FILE NO. SVM-12051 1. SAFETY PRECAUTIONS The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual. Be sure to read this installation manual carefully before installing. Recommend to the owner to perform maintenance periodically when using over long periods of time. Be sure to follow the precautions provided here to avoid safety risks.
Page 4
FILE NO. SVM-12051 WARNING • Installation work must be requested from the supplying retail dealership or professional vendors. Self-installation may cause water leakage, electrical shock, or fire as a result of improper installation. • Specified tools and pipe parts for model R410A are required, and installation work must be done in accordance with the manual.
Page 5
FILE NO. SVM-12051 CAUTION • Please read this installation manual carefbefore installing the unit. It contains further important instructions for proper installation. • Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water.
FILE NO. SVM-12051 3. REFRIGERANT R410A This air conditioner adopts the new refrigerant HFC 6. When an air conditioning system charged with a (R410A) which does not damage the ozone layer. large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, The working pressure of the new refrigerant R410A even when refrigerant leaks, its concentration...
Page 9
FILE NO. SVM-12051 Table 3-2-1 Thicknesses of annealed copper pipes Thickness (mm) Nominal diameter Outer diameter (mm) R410A 6.35 0.80 0.80 9.52 0.80 0.80 12.70 0.80 0.80 15.88 1.00 1.00 2. Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm.
Page 10
FILE NO. SVM-12051 d) Flare Processing Make certain that a clamp bar and copper pipe have been cleaned. ØD By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R410A or conven- tional flare tool. Flare processing dimensions differ according to the type of flare tool.
Page 12
FILE NO. SVM-12051 3-3. Tools 3-3-1. Required Tools The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
FILE NO. SVM-12051 3-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
FILE NO. SVM-12051 1. Be sure to make setting so that liquid can be charged. 2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down. It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
Page 15
FILE NO. SVM-12051 3-5-3. Brazing 2. Characteristics required for flux • Activated temperature of flux coincides with the As brazing work requires sophisticated techniques, brazing temperature. experiences based upon a theoretical knowledge, it must be performed by a person qualified. •...
FILE NO. SVM-12051 4. CONSTRUCTION VIEWS 4-1. Indoor Unit Grille Inlet Air filter Front panel Plasma purifier Air inlet Heat exchanger Knock out system Knock out system 60 55 Wireless remote controller Remote controller holder Connecting pipe (0.37m) Drain hose (0.5m) (Flare 6.35) Hanger...
FILE NO. SVM-12051 6. SPECIFICATIONS OF ELECTRICAL PARTS 6-1. Indoor Unit Part s n ame Type Specif icat io ns Fan motor (for indoor) MF-340-30-3 DC250~370, 30W Ω Room temp. sensor (TA-sensor) ( - ) at 25°C Heat exchanger temp. sensor (TC-sensor) 10kΩ...
FILE NO. SVM-12051 7-2. Operation Data <Cooling> Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor condition(°C) RAS- pressure pipe temp. fan mode fan mode revolution Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps) 27/19 35/- B10N3KVP-E 0.9 to 1.1 12 to 14 40 to 42 High...
FILE NO. SVM-12051 8. CONTROL BLOCK DIAGRAM 8-1. Indoor Unit Indoor Unit Control Unit M.C.U. Heat Exchanger Sensor (Tcj) Louver Functions Motor Heat Exchanger Sensor (Tc) • Cold draft preventing Function Room Temperature Sensor (Ta) Louver Motor • 3-minute Delay at Restart for Compressor Drive Control Infrared Rays Signal Receiver •...
FILE NO. SVM-12051 9. OPERATION DESCRIPTION 9-1. Outline of Air Conditioner Control • Detection of inverter input current and current release operation This air conditioner is a capacity-variable type air • Over-current detection and prevention operation conditioner, which uses AC or DC motor for the indoor to IGBT module (Compressor stop function) for motor and the outdoor fan motor.
Page 26
FILE NO. SVM-12051 9-2. Operation Description 1. Basic operation ......................26 1. Operation control ....................26 2. Cooling/Heating operation ..................27 3. AUTO operation ..................... 27 4. DRY operation ......................27 2. Indoor fan motor control ..................... 28 3. Outdoor fan motor control ................... 30 4.
