7-7-3. Error Clearing Function

(1)Clearing from the main remote controller
Error clearing in outdoor unit
Error of the outdoor unit currently detected is cleared by the unit of one refrigerant circuit system to which the indoor
units operated by the remote controller is connected. (Error of the indoor unit is not cleared.)
For clearing errors, the service monitor function of the remote controller is used.
<Method>
1
Change the mode to service monitor mode by pushing
seconds or more.
2
Using
buttons, set CODE No. to "FF".
3
The display in Section A in the following figure is counted with interval of 5 seconds as
"0005" --> "0004" --> "0003" --> "0002" --> "0001" --> "0000".
When the count arrives "0000", the error is cleared.
*However, counting from "0005" is repeated on the display.
4
When
button is pushed, the status returns to the normal status.
Error clearing in indoor unit
Error in the indoor unit is cleared by
(Only error of the indoor unit connected with operating remote controller is cleared.)
3
Section A
TEMP.
2
FILTER
RESET
TEST
4
button on the remote controller.
– 149 –
+
buttons simultaneously for 4
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
VENT
SET
CL
SWING/FIX
UNIT LOUVER
1