Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
Page 4
Definition of Protective Gear When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and “safety” work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below.
Page 5
Warning Indications on the Air Conditioner Unit [Confirmation of warning label on the main unit] Confirm that labels are indicated on the specified positions If removing the label during parts replace, stick it as the original. This mark is for R32 refrigerant only. Refrigerant type is written on nameplate of outdoor unit.
Page 6
CAUTION CAUTION Do not touch the aluminum fins Do not touch the aluminum fins of the of the unit. unit. Doing so may result in injury. Doing so may result in injury. CAUTION CAUTION BURST HAZARD BURST HAZARD Open the service valves before the operation, Open the service valves before otherwise there might be the burst.
Page 7
Precaution for Safety The appliance shall be installed in accordance with national wiring regulations. Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire. DANGER Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breaker to the OFF position.
Page 8
When you access inside of the electric cover to repair electric parts, wait for about five minutes after turning off the breaker. Do not start repairing immediately. Otherwise you may get electric shock by touching terminals of high-voltage capacitors. Natural discharge of the capacitor takes Electric about five minutes.
Page 9
When performing repairs using a gas burner, replace the refrigerant with nitrogen gas because the oil that coats the pipes may otherwise burn. When repairing the refrigerating cycle, take the following measures. 1) Be attentive to fire around the cycle. When using a gas stove, etc., be sure to put out fire before work;...
Page 10
When the refrigerant gas leaks, find up the leaked position and repair it surely. If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. When gas touches to fire such as fan heater, stove or cocking stove, it may generate noxious gases, causing a fire though the refrigerant gas itself is innocuous.
Page 11
Only a qualified installer ( 1) or qualified service person ( 1) is allowed to install the air conditioner. If the air conditioner is installed by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result. Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install the air conditioner.
Page 12
( 1) Refer to the “Definition of Qualified Installer or Qualified Service Person.” Declaration of Conformity Manufacturer: TOSHIBA CARRIER (THAILAND) CO., LTD. 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand TOSHIBA CARRIER EUROPE S.A.S...
Page 13
Specifications Sound power level (dBA) Model Weight (kg) Cooling Heating RAV-GM301ATP-E RAV-GM301ATJP-E RAV-GM401ATP-E RAV-GM401ATJP-E RAV-GM301ATP-TR RAV-GM401ATP-TR RAV-GM301ATP-NZ RAV-GM401ATP-NZ : Under 70 dBA – 13 –...
Page 14
Refrigerant R32 This air conditioner adopts a new HFC type refrigerant (R32) which does not deplete the ozone layer. 1. Safety Caution Concerned to Refrigerant R32 Be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with refrigerant R32 during installation work or service work.
Page 15
<Caution items> 1) The opposite side dimension of the air-conditioner's flared nut using R32 and the shape of the charge port are the same as those of R410A. 2) Be careful not to charge refrigerant by mistake. Should the different type of refrigerant mix in, be sure to recharge the refrigerant 3) Do not mix the other refrigerant or refrigerating oil with the refrigerant.
Page 16
4. Tools Tools exclusive for R410A (The following tools for R410A are required.) : R410A tools available : Partly unavailable, : R410A tools unavailable Installation/service tools Applicability to R32 air Applicability to R22 air conditioner or not conditioner or not Tools / Equipment specification 1 Flare tool...
1. SPECIFICATIONS 1-1. Outdoor Unit <Digital Inverter> Model name Outdoor unit RAV-GM 301AT * P * 401AT * P * 1 phase 220-240V, 50Hz Power supply 1 phase 220V, 60Hz Type Rotary DC Invertor Compressor Motor (kW) 0.75 Pole Refrigerant charged (kg) 0.63 0.90...
1-2. Operation Characteristic Curve RAV-GM301AT P <Cooling> < > Conditions Conditions Indoor : DB 27 C/WB 19 Indoor : DB 20 Outdoor : DB 35 Outdoor : DB 7 C/WB 6 Air Flow : High Air Flow : High Pip Length : 7.5m Pip Length : 7.5m Voltage : 230V Voltage : 230V...