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 1. Basic 1. Operation control operation Receiving the user’s operation condition setup, the operation statuses of indoor/outdoor units are controlled. 1) The operation conditions are selected by the remote controller as shown in the below. 2) A signal is sent by ON button of the remote controller.
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 1. Basic 2. Cooling/Heating operation operation The operations are performed in the following parts by controls according to cooling/heating conditions. 1) Receiving the operation ON signal of the remote controller, the cooling or heating operation signal starts being transferred form the indoor controller to the outdoor unit.
+1.5 *5 : Fan speed = (M + –L) x 1/4 + L +1.0 +0.5 (Linear approximation L(W6) from M+ and L) (Table 1) Indoor fan air flow rate RAS-B10N3KVP-E RAS-B13N3KVP-E RAS-B16N3KVP-E Fan speed COOL HEAT level Fan speed Air flow rate...
Page 30
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 2. Indoor fan <In heating operation> 1) When setting the fan speed to L, motor control L+, M, M+, H or Quiet on the remote controller, the operation is per- formed with the constant speed HEAT ON shown in Fig.
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 3. Outdoor fan The blowing air volume at the outdoor unit side is controlled. 1) The operation command sent motor control from the remote controller is Receiving the operation command from the controller of processed by the indoor unit indoor unit, the controller of outdoor unit controls fan speed.
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 4. Capacity The cooling or heating capacity depending on the load is 1) The difference between set control adjusted. temperature on remote controller (Ts) and room temperature (Ta) According to difference between the setup value of tempera- is calculated.
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 6. Release protective <In cooling/dry operation> 1) When temperature of the indoor control by tempera- heat exchanger drops below 5°C, (Prevent-freezing control for indoor heat exchanger) ture of indoor heat the compressor speed is In cooling/dry operation, the sensor of indoor heat exchanger...
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 7. Defrost control (This function removes frost adhered to the outdoor The necessity of defrost operation is (Only in heating heat exchanger.) detected by the outdoor heat exchanger operation) temperature.
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 8. Louver control This function controls the air direction of the indoor unit. • The position is automatically controlled according to the operation 1) Louver position mode (COOL/HEAT). • The set louver position is stored in memory by the microcomputer, and the louver returns to the stored position when the next operation is performed.
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 9. ECO When pressing [ECO] button on the remote controller, a <Cooling operation> operation Economic operation is performed. 1) The control target temperature <Cooling operation> increase 0.5ºC per hour up to 2ºC This function operates the air conditioner with the difference starting from the set temperature between the set and the room temperature as shown in the...
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 10. Temporary Pressing [RESET] button starts the temporary opera- 1) When pressing [RESET] button, the operation tion of [AUTO] operation. When keeping [RESET] temporary [AUTO] operation starts. button pressed for 10 seconds or more, the temporary 2) When keeping [RESET] button pressed [COOL] operation is performed.
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 11. Air purifying control [Detection of abnormality] 1. Purpose The air purifying control function is to alert the user to trouble in the ionizing or Purifying operation air purifying operation. 2.
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 13. Pulse This function controls throttle amount of the 1) When starting the operation, move the Modulating refrigerant in the refrigerating cycle. valve once until it fits to the stopper. valve (P.M.V.) (Initialize) According to operating status of the air conditioner,...
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 14. Self-Cleaning 1. Purpose function The Self-Cleaning operation is to minimize the growth of mold, bacteria etc. by running the fan and drying so as to keep the inside of the air conditioner clean. Unit now performing cooling or dry operation Self-Cleaning operation When the cooling or dry operation shuts...
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description • Self-Cleaning diagram 14. Self-Cleaning function Operation display FCU fan rpm is depend on presetting. (500RPM) FCU louver OPEN OPEN (12.7º) CLOSE ON or OFF ON or OFF Timer display depend on presetting of timer function.
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 16. QUIET mode When the [QUIET] selected form [Fan] button, the Quiet mode is the system which, control the fan of the indoor unit will be restricted the revolving revolving speed of indoor fan to work −...
