Cooling/Heating Operation; Auto Operation; Dry Operation - Toshiba RAS-25G3KVSG-ND Service Manual

Hide thumbs Also See for RAS-25G3KVSG-ND:
Table of Contents

Advertisement

Item
Operation flow and applicable data, etc.
1. Basic

2. Cooling/Heating operation

operation
The operations are performed in the following parts by controls according to cooling/heating conditions.
1) Receiving the operation ON signal of the remote controller, the cooling or heating operation signal
starts being transferred form the indoor controller to the outdoor unit.
2) At the indoor unit side, the indoor fan is operated according to the contents of "2. Indoor fan
motor control" and the louver according to the contents of "8. Louver control", respectively.
3) The outdoor unit controls the outdoor fan motor, compressor, pulse Modulating valve and
4-way valve according to the operation signal sent from the indoor unit.
Operation ON
Indoor unit control
Sending of operation command signal
Outdoor unit control

3. AUTO operation

Selection of operation mode
As shown in the following figure, the operation starts by
selecting automatically the status of room temperature
(Ta) when starting AUTO operation.
*1. When reselecting the operation mode, the fan
speed is controlled by the previous operation mode.
Ta
Ts + 1
Ts – 1

4. DRY operation

DRY operation is performed according to the difference
between room temperature and the setup temperature
as shown below.
In DRY operation, fan speed is controlled in order to
prevent lowering of the room temperature and to avoid
air flow from blowing directly to persons.
[ °C ]
Ta
+ 1.0
+ 0.5
Tsc
Setup of remote controller
Indoor fan motor control / Louver control / Operation Hz
Control (Requierment)
Compressor revolution control / Outdoor fan motor control /
Operation Hz control (Include limit control)
4-way valve control
Pulse Modulating valve control
Cooling operation
Monitoring (Fan)
Heating operation
L– (W5)
(W5+W3) / 2
SUL (W3)
Fan speed
- 28 -
Description
[
In cooling operation:
OFF
In heating operation:
ON
1) Detects the room temperature (Ta) when
the operation started.
2) Selects an operation mode from Ta in
the left figure.
3) Fan operation continues until an
operation mode is selected.
4) When AUTO operation has started
within 2 hours after heating operation
stopped and if the room temperature is
20°C or more, the fan operation is
performed with "Super Ultra LOW" mode
for 3 minutes.
Then, select an operation mode.
5) If the status of compressor-OFF
continues for 15 minutes the room
temperature after selecting an operation
mode (COOL/HEAT), reselect an
operation mode.
1) Detects the room temperature (Ta) when
the DRY operation started.
2) Starts operation under conditions in the
left figure according to the temperature
difference between the room
temperature and the setup temperature
(Tsc). Setup temperature (Tsc)
= Set temperature on remote controller
(Ts) + (0.0 to 1.0)
3) When the room temperature is lower
1°C or less than the setup temperature,
turn off the compressor.
]