SERVICE MANUAL

AIR CONDITIONER

RAS-13UKH-ES3 / RAS-13UAH-ES3
RAS-10UKH-ES3 / RAS-10UAH-ES3
RAS-13UK-ES3 / RAS-13UA-ES3
RAS-10UK-ES3 / RAS-10UA-ES3
FILE NO. SVM-04017-4
SPLIT WALL TYPE
Revised on Nov, 2005

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAS-13UKH-ES3

  • Page 1: Service Manual

    FILE NO. SVM-04017-4 SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-13UKH-ES3 / RAS-13UAH-ES3 RAS-10UKH-ES3 / RAS-10UAH-ES3 RAS-13UK-ES3 / RAS-13UA-ES3 RAS-10UK-ES3 / RAS-10UA-ES3 Revised on Nov, 2005...
  • Page 2: Table Of Contents

    RAS-13UKH-ES3 / RAS-13UAH-ES3 RAS-10UKH-ES3 / RAS-10UAH-ES3 RAS-13UK-ES3 / RAS-13UA-ES3 RAS-10UK-ES3 / RAS-10UA-ES3 CONTROL BLOCK DIAGRAM RAS-13UKH-ES3 / RAS-13UAH-ES3, RAS-10UKH-ES3 / RAS-10UAH-ES3 RAS-13UK-ES3 / RAS-13UA-ES3, RAS-10UK-ES3 / RAS-10UA-ES3 OPERATION DESCRIPTION Outline of Air Conditioner Control Description of Operation Circuit Hi POWER Mode...
  • Page 3 FILE NO. SVM-04017 INSTALLATION PROCEDURE Safety Cautions Installation Diagram of Indoor and Outdoor Units Installation Indoor Unit Outdoor Unit How to Set Remote Control Selector Switch Others TROUBLESHOOTING CHART Troubleshooting Procedure Basic Check Items Primary Judgement Self-Diagnosis by Remote Control (Check Code) Troubleshooting Flowcharts Troubleshooting for Remote Control 10.
  • Page 4: Specifications

    FILE NO. SVM-04017 1. SPECIFICATIONS MODEL RAS-13UKH-ES3 / RAS-13UAH-ES3 RAS-13UK-ES3 / RAS-13UA-ES3 ITEM Cooling Heating Cooling 220 V 240 V 220 V 240 V 220 V 240 V Capacity 3.60 3.60 4.20 4.26 3.75 3.75 Phase ∅ 1 Power source...
  • Page 5 FILE NO. SVM-04017 MODEL RAS-10UKH-ES3 / RAS-10 UAH-ES3 RAS-10UK-ES3 / RAS-10 UA-ES3 ITEM Cooling Heating Cooling 220 V 240 V 220 V 240 V 220 V 240 V Capacity 2.70 2.70 2.90 2.96 2.70 2.70 Phase 1∅ Power source 220 - 240 Power consumption 0.82 0.84...
  • Page 6 Outdoor unit inlet air temperature (WB) 24°C 6°C Note : 2 • Charge refrigerant according to the table below. RAS-13UKH-ES3 / RAS-13UAH-ES3 RAS-10UKH-ES3 / RAS-10UAH-ES3 RAS-13UK-ES3 / RAS-13UA-ES3 RAS-10UK-ES3 / RAS-10UA-ES3 No need to charge 15 m or less 10 m or less extra refrigerant –...
  • Page 7: Construction Views

    FILE NO. SVM-04017 2. CONSTRUCTION VIEWS 2-1. Indoor Unit Front panel Heat exchanger Air inlet Air Filter Back body Air outlet Knock out system Knock out system Hanger Connecting pipe (0.43 m) Drain hose (0.54 m) (Flare ∅6.35) Hanger Connecting pipe (0.33 m) (For 13 series ;...
  • Page 8: Outdoor Unit

    FILE NO. SVM-04017 2-2. Outdoor Unit 32.5 A Detail Drawing (Back Leg) B Detail Drawing (Front Leg) ∅6 Hole ∅6 Hole ∅11 x 14 Hole R5.5 ∅30 Drain outlet 2-∅11 x 14 Hole (For ∅8-∅10 anchor bolt) ∅436 FAN GUARD COVER PV Electrical part cover...
  • Page 9: Wiring Diagram

