FILE NO. SVM-19004 1. SAFETY PRECAUTIONS Read the precautions in this manual This appliance is fi lled with R32. carefully before operating the unit. (Flammable Material) Information included in the Operation Service personnel should be handing this equipment Manual and/or Installation Manual. with reference to the Installation Manual.
Page 4
FILE NO. SVM-19004 DANGER • ASK AN AUTHORIZED DEALER OR QUALIFIED INSTALLATION PROFESSIONAL TO IN- STALL/MAINTAIN THE AIR CONDITIONER. INAPPROPRIATE SERVICING MAY RESULT IN WATER LEAKAGE, ELECTRIC SHOCK OR FIRE. • TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF.
Page 5
FILE NO. SVM-19004 Do not pierce or burn as the appliance is pressurized. Do not expose the appliance to heat, fl ame, sparks, or • other sources or ignition. Else, it may explode and cause injury or death. • For R32 model, use pipes, fl are nut and tools which is specifi ed for R32 refrigerant. Using of existing (R22) piping, fl...
FILE NO. SVM-19004 3. REFRIGERANT R32 3. If a refrigeration gas leakage occurs during This air conditioner adopts the new refrigerant HFC (R32) which does not damage the ozone layer. installation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire, a The next section describes the precautions for air conditioner using the new refrigerant.
Page 11
FILE NO. SVM-19004 Table 3-2-1 Thicknesses of annealed copper pipes Thickness (mm) Nominal diameter Outer diameter (mm) R32(R410A) 6.35 0.80 0.80 9.52 0.80 0.80 12.70 0.80 0.80 15.88 1.00 1.00 2. Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm.
Page 12
FILE NO. SVM-19004 d) Flare Processing Make certain that a clamp bar and copper pipe have been cleaned. ØD By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R32 or conven- tional flare tool. Flare processing dimensions differ according to the type of flare tool.
Page 14
FILE NO. SVM-19004 3-3. Tools 3-3-1. Required Tools The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R32 is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
Page 15
FILE NO. SVM-19004 3-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Page 16
FILE NO. SVM-19004 1. Be sure to make setting so that liquid can be charged. 2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
Page 17
FILE NO. SVM-19004 2. Characteristics required for flux 3-5-3. Brazing • Activated temperature of flux coincides with the As brazing work requires sophisticated techniques, brazing temperature. experiences based upon a theoretical knowledge, it must be performed by a person qualified. •...
FILE NO. SVM-19004 4. CONSTRUCTION VIEWS 4-1. Indoor Unit Air Inlet Air Filter Front Panel Grille Inlet Back Body Hert Exchanger Air Outlet Knock Out System Knock Out System 66.5 55 66.5 Installation plate hanger 17.5 Wireless remote controller 64.5 Remote controller holder Drain hose (0.4m) Installation plate hanger...
FILE NO. SVM-19004 6. SPECIFICATIONS OF ELECTRICAL PARTS 6-1. Indoor Unit Parts name Type Specificat RAS-05,07,10,13 Fan Motor (for indoor) SJM-240-25 AC 220~240V, 25W SJM-240-35 AC 220~240V, 35W RAS-16 RAS-18 ICF-340-30-6 DC 340V, 42W Room temp. sensor (TA-sensor) 10kΩ at 25°C Heat exchanger temp.
Page 29
FILE NO. SVM-19004 7-2. Operation Data <Cooling> Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor Connecting condition(°C) pipe temp. RAS- pressure fan mode fan mode revolution piping Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps) 05J2KVG-EE High 27/19 35/- 1.2 to 1.3 43 to 44...
FILE NO. SVM-19004 8. CONTROL BLOCK DIAGRAM 8-1. Indoor Unit Indoor Unit Control Panel M.C.U Functions Operation Heat Exchanger Sensor Display • Louver Control Timer Temperature Sensor • 3-minute Delay at Restart for Compressor Display • Motor Revolution Control Hi-Power Infrared Rays Signal Receiver Display •...
FILE NO. SVM-19004 9. OPERATION DESCRIPTION 9-1. Outline of Air Conditioner Control • Detection of inverter input current and current release operation This air conditioner is a capacity-variable type air conditioner. Its system can control the speed of • Over-current detection and prevention operation to IGBT module (Compressor stop function) compressor motor according to load.