3-2. Operation Data RAV-GM301AT P <Cooling> Tempeature Heat exchanger pipe Standard Indoor Outdoor Compressor condition(°C) temp. pressure fan mode fan mode revolution Indoor Outdoor TE (°C) P (MPa) TC (°C) TS (°C) (rps) 27/19 35/- 37 to 41 0.9 to 1.1 13 to 15 13 to 15 High High...
5. SPECIFICATIONS OF ELECTRICAL PARTS RAV-GM301AT Parts name Type Specifications Compressor KSK89D53UFZ 3 phase, 6P, 712W Fan motor WDF-340-A43-1 Output 43 W 4-way valve coil SQ-A2522G-00352 PMV coil PQ-M10012-000313 Reactor CH-69-Z-T 19mH, 10A P.C. board WP-030 Fuse (Mounted on P.C. board) AC250 V, 25 A Fuse AC250 V, 6.3 A...
6. REFRIGERANT R32 This air conditioner adopted the R32 refrigerant 6. When an air conditioning system charged with a which does not damage the ozone layer. large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, The working pressure of the refrigerant R32 even when refrigerant leaks, its concentration is 1.6 times higher than conventional refrigerant...
Page 27
Table 6-2-1 Thicknesses of annealed copper pipes Thickness (mm) Nominal diameter Outer diameter (mm) 12.7 15.9 1. Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm.
Page 28
c) Insertion of Flare Nut d) Flare Processing Make certain that a clamp bar and copper pipe have been cleaned. By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R410A/R32 or conventional flare tool. ØD Flare processing dimensions differ according to the type of flare tool.
Page 29
Fig. 6-2-2 Relations between flare nut and flare seal surface 2. Flare Connecting Procedures and Precautions a) Make sure that the flare and union portions do not have any scar or dust, etc. b) Correctly align the processed flare surface with the union axis. c) Tighten the flare with designated torque by means of a torque wrench.
6-3. Tools 6-3-1.Required Tools Refer to the “4. Tools” (Page 13) 6-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment.
6-5. Brazing of Pipes 6-5-1. Materials for Brazing 3. Types of flux • Noncorrosive flux 1. Silver brazing filler Generally, it is a compound of borax and boric Silver brazing filler is an alloy mainly composed acid. of silver and copper. It is used to join iron, copper It is effective in case where the brazing tem- or copper alloy, and is relatively expensive though perature is higher than 800°C.
Page 32
6-5-3. Brazing As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified. Flow meter In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to Stop valve proceed with brazing while letting dry Nitrogen gas (N2) flow.
6-6. Instructions for Re-use Piping of R22 or R407C Instruction of Works: 5. When a commercially available dryer is attached to the existing pipes. The existing R22 and R407C piping can There is the possibility that copper green rust has be reused for our super digital inverter been generated.
Page 34
6-6-4. Final Installation Checks Are there no scratch or dent on the existing pipes? Existing pipe: NO ∗ Use a new pipes. Is it possible to operate the existing air conditioner? ∗ After the existing air conditioner is operated in cooling mode for approx.
Page 35
6-6-5. Handling of Existing Pipe Piping necessary to change the flare nut/ machining size due to pipe compression. When using the existing pipe, carefully check it for the following: 1) Flare nut width: H (mm) Wall thickness (within the specified range) Copper pipe Ø6.4 Ø9.5...
6-7. Replenishing refrigerant In order to assure the reliability of the appliance, the amount of refrigerant to be replenished shall be subject to the following restrictions. Follow the margin of excess replenished refrigerant, which is equivalent to the current R22. Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in failure, explosion of the product, or personal injury.
Page 37
6-8 General safety precautions for using R32 refrigerant 6-8-1 Recovery 6-8-2 Decommissioning ・ When removing refrigerant from a system, either ・Before carrying out this procedure, it is essential that for servicing or decommissioning, it is recommended the technician is completely familiar with the good practice that all refrigerants are removed safely.
7. OUTDOOR CONTROL CIRCUIT 7-1. Outline of Main Controls 1. Pulse Modulating Valve (PMV) control 1) For PMV 50 to 500 pulses during operation. 2) In cooling operation, PMV is controlled with the temperature difference between TS sensor and TC sensor.
Page 39
Item Operation flow and applicable data, etc. Description 3. Outdoor fan The blowing air volume at the outdoor unit side is controlled. 1) The operation command sent motor control from the remote controller is Receiving the operation command from the controller of processed by the indoor unit (for GM30) indoor unit, the controller of outdoor unit controls fan speed.