    FILE NO. SVM-04017 3. WIRING DIAGRAM 3-1. RAS-13UKH-ES3 / RAS-13UAH-ES3 73°C THERMAL FUSE INFRARED RAYS RECEIVE AND INDICATION PARTS 4 5 6 7 8 9 10 11 CN25 4 5 6 7 8 9 10 11 6 7 8 9 10 11...
  • Page 10: Ras-10Ukh-Es3 / Ras-10Uah-Es3

    FILE NO. SVM-04017 3-2. RAS-10UKH-ES3 / RAS-10UAH-ES3 Louver motor 73°C THERMAL FUSE INFRARED RAYS RECEIVE AND INDICATION PARTS 4 5 6 7 8 9 10 11 CN25 4 5 6 7 8 9 10 11 6 7 8 9 10 11 4 5 6 7 8 9 10 11 CN04 CN07...
  • Page 11: Ras-13Uk-Es3 / Ras-13Ua-Es3

    FILE NO. SVM-04017 3-3. RAS-13UKP-ES3 / RAS-13UA-ES3, RAS-10UKP-ES3 / RAS-10UA-ES3 Infrared rays receiver and indication parts. TRANS (TT-10) CN25 CN14 CN05 CN06 MCC-920 CN07 DB50 Heat Exchanger CN01 Sensor (TC) RY01 DC 12 V Regulator circuit DC 5 V T6.3 A CN03 Thermo Sensor (TA) Louver motor...
  • Page 12: Specification Of Electrical Parts

    FILE NO. SVM-04017 4. SPECIFICATION OF ELECTRICAL PARTS 4-1. Indoor Unit (RAS-13UKH-ES3, RAS-10UKH-ES3) Parts name Type Specifications Fan motor (for indoor) MMF-240-20-4A-1 AC Motor with 135°C thermo fuse Thermo sensor (TA-sensor) 10kΩ at 25°C  Switching transformer (T01) SWT-47 Microcontroller unit (IC30)
  • Page 13: Outdoor Unit (Ras-10Uah-Es3)

    FILE NO. SVM-04017 4-3. Outdoor Unit (RAS-10UAH-ES3) Parts name Type Specifications Output (Rated) 750 W, 2 poles, 1 phase, 220 − 240 V, 50Hz Compressor PA108X1T-4FZ1 Winding resistance (Ω ) (at 20° C) 3.89 4.51 Output (Rated) 30 W, 6 poles, 1 phase, 220 − 240 V, 50Hz Fan motor (for outdoor) HF-240-30B Winding resistance (Ω...
  • Page 14: Outdoor Unit (Ras-13Ua-Es3)

    FILE NO. SVM-04017 4-5. Outdoor Unit (RAS-13UA-ES3) Parts name Type Specifications Output (Rated) 1100 W, 2 poles, 1 phase, 220 − 240 V, 50Hz Compressor PA150X2T-4FM1 Winding resistance (Ω ) (at 20° C) 2.49 3.95 Output (Rated) 30 W, 6 poles, 1 phase, 220 − 240 V, 50Hz Fan motor (for outdoor) HF-240-30B Winding resistance (Ω...
  • Page 15: Refrigeration Cycle Diagram

    FILE NO. SVM-04017 5. REFRIGERATION CYCLE DIAGRAM 5-1. RAS-13UKH-ES3 / RAS-13UAH-ES3 Indoor unit Evaporator Cooling 0.39 m 0.49 m Heating (Connecting pipe) (Connecting pipe) ∅12.7 ∅6.35 Cross flow fan O.D.:12.7 mm O.D.:6.35 mm Packed valve Packed valve (∅12.7) (∅6.35) Heating...
  • Page 16: Ras-10Ukh-Es3 / Ras-10Uah-Es3

    FILE NO. SVM-04017 5-2. RAS-10UKH-ES3 / RAS-10UAH-ES3 Indoor unit Evaporator Cooling 0.39 m 0.49 m Heating (Connecting pipe) (Connecting pipe) ∅9.52 ∅6.35 Cross flow fan O.D.:9.52 mm O.D.:6.35 mm Packed valve Packed valve (∅9.52) (∅6.35) Heating Cooling 4-way valve Heating Cooling Compressor PA108X1T-4FZ1 Capillary tube Capillary tube...
  • Page 17: Ras-13Uk-Es3 / Ras-13Ua-Es3