Page 34
FILE NO. SVM-19004 9-2. Operation Description 1. Basic operation ......................35 1. Operation control ....................35 2. Cooling/Heating operation ..................36 3. AUTO operation ..................... 36 4. DRY operation ......................36 2. Indoor fan motor control ..................... 37 3. Outdoor fan motor control ................... 40 4.
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 1. Basic 1. Operation control operation Receiving the user’s operation condition setup, the operation statuses of indoor/outdoor units are controlled. 1) The operation conditions are selected by the remote controller as shown in the below. 2) A signal is sent by ON button of the remote controller.
FILE NO. SVM-19004 Operation flow and applicable data, etc. Description Item 1. Basic 2. Cooling/Heating operation operation The operations are performed in the following parts by controls according to cooling/heating conditions. 1) Receiving the operation ON signal of the remote controller, the cooling or heating operation signal starts being transferred form the indoor controller to the outdoor unit.
+1.0 *5 : Fan speed = (M + –L) x 1/4 + L +0.5 (Linear approximation L(W7) from M+ and L) (Table 1) Indoor fan air flow rate Fan speed level RAS-05J2KVG-EE RAS-07J2KVG-EE Mode Cooling Heating Cooling Heating Cool Heat...
Page 38
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 2. Indoor fan motor control Fan speed level Mode RAS-10J2KVG-EE RAS-13J2KVG-EE Cooling Heating Cooling Heating Cool Heat Fan speed Air flow rate Fan speed Air flow rate Fan speed Air flow rate Fan speed Air flow rate...
Page 39
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 2. Indoor fan <In heating operation> 1) When setting the fan speed to L, motor control L+, M, M+ or H on the remote controller, the operation is per- formed with the constant speed HEAT ON shown in Fig.
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 3. Outdoor fan The blowing air volume at the outdoor unit side is controlled. 1) The operation command sent motor control from the remote controller is Receiving the operation command from the controller of processed by the indoor unit indoor unit, the controller of outdoor unit controls fan speed.
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 4. Capacity The cooling or heating capacity depending on the load is 1) The difference between set control adjusted. temperature on remote controller (Ts) and room temperature (Ta) According to difference between the setup value of tempera- is calculated.
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 6. Release protective <In cooling/dry operation> 1) When temperature of the indoor control by tempera- heat exchanger drops below 5°C, (Prevent-freezing control for indoor heat exchanger) ture of indoor heat the compressor speed is In cooling/dry operation, the sensor of indoor heat exchanger...
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 7. Defrost control (This function removes frost adhered to the outdoor The necessity of defrost operation is (Only in heating heat exchanger.) detected by the outdoor heat exchanger operation) temperature.
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 8. Louver control This function controls the air direction of the indoor unit. 1) Louver • The position is automatically controlled according to the operation position mode (COOL/HEAT). • The set louver position is stored in memory by the microcomputer, and the louver returns to the stored position when the next operation is performed.
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 9. ECO When pressing [ECO] button on the remote controller, a <Cooling operation> operation Economic operation is performed. 1) The control target temperature <Cooling operation> increase 0.5ºC per hour up to 2ºC This function operates the air conditioner with the difference starting from the set temperature between the set and the room temperature as shown in the...
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 10. Temporary Pressing [RESET] button starts the temporary opera- 1) When pressing [RESET] button, the operation tion of [AUTO] operation. When keeping [RESET] temporary [AUTO] operation starts. button pressed for 10 seconds or more, the temporary 2) When keeping [RESET] button pressed [COOL] operation is performed.
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 13. Pulse This function controls throttle amount of the 1) When starting the operation, move the Modulating refrigerant in the refrigerating cycle. valve once until it fits to the stopper. valve (P.M.V.) (Initialize) According to operating status of the air conditioner,...
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 14. Self-Cleaning 1. Purpose function The Self-Cleaning operation is to minimize the growth of mold, bacteria etc. by running the fan and drying so as to keep the inside of the air conditioner clean. Unit now performing cooling or dry operation Self-Cleaning operation When the cooling or dry operation shuts...
Page 49
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 14. Self-Cleaning function 13-1-1. Self-Cleaning diagram Operation display FCU fan rpm is depend on presetting. (500RPM) FCU louver OPEN OPEN (12.7º) CLOSE ON or OFF ON or OFF Timer display depend on presetting of timer function.
