SPLIT-TYPE, HEAT PUMP 2005 AIR CONDITIONERS SERVICE MANUAL Series PEAD R407C/R410A <indoor unit> Service ref. NOTE: Models PEAD-RP60GA • This manual describes only service data of the indoor PEAD-RP71GA units. PEAD-RP100GA CONTENTS 1. REFERENCE MANUAL ····························· 2 2. SAFETY PRECAUTION ···························· 3 3.
SAFETY PRECAUTION CAUTIONS RELATED TO NEW REFRIGERANT Cautions for units utilising refrigerant R407C Do not use the existing refrigerant piping. Use liquid refrigerant to charge the system. The old refrigerant and lubricant in the existing piping If gas refrigerant is used to seal the system, the composition contains a large amount of chlorine which may cause the of the refrigerant in the cylinder will change and performance lubricant deterioration of the new unit.
Page 4
[3] Service tools Use the below service tools as exclusive tools for R407C refrigerant. Tool name Specifications Gauge manifold ·Only for R407C. ·Use the existing fitting SPECIFICATIONS. (UNF7/16) ·Use high-tension side pressure of 3.43MPa·G or over. Charge hose ·Only for R407C. ·Use pressure performance of 5.10MPa·G or over.
Page 5
CAUTIONS RELATED TO NEW REFRIGERANT <Cautions for units utilizing refrigerant R410A> Use new refrigerant pipes. Do not use refrigerant other than R410A. n case of using the existing pipes for R22, be careful with f other refrigerant (R22 etc.) is used, chlorine in refrige- the following.
Page 6
Unit ravimeter [3] Service tools Use the below service tools as exclusive tools for R410A refrigerant. Specifications Gauge manifold • Only for R410A • Use the existing fitting specifications . (UNF1/2) • Use high-tension side pressure of 5.3MPa·G or over. Charge hose •...
PART NAMES AND FUNCTIONS Indoor Unit • Air intake (sucks the air from inside the room into the unit) Air outlet...
Page 8
• Remote controller Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button. • Operation buttons ON/OFF button Set Temperature buttons Down Fan Speed button Timer Menu button (Monitor/Set button) Filter button (<Enter>...
SPECIFICATION Service Ref. PEAD-RP60GA Power supply Single phase, 50Hz, 220-240V ❇ Input 0.18 ❇ Running current 0.80 ❇ Starting current 1.03 External finish Galvanized sheets Heat exchanger Plate fin coil Fan (drive) × No. Centrifugal (direct) × 2 Fan motor output 0.10...
OUTLINES & DIMENSIONS 1. INDOOR UNIT PEAD-RP60, 71, 100GA ❊ Service space:550 or more 2XG-ø2.9 Refrigerant piping flare connection(liquid øH copper tube):HP 120XE=F Refrigerant piping flare connection(gas øJ copper tube):LP 100~200 Electrical parts box Terminal bed : Power source Access door Terminal bed : Remote control Filter Drain pan (R1 External thread: ø34)(❊;Fixable to opposition side.)
WIRING DIAGRAM PEAD-RP60, 71, 100GA INSIDE SECTION OF CONTROL BOX <❊A> (IN CASE OF CONNECT THE REPLACEMENT WIRING) POWER SUPPLY ~(1PHASE) I.B. 230V 50Hz 1 2 3 1 2 3 4 5 6 7 8 9 TO OUTDOOR UNIT CN20 CN21 CN29 CN31...
TROUBLESHOOTING 9-1. TROUBLESHOOTING <Error code display by self-diagnosis and actions to be taken for service (summary)> Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service and the inferior phenomenon reoccurrence at field are summarized in the table below. Check the contents below before investigating details.
Page 16
Note: Refer to the manual of outdoor unit for the details of display 9-2. SELF-DIAGNOSIS ACTION TABLE such as F, U, and other E. Error Code Meaning of error code and detection method Countermeasure Cause Abnormality of room temperature 1 Defective thermistor 1–3 Check resistance value of thermistor.
Page 17
Error Code Meaning of error code and detection method Countermeasure Cause Freezing/overheating protection is (Cooling or drying mode) (Cooling or drying mode) working 1 Clogged filter (reduced airflow) 1 Check clogs of the filter. 1 Freezing protection (Cooling mode) 2 Short cycle of air path 2 Remove shields.