    FILE NO. SVM-04017 5-3. RAS-13UK-ES3 / RAS-13UA-ES3 Indoor unit Heat exchanger Cooling 0.49 m 0.39 m (Connecting pipe) (Connecting pipe) ∅6.35 ∅12.7 Cross flow fan O.D.:12.7 mm O.D.:6.35 mm Packed valve Packed valve (∅12.7) (∅6.35) Cooling Cooling Compressor PA150X2T-4FM1 Capillary tube ∅1.5 x 500l Condenser Refrigerant...
  • Page 18: Ras-10Uk-Es3 / Ras-10Ua-Es3

    FILE NO. SVM-04017 5-4. RAS-10UK-ES3 / RAS-10UA-ES3 Indoor unit Evaporator Cooling 0.39 m 0.49 m (Connecting pipe) (Connecting pipe) ∅9.52 ∅6.35 Cross flow fan O.D.:9.52 mm O.D.:6.35 mm Packed valve Packed valve (∅9.52) (∅6.35) Cooling Cooling Compressor PA108X1T-4FZ1 Capillary tube ∅1.5 x 1100l Condenser Refrigerant...
  • Page 19: Control Block Diagram

    FILE NO. SVM-04017 6. CONTROL BLOCK DIAGRAM 6-1. RAS-13UKH-ES3 / RAS-13 UAH-ES3, RAS-10UKH-ES3 / RAS-10 UAH-ES3 M.C.U. Main Unit Control Panel Operation Heat Exchange sensor Functions Display Timer • Louver Control Thermo. Sensor Display Filter Sign • 3-minutes Delay at Restart...
  • Page 20: Ras-13Uk-Es3 / Ras-13Ua-Es3, Ras-10Uk-Es3 / Ras-10Ua-Es3

    FILE NO. SVM-04017 6-2. RAS-13UK-ES3 / RAS-13UA-ES3, RAS-10UK-ES3 / RAS-10UA-ES3 Main Unit Control Panel M.C.U. Operation Heat Exchange sensor Functions Display Timer • Louver Control Display Thermo. Sensor Filter Sign Display • 3-minutes Delay at Restart Infrared Rays Signal Reciver for Compressor Auto Fan Sign Display...
  • Page 21: Operation Description

    • Transferring of operation commands to the LOW+MED outdoor unit • Receiving of information of the operation status MED+HIGH and judging of the information or indication of error Table 7-1-1 RAS-13UKH-ES3 RAS-10UKH-ES3 Model Motor speed Air flow level Motor speed Air flow level (rpm)
  • Page 22: Description Of Operation Circuit

    FILE NO. SVM-04017 7-2-2. Cooling operation 7-2. Description of Operation Circuit ([MODE] button on the remote control is set (1) When turning on the breaker, the operation lamp to the cooling operation.) blinks. This means that the power is on (or the (1) The compressor, 4-way valve, outdoor fan and power supply is cut off.) operation display on the remote control are...
  • Page 23 FILE NO. SVM-04017 7-2-3. Dry operation 7-2-4. Heating operation *Heat pump model only ([MODE] button on the remote control is set ([MODE] button on the remote control is set to the dry operation.) to the heating operation.) (1) The compressor, 4-way valve, outdoor fan and (1) The compressor, 4-way valve, outdoor fan and operation display on the remote control are operation display on the remote control are...
  • Page 24: Cooling Operation

    Fig. 7-2-8 and Table 7-2-1. speed Starting period Stabilized period • From 12 to 25 minutes • Up until 12 minutes AUTO RAS-13UKH-ES3 passed after starting passed after starting the unit the unit and room °C Manual • From 12 to 25 minutes...
  • Page 25: Hi Power Mode

    Fig. 7-5-1 and 7-5-2. air conditioner operates at maximum airflow level. If the difference between the preset RAS-13UKH-ES3 temperature and the room temperature is small, RAS-13UK-ES3 the air conditioner operates at normal airflow level.
  • Page 26: Defrost Operation

    FILE NO. SVM-04017 7-6. Defrost Operation *Heat pump model only <In case of C> (1) The heating operation is performed for at least 90 During the heating operation, the outdoor heat minutes. exchanger temperature goes down and sometimes it is frozen.
  • Page 27: Current Limit Control

    (2). (1) Current limit control (Cooling operation) Control is performed as shown below by detecting the compressor operating current with a current sensor (C.T). RAS-13UKH-ES3, RAS-10UKH-ES3 Input current Compressor Outdoor fan More than I4 continues for 3 seconds 13.5A/ 19.2A I4 More than I3 continues for 5 seconds 12.5A/ 17.8A I3...
  • Page 28: Auto Restart Function