Page 40
Item Operation flow and applicable data, etc. Description 3. Outdoor fan The blowing air volume at the outdoor unit side is controlled. 1) The operation command sent motor control from the remote controller is Receiving the operation command from the controller of processed by the indoor unit (for SM40) indoor unit, the controller of outdoor unit controls fan speed.
Page 41
Item Operation flow and applicable data, etc. Description 4. Capacity The cooling or heating capacity depending on the load is 1) The difference between set control adjusted. temperature on remote controller (Ts) and room temperature (Ta) According to difference between the setup value of tempera- is calculated.
Page 42
Item Operation flow and applicable data, etc. Description 6. Release protective <In cooling/dry operation> 1) When temperature of the indoor control by heat exchanger drops below 5°C, (Prevent-freezing control for indoor heat exchanger) temperature of the compressor speed is re- In cooling/dry operation, the sensor of indoor heat indoor heat duced.
Page 43
Item Operation flow and applicable data, etc. Description 7. Defrost control (This function removes frost adhered to the outdoor The necessity of defrost operation is (Only in heating heat exchanger.) detected by the outdoor heat exchanger operation) temperature. The conditions to detect the The temperature sensor of the outdoor heat ex- necessity of defrost operation differ in A, changer (Te sensor) judges the frosting status of the...
8. TROUBLESHOOTING 8-1. Summary of Troubleshooting <Wired remote controller type> 1. Before troubleshooting 1) Required tools/instruments • ⊕ and ⊖ screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch • Tester, thermometer, pressure gauge, etc. 2) Confirmation the following points before check a) The following operations are normal.
Page 46
<Wireless remote controller type> 1. Before troubleshooting 1) Required tools/instruments • ⊕ and ⊖ screwdrivers, spanners, radio cutting pliers, nippers, etc. • Tester, thermometer, pressure gauge, etc. 2) Confirmation the following points before check a) The following operations are normal. 1.
8-2. Troubleshooting 8-2-1. Outline of judgment The following method can be done to check whether the problem occurred in indoor or outdoor unit. The error is indicated by indication lamp on the display of the indoor unit. (sensors of the receiving part) The indoor unit monitors the operating status of the air conditioner, and the blocked contents of self-diagnosis are displayed restricted to the following cases if a protective circuit works.
Page 49
8-2-3. Monitor Function of Remote Controller Switch Calling of sensor temperature display <Contents> Each data of the remote controller, indoor unit and outdoor unit can be shown by calling the service monitor mode from the remote controller. <Procedure> <RBC-AMT32E> TEST Push buttons simultaneously for 4 seconds to call the service monitor mode.
Page 52
Error mode detected by indoor unit Operation of diagnostic function Judgment and measures Check Status of Cause of errors Condition code air conditioner 1. Check cables of remote controller and communication adapters. No communication from remote Stop Displayed when Remote controller LCD display OFF (Disconnection) controller (including wireless) and (Automatically error is detected...
Page 53
Error mode detected by outdoor unit Operation of diagnostic function Check code Status of Judgment and measures Cause of errors Condition air conditioner Indoor unit 1. Check discharge temp. sensor (TD). Disconnection, short of discharge Displayed when Stop temp. sensor (TD) error is detected 2.
Page 54
Operation of diagnostic function Check code Status of Judgment and measures Cause of errors Condition air conditioner Indoor unit Displayed when 1. Check outdoor P.C. board. Current detection circuit error Stop error is detected (AC current detection circuit) Discharge temp. error 1.
Page 55
Error mode detected by remote controller or central controller (TCC-LINK) Operation of diagnostic function Judgment and measures Status of Cause of errors Check code Condition air conditioner Power supply error of remote controller, Indoor EEPROM error 1. Check remote controller inter-unit wiring. No communication with master indoor unit 2.
Page 56
Check Outdoor Check and troubleshooting code LED display (Item without special mention Indicates part of outdoor unit.) [E04] [Indoor / Outdoor communication error] — Is setting of group address Check item code [14]. on the remote controller correct? Are inner wiring of the indoor unit Correct wiring and inter-unit wires (1, 2, 3) correct? and inter-unit wires.