FILE NO. SVM-12051 Item Operation flow and applicable data, etc. Description 19. One-Touch One touch comfort is the fully automated operation Operation condition for model to Europe Comfort that is set according to the preferable condition in market a region. When an indoor unit receives "One Touch Comfort Signal"...
FILE NO. SVM-12051 Item Operation flow and applicable data,etc Description • When the level is selected, Power-SEL ([POWER-SEL] button on the remote controller 22. POWER level flashes on LCD display for 3 is pressed) Selection Mode seconds. In case of 75% and 50% The function is used when its circuit breaker is level, number "75"...
FILE NO. SVM-12051 9-3. Auto Restart Function This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of a power supply being accidentally shut down. The operation will resume without warning three minutes after power is restored.
FILE NO. SVM-12051 9-3-2. How to Cancel the Auto Restart Function To cancel auto restart function, proceed as follows : Repeat the setting procedure : the unit receives the signal and beeps three times. The unit will be required to be turned on with the remote controller after the main power supply is turned off. •...
The coutomised settings control temperature air flow strength, air flow direction and other settings to provide you alternate contact with "ONE-TOUCH" OF THE BUTTON. If you prefer other settings you can select from the many other operation functions of your Toshiba unit Press : Start the operaton.
Page 48
FILE NO. SVM-12051 3. COOLING / HEATING / FAN ONLY OPERATION To automatically select cooling, heating, or fan only operation. 1. Press : Select Cool , Heat , or Fan only 2. Press : Set the desired temperature. Cooling: Min. 17°C, Heating : Max, 30°C, Fan Only: No temperature indication 3.
Page 49
FILE NO. SVM-12051 Setting Daily Timer Press for select desired OFF Press for enter ON timer setting timer. Press for select desired Press ON timer. Press again during the Press for enter OFF timer setting ( or ) blink. • During the daily timer is activating, both arrows ( , ) are indicated.
FILE NO. SVM-12051 9-4-3. Name and Functions of Indications on Remote Controller [Display] All indications, except for the clock time indicator, are displayed by pressing the button. Transmission mark TIMER and clock time indicator This transmission mark indicates when the The time setting for timer operation or the clock remote controller transmits signals to the indoor time is indicated.
Shield pipe slightly. Make sure to run the drain hose sloped Plasma air purifier downward. TOSHIBA New IAQ filter Batteries Flat head The auxiliary piping can be connected to Remote control holder wood screw the left, rear left, rear right, right, bottom right or bottom left.
Page 52
FILE NO. SVM-12051 10-2. Installation 10-2-1. Optional installation parts Part Parts name Q'ty Code Refrigerant piping Liquid side : ∅6.35 mm each ∅ Gas side 9.52 mm (10,13k Series) ∅ 12.70 mm (16k Series) Pipe insulating material (polyethylene foam, 6 mm thick) Putty, PVC tapes each Fixing bolt arrangement of outdoor unit...
Page 53
Remote control holder x 1 Flat head wood screw ∅3.1 x 16 s x 2 Wireless remote control x 1 TOSHIBA New IAQ filter (L) x 1 Drain nipple* x 1 Battery x 2 Plasma air purifier x 1 Others Name Owner’s manual...
Page 54
FILE NO. SVM-12051 10-2-3. Installation/Servicing Tools Changes in the product and components In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged accidentally, the service port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch) •...
FILE NO. SVM-12051 10-3. Indoor Unit 10-3-2. Cutting a Hole and Mounting Installation Plate 10-3-1. Installation Place Cutting a hole • A place which provides the spaces around the indoor unit as shown in the above diagram. When installing the refrigerant pipes from the rear. •...
Page 56
FILE NO. SVM-12051 10-3-3. Electrical Work When the installation plate is directly mounted on the wall 1. The supply voltage must be the same as the rated voltage of the air conditioner. 1. Securely fit the installation plate onto the wall by 2.
Page 57
FILE NO. SVM-12051 CAUTION 1. Die-cutting front panel slit CAUTION Cut out the slit on the left or right side of the front • Be sure to refer to the wiring system diagram panel for the left or right connection and the slit labeled inside the front panel.