    FILE NO. SVM-04017 7-8-1. How to set auto restart function 7-8. Auto Restart Function To set the auto restart function, proceed as follows: The indoor unit is equipped with an automatic The power supply to the unit must be on; the function restarting function which allows the unit to restart will not set if the power is off.
  • Page 29: Filter Check Lamp

    FILE NO. SVM-04017 7-8-2. How to cancel auto restart function To cancel auto restart function, proceed as follows: Repeat the setting prodedure: the unit receives the signal and beeps three times. The unit will be required to be turned on with the remote control after the main power supply is turned off.
  • Page 30: Installation Procedure

    Also, make sure the equipment is properly earthed. • Appliance shall be installed in accordance with national wiring regulations. If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately. CAUTION • Exposure of unit to water or other moisture before installation could result in electric shock.
  • Page 31 FILE NO. SVM-04017 REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER Please make absolutely sure that the installation of this appliance is reported to the local power supplier before installation. If you experience any problems, or if the installation is not accepted by the supplier, the service agency will take adequate countermeasures.
  • Page 32: Installation Diagram Of Indoor And Outdoor Units

    FILE NO. SVM-04017 8-2. Installation Diagram of Indoor and Outdoor Units Before installing the For the rear left and left wireless remote control piping Hook • With the remote control cover Installation open, load the batteries supplied plate Wall correctly, observing their polarity.
  • Page 33: Installation

    FILE NO. SVM-04017 8-3. Installation 8-3-1. Optional installation parts Part Parts name Q’ty Code Refrigerant piping Liquid side : ∅6.35 mm : ∅9.52 mm (10 series) Gas side each : ∅12.70 mm (13 series) Gas side Pipe insulating material (polyethylene foam, 6 mm thick) Putty, PVC tapes each <Fixing bolt arrangement of outdoor unit>...
  • Page 34 FILE NO. SVM-04017 8-3-2. Accessory and installation parts Part Part Part Part name (Q’ty) Part name (Q’ty) Part name (Q’ty) Mounting screw ∅4 x 25 s x 6 Installation plate x 1 Remote control holder x 1 Pan head wood screw ∅3.1 x 16 s x 2 Wireless remote control x 1 Zeolite filter x 1...
  • Page 35: Indoor Unit

    FILE NO. SVM-04017 8-4-2. Cutting a hole and mounting installation 8-4. Indoor Unit plate 8-4-1. Installation place <Cutting a hole> • A place which provides the spaces around the When installing the refrigerant pipes from the rear. indoor unit as shown in the above diagram. •...
  • Page 36 Anchor bolt NOTE • Ensure all wiring is used within its electrical rating. Projection 15 mm or less 5 mm dia. hole RAS-13UKH-ES3 RAS-10UKH-ES3 Model RAS-13UK-ES3 RAS-10UK-ES3 7 Mounting Power source 50Hz, 220 – 240 V Single phase screw ∅4 x 25s s s s s...
  • Page 37 FILE NO. SVM-04017 8-4-4. Wiring connection <Stripping length of the connecting cable> <How to connect the power cord> 40 mm Earth line 10 mm For the air conditioner that does not have power cord, connect a power cord to it as mentioned below.
  • Page 38 FILE NO. SVM-04017 <How to connect the connecting cable> For RAS-13/10UK Wiring of the connecting cable can be carried out Cord clamp Terminal Terminal block without removing the front panel. cover 1. Remove the air inlet grille. Screw Open the air inlet grille upward and pull it toward Connecting cable you.
  • Page 39 FILE NO. SVM-04017 8-4-5. Piping and drain hose installation How to fix the drains cap 1) Insert hexagonal wrench (4 mm) in a center <Piping and drain hose forming> head. * Since dewing results in a machine trouble, make sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.) 4 mm Rear right...
  • Page 40 FILE NO. SVM-04017 <Left-hand connection with piping> 8-4-6. Indoor unit fixing Bend the connecting pipe so that it is laid within 43 mm 1. Pass the pipe through the hole in the wall, and hook above the wall surface. If the connecting pipe is laid the indoor unit on the installation plate at the upper exceeding 43 mm above the wall surface, the indoor hooks.
  • Page 41: Outdoor Unit