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 1. Purpose 15. Remote-A or B Setting the remote controller selection This operation is to operate only one To separate using of remote control for each indoor indoor unit using one remote controller. unit in case of 2 air conditioner are installed nearly.
FILE NO. SVM-19004 Item Operation flow and applicable data, etc. Description 17. Display lamp To decrease the display lamp brightness or turn it off. brightness 1. Press and hold for 3 seconds until brightness level ( adjustment ) is shown on remote control LCD then release the button. Rise 2.
Sound level: Rated level > Silent 1 Note: Due to Silent operation reason, In adequate cooling/heating capacity may occur. Silent Operation description Model Cooling Heating Silent operate RAS-05J2KVG-EE Silent1 25.8 normal 36.0 normal RAS-07J2KVG-EE Silent1 37.8 normal 48.0 normal...
FILE NO. SVM-19004 9-3. Auto Restart Function This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of a power supply being accidentally shut down. The operation will resume without warning three minutes after power is restored.
FILE NO. SVM-19004 9-3-2. How to Cancel the Auto Restart Function To cancel auto restart function, proceed as follows : Repeat the setting procedure : the unit receives the signal and beeps three times. The unit will be required to be turned on with the remote controller after the main power supply is turned off. •...
FILE NO. SVM-19004 9-4. Remote Controller and Its Fuctions 9-4-1. Parts Name of Remoe Controller Infrared signal emitter Start/Stop button ( Mode select button (MODE) Hi POWER MODE SILENT Temperature button (TEMP) Fan speed button (FAN) Swing louver button (SWING) Set louver button (FIX) Off timer button (OFF) High power button (Hi-POWER)
Page 56
FILE NO. SVM-19004 5. ECO / SILENT OPERATION ECO OPERATION To automatically control room temperature to save energy (Except in DRY and FAN ONLY mode) Note: Cooling operation; the set temperature will increase automatically 1 degree/hour for 2 hours (maximum 2 degree increase). For Heating operation the set temperature will decrease. SILENT OPERATION To reduce outdoor sound level during operation (Except in DRY and FAN ONLY mode) Note: Though operating silently, the Heating or Cooling capacity is still prioritized to ensure...
FILE NO. SVM-19004 9. MANUAL DEFORST OPERATION To defrosting the heat exchanger of the outdoor unit during Heating operation. Press and hold : for 5 sec. then remote control display will show [ ] as picture 1 for 2 sec. Hi POWER MODE SILENT...
FILE NO. SVM-19004 10. INSTALLATION PROCEDURE 10-1. Installation Diagram of Indoor and Outdoor Units For the rear left, bottom left and left piping Wall Hook Installation plate Cut out a piece of SPACER from indoor unit packaging box, roll it and insert between the indoor unit and wall to tilt the indoor unit for better operation.
Page 59
FILE NO. SVM-19004 10-2. Installation 10-2-1. Optional installation parts Part Parts name Q’ty code Refrigerant piping Liquid side : Ø6.35 mm Gas side : Ø9.52 mm (RAS-05,07,10,13J2KVG-EE) : each Ø12.70 mm (RAS-16,18J2KVG-EE) Pipe insulating material (polyethylene foam, 6 mm thick) Putty, PVC tapes each <Fixing bolt arrangement of outdoor unit>...
Page 60
FILE NO. SVM-19004 10-2-2. Accessory and installation parts Indoor Unit Part name Part name Installation plate × 1 Wireless remote control × 1 Battery × 2 Remote control holder × 1 Mounting screw × 6 Flat head wood screw × 2 Owner’s Manual ×...
Page 61
FILE NO. SVM-19004 10-2-3. Installation/Servicing Tools Changes in the product and components In the case of an air conditioner using R32, in order to prevent any other refrigerant from being charged accidentally, the service port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch) •...
Page 62
FILE NO. SVM-19004 10-3. Indoor Unit 10-3-2. Cutting a hole and mounting installation 10-3-1. Installation place <Cutting a hole> • A place which provides the spaces around the When installing the refrigerant pipes from the rear. indoor unit as shown in the diagram •...