Page 58
FILE NO. SVM-12051 2. Firmly insert drain cap. Bend the connecting pipe within a radius of 30 mm To connect the pipe after installation of the unit (figure) No gap (To the front flare) Do not apply lubricating oil (refrigerant machine oil) 270 mm Gas side when inserting the drain cap.
Page 59
FILE NO. SVM-12051 10-3-6. Indoor Unit Installation 2. Put water in the drain pan and make sure that the water is being drained outside. 1. Pass the pipe through the hole in the wall, and 3. When connecting extension drain hose, insulate hook the indoor unit on the installation plate at the connection part of extension drain hose with the upper hooks.
Page 60
FILE NO. SVM-12051 10-4. Outdoor Unit Precautions for adding refrigerant 10-4-1. Installation Place • Use a scale having a precision with at least 10 g per index line when adding the refrigerant. • A place which provides enough space around the outdoor unit as shown in the diagram.
Page 61
FILE NO. SVM-12051 10-4-2. Draining the Water 10-4-3. Refrigerant Piping Connection • Holes are provided on the base plate of the Flaring outdoor unit to ensure that the defrost water produced during heating operations is drained off 1. Cut the pipe with a pipe cutter. efficiently.
Page 62
FILE NO. SVM-12051 Tightening Connection Use a vacuum pump Align the centers of the connecting pipes and tighten Be sure to use a vacuum pump with counter-flow the flare nut as much as possible with your fingers. prevention function so that oil inside the pump does Then tighten the nut with a wrench and torque not flow back into the air conditioner pipes when the wrench as shown in the figure.
Page 63
FILE NO. SVM-12051 Stripping length of connecting cable Packed Valve handling precautions • Open the valve stem all the way out, but do not try Terminal block to open it beyond the stopper. Pipe size of Packed Valve Size of Hexagon wrench 12.70 mm and smallers A = 4 mm 15.88 mm...
FILE NO. SVM-12051 10-5. Test Operation 10-5-4. Remote Controller A or B Selection Setting 10-5-1. Gas Leak Test When two indoor units are installed in the separated rooms, it • Check the flare nut connections for gas leaks with is not necessary to change the selector switches. a gas leak detector and/or soapy water.
FILE NO. SVM-12051 11. HOW TO DIAGNOSE THE TROUBLE The pulse motor circuits are mounted to both indoor and outdoor units. Therefore, diagnose troubles according to the trouble diagnosis procedure as described below. (Refer to the check points in servicing written on the wiring diagrams attached to the indoor/outdoor units.) Table 11-1 Troubleshooting Procedure...
Page 66
FILE NO. SVM-12051 CAUTION A high voltage (equivalent to the supply voltage) is also energized to ground through the sensors, PMV and other low-voltage circuits. The sensor leads and other wires are covered with insulated tubes for protection. Nevertheless, care must be taken to ensure that these wires are not pinched.
Page 67
FILE NO. SVM-12051 11-1. First Confirmation 11-1-1. Confirmation of Power Supply Confirm that the power breaker operates (ON) normally. 11-1-2. Confirmation of Power Voltage Confirm that power voltage is AC 220–230–240 ± 10%. If power voltage is not in this range, the unit may not operate normally. 11-1-3.
FILE NO. SVM-12051 11-2. Primary Judgment To diagnose the troubles, use the following methods. 1) Judgment by flashing LED of indoor unit 2) Self-diagnosis by service check remote controller 3) Judgment of trouble by every symptom Firstly use the method 1) for diagnosis. Then, use the method 2) or 3) to diagnose the details of troubles. 11-3.
Page 69
FILE NO. SVM-12051 11-4. Self-Dia gnosis by Remote Controller (Check Code) 1. If the lamps are indicated as shown B to E in Table 11-4-1, execute the self-diagnosis by the remote controller. 2. When the remote controller is set to the service mode, the indoor controller diagnoses the operation condition and indicates the information of the self-diagnosis on the display of the remote controller with the check codes.
Page 70
FILE NO. SVM-12051 11-4-2 Caution at Servicing 1. After using the service mode of remote controller finished, press the [ ] button to reset the remote controller to normal function. 2. After finished the diagnosis by the remote controller, turn OFF power supply and turn its ON again to reset the air conditioner to normal operation.