    FILE NO. SVM-04017 8-4-7. Drainage 8-5. Outdoor Unit 1. Run the drain hose sloped downwards. 8-5-1. Installation place • A place which provides the spaces around the NOTE outdoor unit as shown in the left diagram. • Hole should be made at a slight downward slant on •...
  • Page 42 FILE NO. SVM-04017 8-5-2. Refrigerant piping connection (Unit : N·m) Outer dia. 1. Cut the pipe with a pipe cutter. Tightening torque of copper pipe ∅6.35 16 to 18 (1.6 to 1.8 kgf·m) Roughness Warp Obliquity 90° ∅9.52 30 to 42 (3.0 to 4.2 kgf·m) ∅12.70 50 to 62 (5.0 to 6.2 kgf·m) Fig.
  • Page 43 FILE NO. SVM-04017 8-5-3. Evacuating <Packed valve handling precautions> • Open the valve stem all the way out; but do not try After the piping has been connected to the indoor unit, you can perform the air purge together at once. to open it beyond the stopper.
  • Page 44: How To Set Remote Control Selector Switch

    FILE NO. SVM-04017 8-5-4. Wiring connection 8-6. How to Set Remote Control Selector Switch 1. Remove the valve cover from the outdoor unit. 2. Connect the connecting cable to the terminal as When two indoor units ae installed in seperated rooms, identified with their respective matched numbers on there is no need to change the selector switch.
  • Page 45: Others

    FILE NO. SVM-04017 2. Set the remote control selector switch with the 8-7. Others remote control 8-7-1. Gas leak test [B] is indicated on the liquid crystal display when setting remote control selector switch to B. [A] is not indicated on the display even if the selector switch is set to A.
  • Page 46: Troubleshooting Chart

    FILE NO. SVM-04017 9. TROUBLESHOOTING CHART 9-1. Troubleshooting Procedure 9-2-2. Incorrect cable connection between Indoor and outdoor units Follow the details of 9-2. Basic Check Items. The indoor unit is connected to the outdoor unit with If there is no trouble corresponding to 9-2, check 5 cables (Heat pump model) or 3 cables (Cooling Only whether or not there are faulty parts following model).
  • Page 47: Primary Judgement

    FILE NO. SVM-04017 9-3. Primary Judgement 9-3-2. Failure diagnosis The indoor unit diagnoses the operation condition and 9-3-1. Role of indoor unit controller indicates the information of the self-diagnosis with the The indoor unit controller receives the operation lamps on the display panel of the indoor unit. commands from the remote control and executes them.
  • Page 48: Self-Diagnosis By Remote Control (Check Code)

    FILE NO. SVM-04017 9-4. Self-Diagnosis by Remote Control (Check Code) (1) If the lamps are indicated as shown B to G in Table 9-3-1, exchanger the self-diagnosis by the remote control. (2) When the remote control is set to the service mode, the indoor controller diagnoses the operation condition and indicate the information of the self-diagnosis on the display of the remote...
  • Page 49 FILE NO. SVM-04017 Table 9-4-1 Block level Diagnosis function Judgement and action Check Check Block Symptom Conditioner Condition code code status Indoor Thermo. sensor short/ Continued Indicated 1. Check thermo sensor. P.C. board break. operation. when detected 2. If it is OK, check abnormal P.C.
  • Page 50: Troubleshooting Flowcharts