Page 63
FILE NO. SVM-19004 <When the installation plate is directly mounted on 10-3-3. Piping and drain hose installation the wall> <Piping and Drain Hose Forming> 1. Securely fit the installation plate onto the wall by * Since dewing results in a machine trouble, make screwing it in the upper and lower parts to hook up sure to insulate both the connecting pipes.
Page 64
FILE NO. SVM-19004 <How to fix the Drain Cap> <Left-hand connection with piping> 1) Insert hexagon wrench (4 mm) in a center head. Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe is laid exceeding 43 mm above the wall surface, the indoor unit may unstably be set on the wall.
Page 65
FILE NO. SVM-19004 10-3-4. Indoor unit fixing 10-3-5. Drainage 1. Pass the pipe through the hole in the wall, and hook 1. Run the drain hose sloped downwards. the indoor unit on the installation plate at the upper hooks. NOTE 2.
Page 66
FILE NO. SVM-19004 10-4. Outdoor Unit 10-4-1. Installation place Snow protection plate • A place which provides the spaces around the Front Install at least 50 cm outdoor unit as shown in the diagram Snow protection hood above the snow •...
Page 67
FILE NO. SVM-19004 10-4-3. Draining the Water 2. Install the drain nipple and a commercially available drain hose (with 16 mm inside • Holes are provided on the base plate of the diameter), and drain off the water. outdoor unit to ensure that the defrost water (For the position where the drain nipple is produced during heating operations is drained off installed, refer to the installation diagram of the...
Page 68
FILE NO. SVM-19004 10-4-4. Refrigerant piping connection <Tightening connection> <Flaring> Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then 1. Cut the pipe with a pipe cutter. tighten the nut with a spanner and torque wrench as shown in the figure.
Page 69
FILE NO. SVM-19004 CAUTION AIR PURGE acuate the air in the connecting pipes and in the • KEEP IMPORTANT 6 POINTS FOR PIPING WORK indoor unit using a v acuum pump. Do not use the 1) Take away dust and moisture (inside of the refriger ant in the outdoor unit.
Page 70
FILE NO. SVM-19004 10-5. Electrical works Model RAS-05J2KVG-EE RAS-07J2KVG-EE RAS-10J2KVG-EE RAS-13J2KVG-EE RAS-16J2KVG-EE RAS-18J2KVG-EE Power source 50Hz, 220 – 240 V Single phase Maximum running current 5.0A 5.4A 7.2A 7.4A 9.0A 9.25A Circuit breaker rating 6.5A 7.0A 9.0A 9.5A 11.5A H07RN-F or...
Page 71
FILE NO. SVM-19004 10-5-2. Power Supply and Connecting Cable Connection Power Supply Input at Indoor Unit Terminal Block (Recommend) Indoor unit Outdoor unit Stripping length of the power Power supply cable Power supply cable Terminal block supply cable connect to Terminal block (L N 1 2 3) Earth line 50 mm...
Page 72
FILE NO. SVM-19004 Power supply input Wiring Diagram Power supply input at Indoor unit Terminal Block (Recommend) Indoor L N 1 2 3 Terminal Block Power supply input CHASSIS INDOOR UNIT OUTDOOR UNIT Outdoor 1 2 3 Terminal Block CHASSIS EARTH Power supply input at Outdoor unit Terminal Block (Optional) Indoor L N 1 2 3 Terminal Block CHASSIS...
Page 73
FILE NO. SVM-19004 10-6. Others NOTE : 1. Repeat previous step to reset Remote 10-6-1 . Gas leak test Control to be A. 2. Remote Control A has not "A" display. 3. Default setting of Remote Control from Check places for indoor unit (Flarenut factory is A.
FILE NO. SVM-19004 11. HOW TO DIAGNOSE THE TROUBLE The pulse motor circuits are mounted to both indoor and outdoor units. Therefore, diagnose troubles according to the trouble diagnosis procedure as described below. (Refer to the check points in servicing written on the wiring diagrams attached to the indoor/outdoor units.) Table 11-1 Troubleshooting Procedure...
Page 75
FILE NO. SVM-19004 RAS-16,18J2AVG-EE Fig. 11-2 CAUTION A high voltage (equivalent to the supply voltage) is also energized to ground through the sensors, PMV and other low-voltage circuits. The sensor leads and other wires are covered with insulated tubes for protection. Nevertheless, care must be taken to ensure that these wires are not pinched.
