Three phase - 15/20/25/30/50/80/100 kva (138 pages)
Summary of Contents for Toshiba 4200FA
Page 1
NINTERRUPTIBLE OWER YSTEM THREE-PHASE 15/ 25/ 30/ 33/ 50 kVA UPS 4200 USER'S MANUAL MANUFACTURED IN THE U.S.A. Document Number: 53878-004 Date: April 2005...
Page 2
4200FA THREE PHASE- 15/25/30/33/50 kVA UNINTERRUPTIBLE POWER SYSTEM OPERATION MANUAL FOR MODELS T42F3F150X#MBN T42F3F150F#MBN T42#3#150##MXN T42F3F250X#MBN T42F3F250F#MBN T42#3#250##MXN T42F3F300X#MBN T42F3F300F#MBN T42#3#300##MXN T42F3F330X#MBN T42F3F330F#MBN T42#3#330##MXN T42F3F500XAMBN T42F3F500F#MBN T42#3#500##MXN TOSHIBA INTERNATIONAL CORPORATION INDUSTRIAL DIVISION 13131 West Little York Rd., Houston, Texas 77041...
Page 3
Should further information be desired or should particular problems arise which are not covered sufficiently, the matter should be referred to your local Toshiba sales office. The contents of this instruction manual shall not become a part of or modify any prior or existing equipment, commitment, or relationship.
Page 4
TOSHIBA is a registered trademark of the Toshiba Corporation. All other product or trade references appearing in this manual are registered trademarks of their respective owners.
CAUTION The word CAUTION or ATTENTION in capital letters without the safety alert symbol indicates a potentially hazardous situation exists which, if not avoided, may result in equipment and property damage. CAUTION/ATTENTION TOSHIBA...
It is comprised of an equilateral triangle enclosing a lightning bolt. Explosion Hazard Symbol A symbol which indicates a hazard of injury from exploding parts. It is comprised of an equilateral triangle enclosing an explosion image. TOSHIBA...
If the labels are damaged or if additional labels are required, contact your Toshiba representative for additional labels. Labels attached to the equipment are there to provide useful information or to indicate an imminently hazardous situation that may result in serious injury, severe property and equipment damage, or death if the instructions are not followed.
Therefore, a user-installed circuit breaker should be provided between the UPS output and the load input. 3. Battery servicing should be performed by a qualified Toshiba Representative only. 4. Unauthorized personnel should not service batteries.
Page 12
The nominal battery voltage for all internal battery models is 288VDC. The nominal battery voltage for all external battery models is 288VDC. An Authorized Toshiba Service Representative who is knowledgeable of batteries and the required precautions should perform service on the batteries. Keep unauthorized personnel away from batteries.
Page 13
INSTRUCTIONS IMPORTANTES CONCERNANT CONSERVER CES INSTRUCTIONS ATTENTION ATTENTION ATTENTION TOSHIBA LA SÉCURITÉ Un battery puet présenter un risque de choc électrique, de brûlure par transfert d’ énergie. Por le replacement, utiliser le même nombre de batteries du modéle suivant.
Application and Use Toshiba's 4200FA On-Line, Uninterruptible Power Systems (UPS) provide continuous computer grade isolated AC power in a compact, efficient, high performance unit. The UPS assures safe, reliable operation of critical office equipment, ranging from personal computers to mini-computers to local area networks (LAN).
½x3” bolts to secure the rails to the shipping pallet. Attach the rails as shown to the front of the pallet. DANGER TOSHIBA Remove packing material. the screws that attach the shipping crate to the pallet. Remove the crate and foam packing material.
TOP HEAVY EQUIPMENT. IMPROPER LIFTING CAN RESULT IN INJURY OR DEATH. LIFT AND MOVE CAREFULLY AND ONLY WITH ADEQUATE EQUIPMENT AND TRAINED DANGER PERSONNEL. THIS EQUIPMENT WILL TIP OVER EASILY UNTIL FIXED IN PLACE. TOSHIBA...
It is ILLEGAL to dump lead-acid batteries in landfills or dispose of ATTENTION improperly. Please help our Earth by contacting the environmental protection agencies in your area, the battery manufacturer, or call Toshiba toll-free at (800) 231-1412 for more information about recycling batteries. TOSHIBA 5.18...
3.0 Installation Precautions Based on the 4200FA UPS external dimensions and the way the outer panels are removed; minimum amounts of unobstructed space around the unit are necessary for ventilation and maintenance access. Figure 3.1 shows the minimum clearances required for proper UPS site installation.
5) Do not insert metal objects or combustible materials in the unit's ventilation slots. 6) Do not place, hang, or paste any objects on the top or on the exterior surfaces of the UPS. TOSHIBA...
The following illustrates the wiring connections from the power distribution panel (not part of the UPS) to the terminal block of the 15/25/30/33 kVA UPS Models 4.1.1 CUSTOMER-PROVIDED AC DISTRIBUTION PANEL Optional Bypass Input: 3-phase, 3-Wire *208V requires 3-phase, 4-Wire Wye TOSHIBA INPUT GROUND RESISTANCE LESS THAN 10 OHMS...
The following illustrates the wiring connections from the power distribution panel (not part of the UPS) to the terminal block of the 15/25/30/33 kVA UPS Models TO BATTERY SYSTEM GND Optional Bypass Input: 3-Phase, 3-Wire *208V requires 3-Phase, 4-Wire Wye TOSHIBA CUSTOMER-PROVIDED AC DISTRIBUTION PANEL INPUT GROUND RESISTANCE LESS THAN 10 OHMS...
1) Input and Output conductors shall be installed in separate conduits, and installed in accordance with the latest edition of NEC and the Local Authority having jurisdiction. 2) Battery conductors shall be installed in a separate conduit and be of low resistance type. TOSHIBA OUTPUT CONDUIT BATTERY CONDUIT...
BATTERY CONTROL CIRCUITS (3-6)* BATTERY (+/-) *Indicates Class 1 wiring methods is to be used. Maximum Wire Size for Control Circuits is 12 AWG. Maximum for Battery is 2 AWG. TOSHIBA Battery Connection (+) Positive (-) Negative 15/25/30/33 kVA TIGHTENING...
The following illustrates the wiring connections from the power distribution panel (not part of the UPS) to the terminal block of the 50 kVA UPS Model (H1) (H2) (H3) (N) INPUT: 3-phase, 3-wire 208V requires 3-phase, 4-wire TOSHIBA (L1) (L2) (L3) OUTPUT: 3-phase (4-wire) (H1)
Phase: (A) (B) (C) Input: (H1) (H2) (H3) 208/120 Maximum Wire Size for Input is 1/0 AWG. Maximum Wire Size for Neutral is 250MCM. TOSHIBA Minimum Wire Size and Torque Requirements UPS Input and Output Terminals 50 kVA OUTPUT: NEUTRAL...
4.3.2 Power Connection Cable Routing The following illustrates the proper cable routing that should be followed during the power connection process for the 50kVA. Removable cover for conduit access TOSHIBA Bottom Conduit Entry...
UPS CONTROL CIRCUITS (1-24)* BATTERY CONTROL CIRCUITS (3-6)* *Indicates Class 1 wiring methods is to be used. Maximum Wire Size is 12 AWG. TOSHIBA (3) Battery Shunt Trip (4) Battery Shunt Trip (5) Battery Aux. (6) Battery Aux. 50 kVA...
1) Pin “switches” are shown in their inactive states. Example: (if battery voltage is low, pin 7 will be connected to System Common). 2) Contacts are rated at 30 VDC, 0.1 amps; 125 VAC, 3 amps. 3) Pin number “3” is not used. TOSHIBA DB9 Male Connector Outline (Facing Connector) Battery Discharge...
UPS. This interface allows control of the UPS from a computer network running Toshiba RemotEyeII™ software. The computer and the UPS are connected through a serial RS-232C communication port. The available data from the UPS, via the RS-...
5.0 Technical Data 4200FA 15 / 25kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries Model Number Rated Output Capacity External Dimensions W x D x H (mm) Input Rated Voltage Voltage Variation Rated Frequency Input Cables required Dual Input Option Cables required...
4200FA 15/ 25kVA w/Internal Transformer Model Number Rated Output Capacity External Dimensions W x D x H (mm) Input Rated Voltage Voltage Variation Rated Frequency Input Cables Required Dual Input Option Cables required * Power Factor Required Input kVA Walk-in Function...
4200FA 30 / 33kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries Model Number Rated Output Capacity External Dimensions W x D x H (mm) Input Rated Voltage Voltage Variation Rated Frequency Input Cables required Dual Input Option Cables required...
4200FA 30/ 33kVA w/Internal Transformer Model Number Rated Output Capacity External Dimensions W x D x H (mm) Input Rated Voltage Voltage Variation Rated Frequency Input Cables Required Dual Input Option Cables required * Power Factor Required Input kVA Walk-in Function...
4200FA 50kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries Model Number Rated Output Capacity External Dimensions W x D x H (mm) Input Rated Voltage Voltage Variation Rated Frequency Input Cables Required Dual Input Option Cables required * Power Factor...
4200FA 50kVA w/Internal Transformer Model Number Rated Output Capacity External Dimensions W x D x H (mm) Rated Voltage Voltage Variation Rated Frequency Input Cables Required Dual Input Option Cables required Input * Power Factor Required Input kVA Walk-in Function...
UPS's Bypass circuit back to the Inverter circuit after removing the overload (see "Overload Operation"). Isolation Transformer Model Input Power 5.7.2.1 Bypass Mode for Optional Alternate Input Models TOSHIBA Bypass Converter Inverter MCCB Chopper Batteries Power flow in AC Input Mode...
When this occurs, the batteries will stop supplying power to the load. This minimum level is the rated minimum voltage (V min). Isolation Transformer Model MCCB Input Power TOSHIBA Bypass Converter Inverter Chopper Batteries Bypass Converter Inverter...
Battery Backup Time and Discharge Process The UPS system, when used in conjunction with a Toshiba designed Battery System, is designed to provide several minutes of back-up time (Refer to the Battery System Manual for back-up times). These times are valid when the unit is operating under full load. When these models are operating at half load, the batteries can provide approximately 2 times the specified value.
Audible alarms will sound when the UPS is in the Battery Backup Mode, has a fault, is at the low battery voltage, or is in an overload condition. The following chart shows the audible alarm TOSHIBA Emergency power off switch STOP/RUN key (see Section 6.6)
Page 42
TOSHIBA pattern duration for each condition. Time intervals are shown in seconds. The audible alarm can be silenced, by pressing “BUZZ STOP” on the keypad. Condition Audible pattern UPS in Battery Backup Mode (Battery Voltage 100-92%) UPS Low Battery (Battery Voltage < 92%) Overload .5 S...
Bypass Operation; UPS Fault AC IN BATT FAULT Battery Back-up; (Battery Voltage Low) AC IN BATT ON (Blinking) FAULT TOSHIBA Output Shutdown (After EPO received (Emergency Power Off )) AC IN BATT FAULT Fatal Communication Error (Display to Control Interface) AC IN...
DCOV VOUV VOOV 5.15.3 Line-3 System Messages Line–3 messages show load current information, and user selected instructions. TOSHIBA LINE-1 MESSAGES Translation Displayed when UPS is in the start-up condition or display board is resetting. Displayed when the UPS is in Bypass Operation.
Line-4 will be blank when the BATT key is pressed during Battery Backup Mode with normal battery voltage. The # symbol signifies numerical values or other information supplied by the UPS. TOSHIBA Line-4 Messages Translation Displayed when Input Phase rotation has been wired in a counter-clockwise rotation.
2) Allow 24-72 hours for the batteries to charge and then move the Circuit Breaker to "off." 3) Repeat Initial Battery Charge procedure. (A failure indicates battery replacement may be necessary). TOSHIBA - UPS START UP - > PLEASE WAIT (DATE) DAY (TIME)
FAULT(s) DETECTED at start-up message such as the following: UPS FAULT (BYPASS ON) PRESS DOWN TO DETAIL > ENTER FOR DETAILS Refer to the "Line-2 System Fault Messages" section for details. TOSHIBA - UPS START UP - > PLEASE WAIT DATE (DAY) TIME - UPS ON-LINE -...
EPO switch) is pushed, the Circuit Breaker is tripped and power is removed from the UPS and to any attached loads. All LED lamps are "off" and the LCD screen will display the following message: - OUTPUT SHUT DOWN - CURRENT=LOW/LOW/LOW% TOSHIBA BYPASS OPERATION OUTPUT VOLTAGE=207V DATE (DAY) TIME OUTPUT VOLTAGE= 0V...
Cam Switch counter-clockwise until “UPS MODE” Position is reached. 5) Rotate the “STOP/RUN” switch to the “RUN” position. 6) Verify that the Inverter indicator light on the front panel is lit. The unit is now back On-Line and supplying conditioned power to the load. TOSHIBA...
Press to confirm user-selected command or action. RESET Press to reset UPS panel’s message-display area. Press to forward through display data values or to forward through menus. Press to reverse through display data values or to reverse through menus. TOSHIBA BATT BATT TEST MENU...
The Output Line Voltages (phase-neutral, and phase to phase), Frequencies / Sync Mode, Inverter Output Power, and Power factor can be monitored by pressing the "up/down" keys. TOSHIBA - UPS ON-LINE - DATE (DAY) TIME - BATTERY BACKUP –...
TOSHIBA 5.21.4 BATT Key When the BATT key is pressed during normal 'AC Input Mode' of operation, the LCD screen displays details about the battery capacity. The following system message is displayed: - UPS ON-LINE - BATTERY VOLTAGE=324V CHARGE CURR.=0% If an AC input power failure occurs, and no abnormal operating conditions are present, the UPS will switch to standard 'Battery Backup Mode'.
TOSHIBA When the battery test is completed, the previous operation will be resumed and the main system MONI screen will be displayed. If the battery test detects a low DC battery voltage, then the message screen will display: - UPS ON-LINE -...
'down' arrow key to scroll to the LCD-Idle Mode Select screen display: DISPLAY DURATION SET <3 MIN> >F1: DATA SET MODE >∆/∇:PRV/NEXT SCREEN TOSHIBA CALENDER / CLOCK DATE (DAY) TIME CALENDER / CLOCK DATE (DAY) TIME 30 MIN...
TOSHIBA Press the F1 key to display the LCD-Idle mode setting adjustment screen: DISPLAY DURATION SET <3 MIN> >∆/∇: CHANGE DATA >ENTER:ACCEPT CHANGE Press the 'up' or 'down' arrow key to move the marker between the two available idle mode times. Press the ENTER key to save the change or press the MENU key to exit to the main menu and discard the change.
TOSHIBA 5.22.6 Output Voltage Adjustment When the MENU key is pressed and held 3-4 seconds during normal 'AC Input Mode' of operation, the LCD screen displays the output voltage on the present output voltage adjust screen: OUTPUT VOLT. ADJUST OUTPUT VOLTAGE.=###% >F1:DATA SET MODE...
If the STOP/RUN key switch is in the STOP position; the UPS is in the Bypass Mode and, if the overload condition is still present, the following screen will be displayed: - BYPASS OPERATION - CURRENT= 114/116/114% * UPS OL: REDUCE LOAD * TOSHIBA MENU DATA RESET MENU DATA RESET - UPS ON-LINE - OUTPUT VOLTAGE=208...
Pressing the MONI and F1 keys simultaneously, for a few seconds will cause the Battery Discharge Count screen to be displayed. Press the F1 key to display the record relating to the first discharge event. TOSHIBA - BYPASS OPERATION - OUTPUT VOLTAGE=208V CURRENT= 100/100/100 >PLEASE WAIT...
Page 59
TOSHIBA Press the F1 key again to display the record relating to each subsequent discharge event. BACKUP HISTORY ( #) #MIN##SEC VB=324V BT *PF OL >∆/∇: EXIT Press the ‘up’ or ‘down’ arrow keys to return to the Battery Discharge Count screen.
10. Internal Maintenance Bypass: This verifies the operation of the Maintenance Bypass. Preventive Maintenance Toshiba's 4200FA Uninterruptible Power Systems have been designed to provide years of trouble-free operation requiring a minimum of preventive maintenance. The best preventive measure that the UPS user can take is to keep the area around the unit, particularly the air inlet vents, clean and free of moisture and dust accumulations.
D. Re-torque all inter-battery connecting hardware (if applicable). E. Perform inter-battery connector resistance checks. 2) Aluminum electrolytic capacitors: Replace once every 5 years. 3) Fuses: Replace once every 7 years. 4) Cooling fan: Replace once every 3 years. TOSHIBA Necessary corrective...
15 kVA (927mm x 1092mm x 1765mm) 36.5” x 43.0” x 69.5” 25/30/33 kVA (927mm x 1092mm x 1765mm) 55.0” x 44.5” x 69.5” 50 kVA (1397mm x 1130mm x 1765mm) TOSHIBA Internal Model Battery Transformer Battery Transformer Battery Transformer Shipping Weights Lbs.
Page 66
TOSHIBA TOSHIBA INTERNATIONAL CORPORATION INDUSTRIAL DIVISION 13131 West Little York Road, Houston, Texas 77041 Tel: (713) 466-0277 Fax: (713) 896-5212 Telex: 762078 E-mail: Toshibaups@tic.toshiba.com Printed in the U.S.A.