    FILE NO. SVM-04017 9-5. Troubleshooting Flowcharts 9-5-1. Power can not be turned on (No operation at all) <Preliminary checks> Operation (1) Is the supply voltage normal? (2) Is the connection to the AC output OK.? Check Items Heat pump Model Main cause Shut off the power supply from AC outlet once and...
  • Page 51 FILE NO. SVM-04017 Cooling Model Operation Check Items Main cause Shut off the power supply from AC outlet once and Countermeasure turn it on after 5 seconds. Symptom Does the OPERATION lamp blink? Does the power turn on Does the transmission by pushing the [START/ indicator of remote Remote control is...
  • Page 52 Return the wiring of the Does the OPERATION Is it wired as shown power relay is returned to lamp blink? in Figure below? the normal procedure. To the paragraph of “No Power turns on”. RAS-13UKH-ES3 Black White Blue Brown RY01 Indoor Power terminal...
  • Page 53 FILE NO. SVM-04017 RAS-13UK-ES3, RAS-10UK-ES3 Black White Blue Brown RY01 Indoor Power terminal terminal block block CN31 P.C. board 9-5-3. Outdoor unit does not operate Shut off the power supply from AC outlet once and turn it on after 5 seconds. Does the OPERATION lamp blink? See “Power can not be turned on”.
  • Page 54 FILE NO. SVM-04017 9-5-3. Only compressor does not operate Shut off the power supply from AC outlet once and turn it on after 5 seconds. Does the OPERATION lamp blink? See “Power can not be turned on”. Does the power turn on by See “Power can not be turned on”.
  • Page 55 FILE NO. SVM-04017 9-5-4. Only outdoor fan does not operate Shut off the power supply from AC outlet once and turn it on after 5 seconds. Does the OPERATION lamp blink? See “Power can not be turned on”. Does the power turn on by See “Power can not be turned on”.
  • Page 56 FILE NO. SVM-04017 9-5-5. Only 4-Way valve does not operate (During heating operation) Heat Pump model Shut off the power supply from AC outlet once and turn it on after 5 seconds. Does the OPERATION lamp blink? See “Power can not be turned on”. Does the power turn on by See “Power can not be turned on”.
  • Page 57 FILE NO. SVM-04017 9-5-6. Only the indoor fan does not operate <Check procedure> Heat Pump model Shut off the power supply once. Turn the power supply. Does the fan stop in Replace the P.C. board. Control P.C. board is defective. no operating status? Start the operation with low fan setting...
  • Page 58 FILE NO. SVM-04017 Cooling model Shut off the power supply once. Turn the power supply. Does the fan stop in Replace the P.C. board. Control P.C. board is defective. no operating status? Start the operation with low fan setting in cool operation. Does connecting terminal, connecting Does AC 120 V...
  • Page 59: Troubleshooting For Remote Control

    FILE NO. SVM-04017 9-6. Troubleshooting for Remote Control (Including the Indoor P.C. Board) There is no been from the indoor unit. Push the START/STOP button. The operation lamp of the air conditioner main unit does not light. Does the transmission indicator blink? Reset the remote control by use the tip pencil push...
  • Page 60 FILE NO. SVM-04017 9-6-1. How to check the P.C. board (2) Inspection procedres 1) When a P.C. board is judged to be defective, (1) Operating precautions check for disconnection, burning, or discolora- 1) When removing the front panel or the P.C. board, tion of the copper foil pattern or this P.C.
  • Page 61 FILE NO. SVM-04017 (3) Checking procedure Heat pump model Table 9-6-1 Procedure Check Point (Symptom) Causes 1. • Application of shock voltage. Shut off the power supply and 1. Is the fuse blown? • Overload by short-circuit of the remove the P.C. board assembly from the electronic parts base.
  • Page 62: Cooling Model

    FILE NO. SVM-04017 Chec king procedure Cooling model Table 9-6-2 Procedure Check Point (Symptom) Causes Shut off the power supply and 1. Is the fuse blown? 1. Application of shock voltage. remove the P.C. board assembly Overload by short-circuit of the from the electronic parts base.
  • Page 63 FILE NO. SVM-04017 Table 9-6-2 Approximate resistance value of thermo sensor (k Ω) Temperature 0°C 20°C 30°C 25°C 10°C Resistance value 33.8 20.35 12.59 10.00 7.99 9-6-2. How to shorten time of restart delay timer (1) Set the operation mode, temperature, and air flow MODE TEMP.
  • Page 64: Part Replacement

    FILE NO. SVM-04017 10. PART REPLACEMENT 10-1. Indoor Unit Part name Procedures Remarks Front panel How to remove the front panel 1) Stop the operation of the air conditioner and turn off its main power supply. 2) Pull the air inlet grille toward you to open it and remove the air inlet grille.
  • Page 65 FILE NO. SVM-04017 Part name Procedures Remarks Heat exchanger 1) Remove the front panel, electrical part and the horizontal louver following procedure 3. 2) Remove the pipe holder at the rear side of main unit. 3) Remove the 2 screws on the heat exchanger at the base bearing.
  • Page 66: Outdoor Unit

    FILE NO. SVM-04017 10-2. Outdoor Unit Part name Procedures Remarks 2-Screws ∅4 x 22L Common 1) Stop the operation of air-conditioner, and Cord clamp procedure disconnect the power cord from the AC Electric supply. parts cover 2) Remove packed valve cover and Electric parts cover.
  • Page 67: Exploded Views And Parts List