Page 71
FILE NO. SVM-12051 Block distinction Operation of diagnosis function Action and Judgment Check Check Display flashing Block Cause of operation conditioner code code error status Serial signal 1) Defective wiring of the Indoor unit Flashes when 1) to 3) The outdoor unit never and connecting connecting cable or operates...
Page 72
FILE NO. SVM-12051 Block distinction Operation of diagnosis function Action and Judgment Check Check Display flashing Block Cause of operation conditioner code code error status Outdoor P.C. Current on inverter circuit All OFF Flashes after 1. Remove connecting lead wire of the board is over limit in short time.
Page 73
FILE NO. SVM-12051 Block distinction Operation of diagnosis function Action and Judgment Check Check Display flashing Block Cause of operation conditioner code code error status Compressor drive output error. All OFF Flashes after 1. Check installation conditions such as (Relation of voltage, current error is detected packed valve opening, refrigerant and frequency is abnormal)
Page 74
FILE NO. SVM-12051 Block distinction Operation of diagnosis function Action and Judgment Check Check Display Block Cause of operation conditioner code code flashing error status Compressor does not rotate. All OFF Flashes after 1. Remove connecting lead wire of the Because of missed wiring, error is detected compressor, and operate again.
FILE NO. SVM-12051 11-5. Judgment of Trouble by Every Symptom 11-5-1. Indoor Unit (Including Remote Controller) (1) Power is not turned on (Does not operate entirely) <Primary check> 1. Is the supply voltage normal? 2. Is the normal voltage provided to the outdoor unit? 3.
Page 76
FILE NO. SVM-12051 (3) Only the indoor motor fan does not operate <Primary check> 1. Is it possible to detect the power supply voltage (AC220–240V) between on the terminal block? 2. Does the indoor fan motor operate in cooling operation? (In heating operation, the indoor fan motor does not operate for approximately 10 minutes after it is turned on, to prevent a cold air from blowing in.) Turn off power...
Page 77
FILE NO. SVM-12051 (4) Indoor fan motor automatically starts to rotate by turning on power supply (For DC fan motor) <Cause> The IC is built in the indoor fan motor. Therefore the P.C. board is also mounted to inside of the motor. If the P .C.
Page 78
FILE NO. SVM-12051 (5) Troubleshooting for remote controller <Primary check> Check that A or B selected on the main unit is matched with A or B selected on the remote controller. The unit does not beep at all. Press [ OPERATION lamp on button.
Page 79
FILE NO. SVM-12051 11-5-2. Wiring Failure (Interconnecting and Serial Signal Wire) (1) Outdoor unit does not operate 1) Is the voltage between of the indoor terminal block varied? Confirm that transmission from indoor unit to outdoor unit is correctly performed based upon the follow- ing diagram.
Page 80
FILE NO. SVM-12051 11-6. Check Code 1C (Miswiring in indoor/outdoor units) and 1E <Check procedure> Gas leakage, Discharge temp. error, disconnection of TS/TC gas leakage sensors (Check code 02, 1C) (Check code 03, 1E) Valve drive check Is coil of the pulse motor valve Set it correctly.
FILE NO. SVM-12051 11-7. Troubleshooting 11-7-1. How to Check Whether the Air Purifier is Good or Not Turn off the power breaker once, and turn on again after 10 seconds. To item “Power supply is not turned on” Does the OPERATION indicator flash? Turn off the power breaker and remove CN41 (Micro switch connector).
Page 82
FILE NO. SVM-12051 11-7-2. How to Check Whether the Minus Ion Generator is Good or Not Turn off the power breaker once, and turn on again after 10 seconds. Does the OPERATION indicator flash? To item “Power supply is not turned on” Turn off the power breaker and remove CN41 (Micro switch connector).
FILE NO. SVM-12051 11-8. How to Diagnose Trouble in Outdoor Unit 11-8-1. Summarized Inner Diagnosis of Inverter Assembly Table 11-8-1 Diagnosis/Process flowchart Item Contents Summary Preparation Turn “OFF” the power supply breaker, and remove 3P Remove connector connector which connects of compressor.