Page 57
Check Outdoor Check and troubleshooting code LED display (Item without special mention Indicates part of outdoor unit.) — [F08] [Outside air temp. sensor (TO) error] Correct connector. Is CN63 connection correct? Is resistance value of TO sensor correct? Sensor error → Replace Check outdoor P.C.
Page 58
Check Outdoor Check and troubleshooting code LED display (Item without special mention Indicates part of outdoor unit.) — [F31] [EEPROM error] Check outdoor P.C. board. Defect → Replace [H01] [Compressor break down] — Is power supply voltage correct? Correct power supply line. 50 Hz : AC 198 to 264 V 60 Hz : AC 198 to 242 V Is wire connection correct?
Page 59
Check Outdoor Check and troubleshooting code LED display (Item without special mention Indicates part of outdoor unit.) — [H03] [Current detection circuit error] Check outdoor P.C. board. Defect → Replace [L10] — [Unset model type] : Only when service P.C. board is used Cut jumper line according to the explanation sheet packaged with the service P.C.
Page 60
Check Outdoor Check and troubleshooting code LED display (Item without special mention Indicates part of outdoor unit.) [P15] [Gas leak detection] — Is there gas leak? Repair defective position. Is there refrigerant shortage? Recharge refrigerant. Correct defective position. Is PMV under correct condition? Replace defective part.
Page 61
Check Outdoor Check and troubleshooting code LED display (Item without special mention Indicates part of outdoor unit.) [P20] [High pressure protective operation] — Is service valve fully opened? Open service valve fully. Reset the power supply and then make a test run Cooling season matching to the season.
Page 62
Check Outdoor Check and troubleshooting code LED display (Item without special mention Indicates part of outdoor unit.) [P22] — [Fan system error] Is the power supply voltage is lower than or over the range? Check wiring construction. 50 Hz : AC 198 to 264 V Ask to repair the power supply.
Page 63
8-2-5. Diagnostic Procedure for Each Check Code (Outdoor Unit) Temperature sensor Temperature – Resistance value characteristic table TA, TC, TCJ, TE, TS, TO sensors TD sensors Representative value Representative value Resistance value (kΩ Ω Ω Ω Ω ) Resistance value (kΩ Ω Ω Ω Ω ) Temperature Temperature (°C)
Page 64
8-3. Table Inspection of outdoor unit main parts Parts name Checking procedure Compressor Measure the resistance value of each winding by using the tester. (Model : KSK89D53UFZ) Position Resistance value Red – White 2.35±7% Ω White – Black White Black Black –...
9. SETUP AT LOCAL SITE AND OTHERS 9-1. Calling of Error History <Contents> The error contents in the past can be called. <Procedure> TEST Push buttons simultaneously for 4 seconds or more to call the service check mode. TEMP. ON / OFF Service Check goes on, the CODE No.
Page 66
Indoor unit power-ON sequence Power ON ë The unit without power feed waits entirely → Waiting status is released by system start ë Reboot when power is fed on the way <By feed unit> <Automatic address judgment> Gr construction check 3 minutes elapse Normal ∗...
10. ADDRESS SETUP 10-1. Address Setup Procedure When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address setup completes with power-ON of the outdoor unit.
10-2. Address Setup & Group Control <Terminology> Indoor unit No. : N - n = Outdoor unit line address N (Max. 30) - Indoor unit address n (Max. 64) Group address : 0 = Single (Not group control) 1 = Master unit in group control 2 = Sub unit in group control Master unit (= 1) : The representative of multiple indoor units in group operation sends/receives signals to/from the remote controllers and sub indoor units.
Page 69
10-2-2. Automatic Address Example from Unset Address (No miswiring) 1. Standard (One outdoor unit) 1) Single (Master/Sub) Individual 2) Group operation (Multiple outdoor units = Miltiple indoor units only with serial communication) Sub/Header Sub/Header Sub/Follower Master/Header Sub/Follower Only turning on source power supply (Automatic completion) Header unit: The header unit receives the indoor unit data (thermo status) of the follower •...
Page 70
10-2-3. Automatic Address Example from Unset Address (No miswiring) 1. Standard (One outdoor unit) 1) Single Individual (Master/Header) Only turning on source power supply (Automatic completion) 2. Group operation (Multiple outdoor units = Multiple indoor units with serial communication only, without twin) Sub/Header Sub/Header Master/Header...