    43T60001 Terminal Block, 2P 43T69364 Fuse, Temperature, 73°C 43T60002 Terminal Block, 3P 43T62003 Cord Clamp 43T69004 TC Sensor 43T69390 P.C. Board (RAS-10UKH-ES3) 10kΩ 25°C 43T69391 P.C. Board (RAS-13UKH-ES3) 43T69005 Sensor, Thermostat 10kΩ 25°C 43T69079 P.C. Board ASSY, WRS-LED MCC-861 - 66 -...
  • Page 68 FILE NO. SVM-04017 11. EXPLODED VIEWS AND PARTS LIST Indoor Unit (E-Parts Assy) (For Cooling model) Location Part Location Part Description Description 43T60002 Terminal Block, 3P 43T62003 Cord Clamp 43T69004 TC Sensor 43T69369 P.C. Board (RAS-10UK-ES3) 10kΩ 25°C 43T69370 P.C. Board (RAS-13UK-ES3) 43T69005 Sensor, Thermostat 10kΩ...
  • Page 69: Indoor Unit

    FILE NO. SVM-04017-1 11-2. Indoor Unit Location Part Location Part Description Description 43T00391 Front Panel Assy 43T49006 Holder, Plate EVA Seal 43T09327 Inlet Grille Assy 43T79302 Guide Drain 43T03302 Back Body Assy 43T22002 Bearing 43T80301 Air Filter 43T39301 Base, Bearing 43T09328 Horizontal Louver 43T20302 Cross Flow Fan 43T08395 LED Panel Assy...
  • Page 70: Outdoor Unit (Ras-13Uah-Es3)

    FILE NO. SVM-04017-3 11-3. Outdoor Unit (RAS-13UAH-ES3) Location Part Location Part Description Description 43T00368 Front cabinet assembly 43T63303 Fixing plate valve 43T03308 Back cabinet assembly 43T47011 Tube capillary ∅1.5ID 43T03328 Base 43T41321 Compressor (PA150XT2-4FM1) 43T00395 Upper cabinet assembly 43T47324 Bolt compressor(M6) 43T09318 Guard fan 43T49008 Cushion rubber 43T62311 Electrical part cover...
  • Page 71: Outdoor Unit (Ras-10Uah-Es3)

    FILE NO. SVM-04017-2 11-4. Outdoor Unit (RAS-10UAH-ES3) Location Part Location Part Description Description 43T00368 Front cabinet assembly 43T47332 Bonnet, 9.52 Dia. 43T03306 Back cabinet assembly 43T63303 Fixing plate valve 43T03329 Base 43T47007 Tube capillary ∅ 1.2IDA 43T00396 Upper cabinet assembly 43T41327 Compressor (PA108X1T-4FZ1) 43T09318 Guard fan 43T47325 Bolt compressor(M6)
  • Page 72: Outdoor Unit (Ras-13Ua-Es3)

    FILE NO. SVM-04017-4 11-5. Outdoor Unit (RAS-13UA-ES3) Location Part Location Part Description Description 43T00368 Front cabinet assembly 43T63303 Fixing plate valve 43T03308 Back cabinet assembly 43T47008 Tube capillary ∅ 1.5IDA 43T03328 Base 43T41321 Compressor (PA150XT2-4FM1) 43T09318 Guard fan 43T47324 Bolt compressor(M6) 43T62311 Electrical part cover 43T49008 Cushion rubber 43T20307 Fan propeller...
  • Page 73: Outdoor Unit (Ras-10Ua-Es3)

    FILE NO. SVM-04017-2 11-6. Outdoor Unit (RAS-10UA-ES3) Location Part Location Part Description Description 43T03303 Fixing plate valve 43T00368 Front cabinet assembly 43T47008 Tube capillary ∅1.5IDA 43T03308 Back cabinet assembly 43T03329 Base 43T41327 Compressor (PA108X1T-4FZ1) 43T47325 Bolt compressor(M6) 43T09318 Guard fan 43T49001 Cushion rubber 43T62311 Electrical part cover 43T52310 Packed valve cover assembly...
  • Page 74 FILE NO. SVM-03006 TOSHIBA CARRIER (THAILAND) CO.,LTD. 144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI, AMPHUR MUANG, PATHUMTHANI 12000, THAILAND. – 71 –...