FILE NO. SVM-12051 Diagnosis/Process flowchart Item Contents Summary Check Check winding resistance between phases of compres- sor, and resistance between outdoor frames by using a tester. → OK if 10MΩ or more • Is not grounded. Replace control board assembly. ...
Page 85
FILE NO. SVM-12051 (3) Check procedures Table 11-9-1 Procedure Check points Causes Turn off the power supply breaker Check whether or not the fuse (F01) Impulse voltage was applied or the and remove the P.C. board is blown. indoor fan motor short-circuited. assembly from electronic parts base.
Page 87
FILE NO. SVM-12051 11-9-3. Indoor Unit (Other Parts) Part name Checking procedure Room temp. (TA) sensor Disconnect the connector and measure the resistance value with tester. Heat exchanger (TC,Tcj) (Normal temp.) sensor Temperature 10°C 20°C 25°C 30°C 40°C Sensor TA, TC, Tcj (kΩ) 20.7 12.6 10.0...
Page 88
FILE NO. SVM-12051 11-9-5. Checking Method for Each Part Part name Checking procedure Electrolytic capacitor 1. Turn OFF the power supply breaker. (For boost, smoothing) 2. Discharge all three capacitors completely. 3. Check that safety valve at the bottom of capacitor is not broken. 4.
FILE NO. SVM-12051 11-10. How to Simply Judge Whether Outdoor Fan Motor is Good or Bad 1. Symptom • Outdoor fan motor does not rotate. • Outdoor fan motor stops within several tens seconds though it started rotating. • Outdoor fan motor rotates or does not rotate according to the position where the fan stopped, etc. Remote controller check code “02 : Outdoor block, 1A : Outdoor fan drive system error”...
FILE NO. SVM-12051 12. HOW TO REPLACE THE MAIN PARTS WARNING • Since high voltages pass through the electrical parts, turn off the power without fail before proceeding with the repairs. Electric shocks may occur if the power plug is not disconnected. •...
Page 91
FILE NO. SVM-12051 Part name Procedures Remarks Front panel 4) Press "PUSH" part under the front panel and remove hooks of the front panel from Installation plate the installation plate. Front panel Press 5) Remove the front panel fixing screws. (2 pcs.) 6) Take off three hooks of panel from rear side.
Page 92
FILE NO. SVM-12051 Part name Procedures Remarks High voltage 1) Follow to the procedure in the item generator 2) To remove the air ionizer from the back body, pull it toward you. 3) Disconnect the connectors of the high voltage generator.
Page 93
FILE NO. SVM-12051 Part name Procedures Remarks Electric parts 1) Follow the procedure box assembly 2) Remove screw of earth lead attached to the end plate of the evaporator. 3) Remove the lead wire cover, and remove connector for the fan motor and connec- tor for the louver motor from the electric parts box assembly.
Page 94
FILE NO. SVM-12051 Part name Procedures Remarks Horizontal louver 1) Remove shaft of the horizontal louver from the back body. (First remove the left shaft, and then remove other shafts while sliding the horizontal louver leftward.) Evaporator 1) Follow to the procedure in the item (Heat exchanger) 2) Remove the pipe holder from the rear side of the main unit.
Page 95
FILE NO. SVM-12051 Part name Procedures Remarks … Bearing 1) Follow to the procedure in the item 2) Remove the two screws used to secure the bearing base. Two screws 3) Remove the bearing base. <Caution at assembling> • If the bearing is out from the housing, push it into the specified position and then incorporate it in the main body.
Page 96
FILE NO. SVM-12051 12-2. Microcomputer Part name Procedure Remarks Common procedure 1) Turn the power supply off to stop the Replace terminal block, operation of air-conditioner. microcomputer ass’y and the P .C. board ass’y. 2) Remove the front panel. •...
Page 97
FILE NO. SVM-12051 12-3. Outdoor Unit Part name Procedure Remarks Common 1. Detachment procedure Upper cabinet NOTE Wear gloves for this job. Otherwise, you may injure your hands on the parts, etc. Waterproof cover 1) Stop operation of the air conditioner, and turn off the main switch of the breaker for air conditioner.
Page 98
FILE NO. SVM-12051 Part name Procedure Remarks Front cabinet 1. Detachment 1) Perform step 1 in 2) Remove the fixing screws (ST1TØ4 × 10L 2 pcs.) used to secure the front cabinet and inverter cover, the screws (ST1TØ4 ×...
Page 99
FILE NO. SVM-12051 Part name Procedure Remarks Inverter 1) Perform work of item 1 in Inverter cover assembly 2) Remove screw (ST1TØ4 × 10L 2 pcs.) of the P.C. board upper part of the front cabinet. (Soldered surface) •...
Page 100
FILE NO. SVM-12051 Part name Procedure Remarks Control board 1. Disconnect the leads and connectors connected to assembly the other parts from the control board assembly. 1) Leads CN603 • 3 leads (black, white, orange) connected to terminal block. CN601 CN600 CN701...
Page 101
FILE NO. SVM-12051 Part name Procedure Remarks Side cabinet 1. Side cabinet (right) 1) Perform step 1 in and all the steps in 2) Remove the fixing screw (ST1TØ4 × 10L 3 pcs.) used for securing the side cabinet to the bottom plate and valve fixing panel.
Page 102
FILE NO. SVM-12051 Part name Procedure Remarks Compressor 1) Perform work of item 1 of 2) Extract refrigerant gas. 3) Remove the partition board. (ST1TØ4 × 10L 4 pcs.) 4) Remove the sound-insulation material. 5) Remove terminal cover of the compressor, and disconnect lead wire of the compressor from the terminal.
Page 103
FILE NO. SVM-12051 Part name Procedure Remarks Electronic 1. Detachment expansion valve 1) Perform step 1 in , all the steps in coil and 1 in 2) Remove the coil by pull it upward. 2. Attachment 1) Insert a valve coil to value body by push it downward.
Page 104
FILE NO. SVM-12051 Part name Procedure Remarks TE sensor (outdoor heat exchanging temperature sensor) • Attachment Install the sensor onto the straight pipe part of the condenser output pipe. Arrow D Straight Part Sensor lead Detail C Detail B Detail C Detail A TS sensor (Suction pipe temperature sensor) •...
Page 105
FILE NO. SVM-12051 Part name Procedure Remarks Replacement of 1) Cut the sensor 100 mm longer than old temperature sensor one. Cutting here Thermal for servicing only Connector sensor part 2) Cut the protective tube after pulling out it (200 mm). Common service 3) Move the protective tube toward the Cutting here...
FILE NO. SVM-12051-1 13. EXPLODED VIEWS AND PARTS LIST 13-1. Indoor Unit Location Part Location Part Description Description 43T21435 STEPPING MOTOR ASSEMBLY 43T39327 BEARING BASE 43T21428 FAN-MOTOR 43T39343 MOTOR BAND (LEFT) 43T22312 BEARING ASSY, MOLD 43T39329 MOTOR BAND (RIGHT) 43T70313 HOSE, DRAIN 43T09409 HORIZONTAL LOUVER 43T20325 CROSS FLOW FAN ASSEMBLY 43T79313 CAP, DRAIN...
Page 107
13-2. Indoor Unit (E-Parts Assy) Location Part Location Part Description Description 43T69319 TEMPERATURE SENSOR 43T6V313 PC BOARD (RAS-B10N3KVP-E) 43T50306 TEMPERATURE SENSOR 43T6V314 PC BOARD (RAS-B13N3KVP-E) 43T69320 TEMPERATURE SENSOR 43T6V315 PC BOARD (RAS-B16N3KVP-E) 43T62340 CORD-CLAMP 43T60378 TERMINAL 43T6V317 PC BOARD ASSY;WRS-LED 43T60417 TERMINAL –...
FILE NO. SVM-12051 13-3. Outdoor Unit Location Part Location Part Description Description 43T00559 FRONT CABINET(MADE IN THAILAND) 43T00448 FIXING PLATE VALVE 43T00560 LEFT CABINET (MADE IN THAILAND) 43T00563 RIGHT SIDE CABINET ASSEMBLY 43T42345 BASE PLATE ASSEMBLY 43T46347 BODY PMV 43T00561 UPPER CABINET 43T63329 COIL PMV (Made in Thailand)