10-3. Remote Controller Wiring Strip off approx. 9 mm the wire to be connected. Wiring diagram • For single system, use non polarity, 2 core wire is • used for wiring of the remote controller. Terminal block for remote controller Terminal block (0.5 mm²...
TEST Push buttons simultaneously for 4 seconds or more. (← ← ← ← ← Line address) Using the temperature setup buttons, to the CODE No. Using timer time buttons, set the line address. Push button. (OK when display goes on.) (←...
Page 73
2. To know the position of indoor unit body by address ë To confirm the unit No. in the group control (Follow to the procedure during operation) (in this procedure, the indoor units in group control stop.) <Procedure> The indoor unit numbers in the group control are successively displayed, and fan, louver, and drain pump of the corresponding indoor unit are turned on.
11. HOW TO EXCHANGE COMPRESSOR 11-1. Exchanging Procedure of Compressor (Outline) START Open PMV forcedly and then recover refrigerant Has refrigerant recovery work been done? using a refrigerant recovery unit. Turn off the leakage breaker. Never recover the refrigerant to the outdoor unit. For the refrigerant recovery work during reinstallation Remove the defective compressor.
12. DETACHMENTS 12-1. RAV-GM301AT , GM401AT Part name Procedure Remarks Common CAUTION procedure Never forget to put on the gloves at working Valve cover time, otherwise an injury will be caused by the parts, etc. 1. Detachment Stop operation of the air conditioner, and turn off the main switch of the breaker for air conditioner.
Page 76
Part name Procedure Remarks 1. How to remove Front Motor base cabinet 1) Perform 1 of 1. 2) Remove the screw between front cabinet and side cabinet (right). (ST1T Ø4 × 10 , 1 pc.) 3) Remove the screw between front cabinet and inverter.
Page 77
Part name Procedure Remarks 1. Detachment Inverter Screws assembly 1) Perform work of item 1 of 2) Take off screws of the upper part of the front cabinet. (ST1T Ø4 ×10L, 2 pcs.) • If removing the inverter cover under this condition, P .C.
Page 79
Part name Procedure Remarks 1) Take off 1 screws (ST1T Ø4 × 10L) that Control P.C. fixed between ASM-COV-WIRING and board inverter box. then disengage ASM-COV- assembly WIRING from inverter box. 2) Remove P.C.board base’s hook (Hook 1, 2, 3, 4), hold P.C.board base, pull inverter box up.Remove lead wire ・...
Page 80
Part name Procedure Remarks Rear cabinet 1) Perform works of items 1 of 1 and 2 , 3 . 2) Take off fixed screws for the bottom plate. (ST1T Ø4 × 10L, 2 pcs.) 3) Take off fixed screw for the valve mounting plate.
Page 81
Part name Procedure Remarks Compressor 1) Perform works of items 1 of 1 and 2 , Partition plate 2) Discharge refrigerant gas. 3) Remove the partition plate. (ST1T Ø4 × 10L, 3 pcs.) 4) Remove the terminal covers of the compressor, and disconnect lead wires of the compressor and the compressor thermo assembly from the terminal.
Page 82
Part name Procedure Remarks 1. Detachment Pulse Motor Valve (PMV) coil 1) Perform works of items Attachment state 2) Release the coil from the concavity by turning it, and remove coil from the PMV. 2. Attachment 1) Put the coil deep into the bottom posi- tion.
Page 97
<Inverter assembly GM40> TE Sensor (Ø6) TO Sensor (Ø6) TS Sensor (Ø6) TD Sensor (Ø4) – 97 –...
Page 98
RAV- Ref.No. Parts No. Description GM401ATJP-E 43T62351 HEATSINK 43T6W749 PC BOARD ASSY 43T60384 TERMINAL-6P 43T60326 FUSE 43T50369 TEMPERATURE SENSOR 43T50336 TEMPERATURE SENSOR 43T50370 TEMPERATURE SENSOR 43T50371 TEMPERATURE SENSOR 43T62313 PC PLATE BASE 43T60463 FUSE 43T60425 FUSE HOLDER – 98 –...
Page 99
WARNINGS ON REFRIGERANT LEAKAGE Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R32 which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer.