Super heat recovery multi, indoor/outdoor unit, 1-way / 2-way / 4-way air discharge cassette type, floor standing cabinet type, for commercial use (220 pages)
Per uso commerciale Para uso comercial Para uso comercial Voor commercieel gebruik Indoor Unit Ticari amaçlý kullaným için Model name: High-Wall Type English Installation Manual MMK-AP0073H, MMK-AP0073H-C Manuel d’installation Français MMK-AP0093H, MMK-AP0093H-C MMK-AP0123H, MMK-AP0123H-C Deutsch Installations-handbuch MMK-AP0153H, MMK-AP0153H-C Manuale di installazione Italiano...
Installation Manual SMMS High-Wall Type Please read this Installation Manual carefully before installing the Air Conditioner. • This Manual describes the installation method of the indoor unit. • For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit. ADOPTION OF NEW REFRIGERANT This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.
Installation Manual SMMS High-Wall Type PRECAUTIONS FOR SAFETY • Ensure that all Local, National and International regulations are satisfied. • Read this “PRECAUTIONS FOR SAFETY” carefully before Installation. • The precautions described below include the important items regarding safety. Observe them without fail. •...
Page 5
Installation Manual SMMS High-Wall Type • For the refrigerant recovery work (collection of refrigerant from the pipe to the compressor), stop the compressor before disconnecting the refrigerant pipe. If the refrigerant pipe is disconnected while the compressor is working with the valve open, the compressor sucks air and the refrigeration cycle is over pressurized, which may cause a burst or injury.
Installation Manual SMMS High-Wall Type SELECTION OF INSTALLATION PLACE WARNING • Install the air conditioner at enough strong place to withstand the weight of the unit. If the strength is not enough, the unit may fall down resulting in injury. CAUTION •...
Installation Manual SMMS High-Wall Type Installation diagram of Indoor and outdoor units Before installing the wireless remote Hook controller For the rear left and left piping 1.Remove the battery Installation plate cover. Wall 2.Insert 2 new batteries (R03 [AAA] type) following the (+) and (–) positions.
Installation Manual SMMS High-Wall Type Wireless remote controller • A place where there are no obstacles such as a curtain that may block the signal from the indoor unit. • Do not install the remote controller in a place exposed to direct sunlight or close to a heating source, such as a stove.
Installation Manual SMMS High-Wall Type CUTTING A HOLE AND MOUNTING INSTALLATION PLATE Cutting a hole When the installation plate is directly mounted on the wall In case of installing the refrigerant pipes from the rear: 1. Securely fit the installation plate onto the 1.
Installation Manual SMMS High-Wall Type PIPING AND DRAIN HOSE INSTALLATION Piping and drain hose forming * Apply heat-insulation for both refrigerant pipe and drain hose surely so that no dew generates inside of the equipment. (Use polyethylene foam for insulating material.) Rear right Rear left Removing...
Page 11
Installation Manual SMMS High-Wall Type How to remove the drains cap Clip the drain cap by needle-nose pliers and pull out. How to fix the drains cap 1) Insert hexagonal wrench (dia. 4mm) in a centre head. 2) Firmly insert drains cap. No gap Do not apply lubricating oil (refrigerant machine oil) when inserting the drain cap.
Page 12
Installation Manual SMMS High-Wall Type M In case of bottom right or bottom left piping • After scribing slits of the front panel with a knife or a marking-off pin, cut them with a pair of nippers or an equivalent tool. Slit M Left-hand connection with piping Bend the connecting pipe so that it is laid within 43mm above the wall surface.
Installation Manual SMMS High-Wall Type INDOOR UNIT FIXING DRAINAGE 1. Pass the pipe through the hole in the wall, 1. Run the drain hose sloped downwards. and hook the indoor unit on the installation NOTE plate at the upper hooks. 2.
Installation Manual SMMS High-Wall Type REFRIGERANT PIPING Refrigerant Piping Permissible Piping Length and Height Difference 1. Use copper pipe with 0.8 mm or more thickness. (In case pipe size is dia. 15.9, They vary according to the outdoor unit. with 1.0mm or more.) For details, refer to the Installation Manual attached to the outdoor unit.
Installation Manual SMMS High-Wall Type Tightening connection Heat insulation Heat insulation for the pipes should be done CAUTION separately for the liquid side and gas side. Because both of the liquid and gas side pipes become a low • Do not apply excessive torque. Otherwise, the temperature during cooling operation, sufficient nut may crack depending on the conditions.
Installation Manual SMMS High-Wall Type ELECTRIC WORK • Run the refrigerant piping line and control wiring WARNING line in the same line. • Do not turn on the power of the indoor unit until 1. Using the specified wires, ensure to vacuuming of the refrigerant pipes completes.
Page 17
Installation Manual SMMS High-Wall Type Power supply wire and communication wires specifications Power supply wire and communication wires are procured locally. For the power supply specifications, follow the table below. Power supply wiring and communication wiring are to be procured locally. For specifications of the power capacity of the outdoor unit and the power supply wires, refer to the Installation Manual supplied with the outdoor unit.
Installation Manual SMMS High-Wall Type Indoor unit Indoor unit Indoor unit Indoor unit Wired remote controller wiring (Max. 8 units) Wired remote Remote controller inter-unit wiring controller Control wiring between indoor and outdoor units NOTE An outdoor unit that is interconnected to the indoor units automatically becomes the header unit. M Wiring example Outdoor Power supply Outdoor Power supply...
Page 19
Installation Manual SMMS High-Wall Type Wired remote controller wiring • As the wired remote controller wire has non-polarity, there is no problem if connections to indoor unit terminal blocks A and B are reversed. M Wiring diagram Terminal block for remote controller Terminal block wiring of indoor unit...
Installation Manual SMMS High-Wall Type Wiring Connection Power supply terminal block R(L) S(N) Terminal block for How to connect the power supply wiring communication/remote controller wiring and control wiring Terminal The power supply wire and the control wire can be Cord Cover clamp...
Page 21
Installation Manual SMMS High-Wall Type Wiring connection for flow selector unit How to connect the wiring of flow selector unit Connect the power supply wire and the communication wire supplied with the flow selector unit to the indoor unit. 1.
Installation Manual SMMS High-Wall Type APPLICABLE CONTROLS A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller. Changing of settings of for REQUIREMENT applicable controls • When you use this air conditioner for the first time, it takes approx.
Page 23
Installation Manual SMMS High-Wall Type Procedure Change of lighting time of filter Each time you push button, indoor unit sign numbers in the control group change cyclically. According to the installation condition, the lighting Select the indoor unit you want to change settings time of the filter sign (Notification of filter cleaning) for.
Installation Manual SMMS High-Wall Type Adjustment of air direction 1. Using the remote controller switch, change the up/down air direction by moving the horizontal louver. 2. Adjust the right/left air direction by bending the vertical grille inside of the air outlet port with hands.
Installation Manual SMMS High-Wall Type TEST RUN A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller. Before test run In case of wired remote controller • Before turning on the power supply, carry out the 2, 4 following procedure.
Page 26
Installation Manual SMMS High-Wall Type In case of wireless remote controller (Forced test operation is performed in a different way.) REQUIREMENT • For the operation procedure, be sure to follow the Owner’s Manual. • Finish the forced cooling operation in a short time because it applies excessive strength to the air conditioner.
Installation Manual SMMS High-Wall Type TROUBLE SHOOTING A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller. Confirmation and check Procedure Every pushing of “TEMP.” button used to When a trouble occurred in the air conditioner, the set temperature, the trouble history stored in check code and the indoor UNIT No.
Installation Manual SMMS High-Wall Type Check method On the remote controller (Wired remote controller, Central control remote controller) and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C.
Page 29
Installation Manual SMMS High-Wall Type Sending error in communication — between outdoor units — Duplicated follower outdoor addresses No. of outdoor units which Decrease of No. of connected outdoor received signal normally units E28 Detected outdoor unit number Follower outdoor unit error 01: IPDU1 error 02: IPDU2 error 03: IPDU1, 2 error...
Page 30
I/F Differs according to error contents of unit with occurrence of alarm Group control branching unit error TCC-LINK — — (L20 is displayed.) Duplicated central control addresses TCC-LINK: TOSHIBA Carrier Communication Link. 29-EN – 29 –...
Page 31
Installation Manual SMMS High-Wall Type MEMO ........................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................–...