Item
Operation flow and applicable data,etc
([
] button on the remote controller is
17. POWER
pressed)
Selection
Mode
− Power Selection 75% is 75% of maximum
current.
− Power Selection 50% is 50% of rate maximum
current.
POWER-SELECTION AND SILENT OPERATION
18. Silent
Silent
Operation
Silent 1:
Cooling/heating capacity is limited maximum for
70% of rated. Only compressor speed is limited.
Silent 2:
CDU sound level is limited for lowest CDU sound
level. Compressor and CDU fan speed are limited.
Silent Operation description
Model
RAS-25J2AVSG-ND1
RAS-35J2AVSG-ND1
POWER-SELECTION AND SILENT OPERATION
[100%]
[75%]
SILENT#2
SILENT#1
button on remote controller is pressed.
Silent
Compressor
Operation
frequncy
(rps)
24
Silent1
17
Silent2
28
Silent1
20
Silent2
[100%]
[75%]
SILENT#2
SILENT#1
1. Purpose
The function is used when its circuit
breaker is shared with other electrical
appliances. It limits the maximum
current/ power consumption to 100%,
75% or 50%.
The lower the percentage, the higher
the saving and also the longer the
compressor lifetime.
2. Description
When the level is selected, Power-SEL
level flashes on LCD display for 3
[50%]
seconds. In case of 75% and 50%
level, number "75" or "50" also flashes
for 2 seconds.
Note : Due to the reason that POWER
SELECT FUNCTION limits the
maximum current, inadequate
capacity may occur.
This function is used when the user need
to keep silent at outdoor side. It is limit
maximum compressor speed and CDU
fan speed. Sound level can be
implemented by 2 silent level.
Sound level:
Rated level > Silent 1 > Silent 2
Note:
Due to Silent operation reason,
In adequate cooling/heating capacity may
occur.
Cooling
Heating
CDU
Compressor
Fan Speed
frequncy
(rpm)
(rps)
Max 800
28
600
19
Max 860
32
600
24
[50%]
- 44 -
Description
CDU
Fan Speed
(rpm)
Max 860
600
Max 860
600