Rackmount Tower Figure 10 Control Panel Layout T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 42
Line mode. While the factory default settings do not necessarily have to be changed, the user is free to tailor the UPS to their specific needs. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 43
Cabinet For UPS to predict cabinet) Packs Backup time 2 (two external cabinets) Sit Fault You can enable or disable Site wiring alarm Enable /Disable Disable the site wiring alarm T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
On the LCD display, you can also choose silent alarm mode which will not warn you of any malfunction audibly T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Wrong. Rotate the connector. UPS Site wiring Voltage detected Between installed to mains supply without Fault Neutral and Ground second ground. See page 15 on how to disable the Site wiring alarm T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
After a beep sounds, unplug the AC power cord and wait for UPS to shutdown automatically. ** Note: Cold start will be automatically re-enabled when the UPS is plugged into commercial power and switched ON. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Attempting to make such alterations can cause injury. Replace the batteries with the same number and type as originally installed batteries. DO NOT DISCONNECT the batteries while UPS is in Battery mode. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
48Vdc once the battery is disconnected from the UPS. 3. Replace the batteries. 4. Push the cartridge with the new batteries back into the UPS. 5. Re-install the metal plate and the front panel. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Internal Bypass (Automatic and Manual) Bypass Crest Factor > 86% Efficiency WARNING: When power is supplied by external batteries, output towards load should be less than 90% of overall power generation. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Internal Bypass (Automatic and Manual) Bypass Crest Factor > 86% Efficiency WARNING: When power is supplied by external batteries, output towards load should be less than 90% of overall power generation. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
<4 hours to over 90% 16.9 x 16.7 16.9 x 19.7 Dimensions WxDxH (in) 16.9 x 25 x 3.3 x 3.3 x 3.3 Net Weight 35.9 lbs. 39.4 lbs. 65.6 lbs. 73.9 lbs. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
ATTENTION Une battery peut présenter un risque de choc électrique, de brûlure par transfert d' énergie. ATTENTION L' ÉLIMINATION DES BATTERIES EST RÈGLEMENTÈE. CONSULTER LES CODES LOCAUX À CET EFFET. T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
30 ampères conformément au Code Électrique National (National Electrical Code) des États-Unis, ANSI/NFPA 70. La protection de surintensité de sortie ainsi que le sectionneur doivent être fournis par des tiers T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001...
Page 56
13131 West Little York Rd., Houston, TX 77041 Tel: 713/466-0277 Fax 713/466-8773 US 877/867-8773 www.toshibaups.com Printed in Taiwan...