Page 18
Error Code Meaning of error code and detection method Countermeasure Cause Abnormality of pipe temperature ther- 1 Defective thermistor 1–3 Check resistance value of thermistor. mistor / Condenser-Evaporator (TH5) For characteristics, refer to (P1) above. characteristics 2 Check contact failure of connector (CN29) 1 The unit is in three-minute resume pro- 2 Contact failure of connector on the indoor controller board.
Page 19
Error Code Meaning of error code and detection method Countermeasure Cause ∗ Check LED display on the outdoor control cir- Indoor/outdoor unit communication 1 Contact failure, short circuit or, error (Signal receiving error) cuit board. (Connect A-control service tool, mis-wiring (converse wiring) of 1 Abnormal if indoor controller board PAC-SK52ST.) indoor/outdoor unit connecting...
Page 20
9-3. TROUBLESHOOTING BY INFERIOR PHENOMENA Note: Refer to the manual of outdoor unit for the detail of remote controller. Phenomena Cause Countermeasure (1)LED2 on indoor controller board • When LED1 on indoor controller board is also off. 1 Power supply of rated voltage is not supplied to out- 1 Check the voltage of outdoor power is off.
Page 21
Note: Refer to the manual of outdoor unit for the detail of remote controller. Phenomena Cause Countermeasure (2)LED2 on indoor controller board • When LED1 on indoor controller board is also blinking. Check indoor/outdoor unit connecting wire Connection failure of indoor/outdoor unit connecting for connection failure.
Page 22
9-4. When wired remote controller or indoor unit micro computer troubles 1. If there is not any other wrong when trouble occurs, emergency operation starts as the indoor controller board switch (SWE) is set to ON. During the emergency operation the indoor unit is as follows; (1) Indoor fan high speed operation (2) Drain-up machine operation 2.
Page 23
9-5. HOW TO CHECK THE PARTS PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA Parts name Check points Room temperature Disconnect the connector then measure the resistance using a tester. thermistor (TH1) (Surrounding temperature 10:~30:) Pipe temperature thermistor (TH2) Normal Abnormal (Refer to the thermistor) Condenser/Evaporator 4.3k"~9.6k"...
Page 24
9-6.TEST POINT DIAGRAM 9-6-1. Power board PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA CN2S Connect to the indoor controller board (CN2D) Between 1 1 to 3 3 12.6-13.7V DC (Pin1 1 (+)) CNSK Connect to the indoor controller board (CNDK) Between 1 1 to 3 3 220-240V AC...
Page 25
9-6-2. Indoor controller board PEAD-RP60GA PEAD-RP71GA PEAD-RP100GA CN2D LED1 Connector to the indoor LED2 LED3 Power supply Power supply power board (CN2S) Transmission (I.B) (12.5~13.7V DC) (R.B) (Indoor/outdoor) CN3C – Transmission (Indoor/outdoor) CN22 (0~24V DC) Remote controller connecting wire Non polarity –...
Page 26
Remarks Functions For service board Model settings Service board MODELS 1 2 3 4 5 PEAD-RP60GA Capacity 1 2 3 4 5 PEAD-RP71GA settings 1 2 3 4 5 PEAD-RP100GA <Settings at time of factory shipment> Wireless remote controller: 0...
DISASSEMBLY INSTRUCTIONS Figure1. isconnect the fan motor connecter Control box rain pan catches (Hidden) Heat exchanger Bottom plate Filter assembly rain pan catches (Hidden) Bottom plate rain pan 1. Removing the fan motor 5. Remove the sirocco fan setting screw and the 1.
Page 28
Figure2. an base Sirocco fan Motor Housing Motor base assembly Bush Bush Piece Sirocco fan Piece Housing assembly...
OPTIONAL PARTS 1. REMOTE SENSOR Part No. PAC-SE41TS-E Applied model PEAD-RP60,71,100GA 2. REMOTE OPERATION ADAPTER Part No. PAC-SF40RM-E Applied model PEAD-RP60,71,100GA 3. REMOTE ON/OFF ADAPTER Part No. PAC-SE55RA-E Applied model PEAD-RP60,71,100GA 4. INSULATION KIT Part No. PAC-SK010DK Applied model PEAD-RP60,71,100GA...