Page 76
FILE NO. SVM-19004 K Precautions when inspecting the control section of the outdoor unit NOTE : A large-capacity electrolytic capacitor is used in the outdoor unit controller (inverter). Therefore, if the power supply is turned off, charge (charging voltage DC280 to 380V) remains and discharging takes a lot of time. After turning off the power source, if touching the charging section before discharging, an electrical shock may be caused.
Page 77
FILE NO. SVM-19004 11-1. First Confirmation 11-1-1. Confirmation of Power Supply Confirm that the power breaker operates (ON) normally. 11-1-2. Confirmation of Power Voltage Confirm that power voltage is AC 220–230–240 ± 10%. If power voltage is not in this range, the unit may not operate normally. 11-1-3.
Page 78
FILE NO. SVM-19004 11-2. Primary Judgment To diagnose the troubles, use the following methods. 1) Judgment by flashing LED of indoor unit 2) Self-diagnosis by service check remote controller 3) Judgment of trouble by every symptom Firstly use the method 1) for diagnosis. Then, use the method 2) or 3) to diagnose the details of troubles. 11-3.
Page 79
FILE NO. SVM-19004 11-4. Self-Diagnosis by Remote Controller (Check Code) 1. If the lamps are indicated as shown B to E in Table 11-3-1, execute the self-diagnosis by the remote controller. 2. When the remote controller is set to the service mode, the indoor controller diagnoses the operation condi- tion and indicates the information of the self-diagnosis on the display of the remote controller with the check codes.
Page 80
FILE NO. SVM-19004 11-4-2 Caution at Servicing 1. After using the service mode of remote controller finished, press the [ ] button to reset the remote controller to normal function. 2. After finished the diagnosis by the remote controller, turn OFF power supply and turn its ON again to reset the air conditioner to normal operation.
Page 81
FILE NO. SVM-19004 Block distinction Operation of diagnosis function Action and Judgment Check Check Display flashing Block Cause of operation conditioner code code error status Serial signal 1) Defective wiring of the Indoor unit Flashes when 1) to 3) The outdoor unit never and connecting connecting cable or operates...
Page 82
FILE NO. SVM-19004 Block distinction Operation of diagnosis function Action and Judgment Check Check Display flashing Block Cause of operation conditioner code code error status Outdoor P.C. Current on inverter circuit All OFF Flashes after 1. Remove connecting lead wire of the board is over limit in short time.
Page 83
FILE NO. SVM-19004 Block distinction Operation of diagnosis function Action and Judgment Check Check Display flashing Block Cause of operation conditioner code code error status Compressor drive output error. All OFF Flashes after 1. Check installation conditions such as Outdoor P.C. (Relation of voltage, current error is detected packed valve opening, refrigerant...
Page 84
FILE NO. SVM-19004 Block distinction Operation of diagnosis function Action and Judgment Check Check Display Block Cause of operation conditioner code code flashing error status The others Compressor does not rotate. All OFF Flashes after 1. Remove connecting lead wire of the (including Because of missed wiring, error is detected...
Page 85
FILE NO. SVM-19004 Block distinction Operation of diagnosis function Action and Judgment Check Check Display Block Cause of operation conditioner code code flashing error status The others Return signal of the outdoor Indoor unit Flashes when 1. . Check power supply (Rate +10%) (including operates error is detected...
Page 86
FILE NO. SVM-19004 11-5. Judgment of Trouble by Every Symptom 11-5-1. Indoor Unit (Including Remote Controller) (1) Power is not turned on (Does not operate entirely) <Primary check> 1. Is the supply voltage normal? 2. Is the normal voltage provided to the outdoor unit? 3.
Page 87
FILE NO. SVM-19004 (2) Power is not turned on though Indoor P.C. board is replaced <Confirmation procedure> Turn on power supply. Return the wiring of the power relay is returned to Is it wired as shown in Figure below? Does operation lamp flash? the normal procedure.
Page 88
FILE NO. SVM-19004 11-5. Judgment of Trouble by Every Symptom 11-5-1. Indoor Unit (Including Remote Controller) (1) Power is not turned on (Does not operate entirely) <Primary check> 1. Is the supply voltage normal? 2. Is the normal voltage provided to the outdoor unit? 3.
Page 89
FILE NO. SVM-19004 (2) Power is not turned on though Indoor P.C. board is replaced <Confirmation procedure> Turn on power supply. Return the wiring of the power relay is returned to Is it wired as shown in Figure below? Does operation lamp flash? the normal procedure.
Page 90
FILE NO. SVM-19004 (3) Only the indoor motor fan does not operate <Primary check> (For 05, 07, 10, 13, 16K) 1. Is it possible to detect the power supply voltage (AC220–240V) between on the terminal block? 2. Does the indoor fan motor operate in cooling operation? (In heating operation, the indoor fan motor does not operate for approximately 10 minutes after it is turned on, to prevent a cold air from blowing in.) Shut off the...
Page 91
FILE NO. SVM-19004 (3) Only the indoor motor fan does not operate <Primary check> (For 18K) 1. Is it possible to detect the power supply voltage (AC220–240V) between on the terminal block? 2. Does the indoor fan motor operate in cooling operation? (In heating operation, the indoor fan motor does not operate for approximately 10 minutes after it is turned on, to prevent a cold air from blowing in.) Turn off power...
Page 92
FILE NO. SVM-19004 Is it possible to Does check display Replace change airflow level on remote show high? remote to “HIGH”? Change the new PC Replace board. Does fan speed motor change? Fan motor operates normally. Is it possible to Does check cross-flow Replace bearing rotate cross-flow fan by...
Page 93
FILE NO. SVM-19004 (For AC fan motor) (For 05, 07, 10, 13, 16K) <Inspection procedure> 1. Remove the front panel. (Remove 2 screws.) 2. Remove the cover of the fan motor lead wires. 3. Check AC voltage with CN10 connector while the fan motor is rotating. NOTE : •...
Page 94
FILE NO. SVM-19004 (4) Indoor fan motor automatically starts to rotate by turning on power supply [For DC fan motor] (For 18K) <Cause> The IC is built in the indoor fan motor. Therefore the P.C. board is also mounted to inside of the motor. If the P.C.
Page 95
FILE NO. SVM-19004 (4) Troubleshooting for remote controller <Primary check> Check that A or B selected on the main unit is matched with A or B selected on the remote controller. There is no beep from the indoor unit Push the [ ] button.
Page 96
FILE NO. SVM-19004 11-5-2. Wiring Failure (Interconnecting and Serial Signal Wire) (1) Outdoor unit does not operate 1) Is the voltage between of the indoor terminal block varied? Confirm that transmission from indoor unit to outdoor unit is correctly performed based upon the follow- ing diagram.
Page 97
FILE NO. SVM-19004 11-6. How to Check Simple the Main Parts <Check procedure> Gas leakage, Discharge temp. error, disconnection of TS/TC gas leakage sensors (Check code 02, 1C) (Check code 03, 1E) Valve drive check Is coil of the pulse motor valve Set it correctly.
Page 98
FILE NO. SVM-19004 11-7. How to Diagnose Trouble in Outdoor Unit 11-7-1. Summarized Inner Diagnosis of Inverter Assembly (RAS-05, 07, 10, 13) Table 11-7-1 Diagnosis/Process flowchart Item Contents Summary Preparation Turn “OFF” the power supply breaker, and remove 3P Remove connector connector which connects of compressor.
Page 99
FILE NO. SVM-19004 (RAS-16, 18) Diagnosis/Process flowchart Item Contents Summary Preparation Turn “OFF” the power supply breaker, and remove 3P Remove connector connector which connects of compressor. inverter and compressor. If fuse was blown, be sure to Check • Check whether 25A fuse check the electrolytic Check 25A fuse on the control board...
Page 100
FILE NO. SVM-19004 Diagnosis/Process flowchart Item Contents Summary Check Check winding resistance between phases of compres- sor, and resistance between outdoor frames by using a tester. • Is not grounded. → OK if 20MΩ or more Replace control board assembly. ...
Page 101
FILE NO. SVM-19004 (3) Check procedures (For 05,07,10,13K) Table 11-8-1 Procedure Check points Causes Turn off the power supply breaker Check whether or not the fuse (F01) Impulse voltage was applied or the and remove the P.C. board is blown. indoor fan motor short-circuited.
Page 102
FILE NO. SVM-19004 (3) Check procedures (For 18K) Table 11-8-1 Procedure Check points Causes Turn off the power supply breaker Check whether or not the fuse (F01) Impulse voltage was applied or the and remove the P.C. board or (F02) is blown. indoor fan motor short-circuited.
Page 105
FILE NO. SVM-19004 11-8-3. Indoor Unit (Other Parts) Part name Checking procedure Room temp. (TA) sensor Disconnect the connector and measure the resistance value with tester. Heat exchanger (TC,TCJ) (Normal temp.) sensor Temperature 10°C 20°C 25°C 30°C 40°C Sensor TA, TC, TCJ (kΩ) 20.7 12.6 10.0...
Page 106
FILE NO. SVM-19004 11-8-5. Checking Method for Each Part Part name Checking procedure Electrolytic capacitor 1. Turn OFF the power supply breaker. (For raising pressure, smoothing) 2. Discharge all three capacitors completely. 3. Check that safety valve at the bottom of capacitor is not broken. 4.
Page 107
FILE NO. SVM-19004 11-9. How to Simply Judge Whether Outdoor Fan Motor is Good or Bad 1. Symptom • Outdoor fan motor does not rotate. • Outdoor fan motor stops within several tens seconds though it started rotating. • Outdoor fan motor rotates or does not rotate according to the position where the fan stopped, etc. Remote controller check code “02 : Outdoor block, 1A : Outdoor fan drive system error”...
FILE NO. SVM-19004 12. HOW TO REPLACE THE MAIN PARTS WARNING • Since high voltages pass through the electrical parts, turn off the power without fail before proceeding with the repairs. Electric shocks may occur if the power plug is not disconnected. •...
Page 109
FILE NO. SVM-19004 Part name Procedures Remarks Front panel 1) Stop operation of the air conditioner and turn Front panel Air inlet grille off its main power supply. 2) Open two screw caps and securely remove screws (2 pcs.) at the front panel. Hooks of front panel Screw...
Page 110
FILE NO. SVM-19004 Part name Procedures Remarks Fan motor 1) Follow the procedure item 3 and 4 . Cross flow fan 2) Loosen the set screw of the cross flow fan. Cross flow fan Body back 3.5 mm Vertical louver Set screw Fan motor Hexagon screw driver...
Page 111
FILE NO. SVM-19004 Part name Procedures Remarks Drain pan 1) Follow the procedure item 3 . assembly 2) Remove screw holding the electric part cover. Connectors P.C.board Screw Electric part cover Louver motor connector 3) Disconnect the louver motor connector (5P) from P.C.
Page 112
FILE NO. SVM-19004 Part name Procedures Remarks Vertical louver 1) Follow the procedure item 3 and 7 . assembly 2) Remove 2 fixing screws from the base vertical Vertical louver louver then remove the vertical louver assembly from the body back. Screw Screw Cross flow fan...
Page 113
FILE NO. SVM-19004 Part name Procedures Remarks Heat exchanger 1) Follow the procedure in item 3 and 4 . (Evaporator) 2) Remove 2 fixing screws at the left side of the heat exchanger. Screws 3) Remove fixing screw at the upper right side of the heat exchanger.
Page 114
FILE NO. SVM-19004 12-2. Microcomputer Part name Procedure Remarks Common procedure 1) Turn the power supply off to stop the Replace terminal block, operation of air-conditioner. microcomputer ass’y and the P .C. board ass’y. 2) Remove the front panel. •...
Page 115
FILE NO. SVM-19004 12-3. Outdoor Unit (RAS-05, 07, 10, 13J2AVG-EE) Part name Procedures Remarks Common 1. Detachment procedure 1) Stop operation of the air conditioner, and turn off the main switch and breaker of the air conditioner. 2) Remove the valve cover. (ST2T∅4 x 10s 1 pc) •...
Page 116
FILE NO. SVM-19004 Part name Procedure Remarks Inverter module cover 1) Perform work of item 1 in Inverter assembly 2) Remove screw (ST2TØ4×10L 2 pcs.) of the upper part of the front cabinet. • Disconnect connectors all connector on P.C.
Page 117
FILE NO. SVM-19004 Part name Procedures Remarks „ Fan motor 1) Perform work of item 1 of 1 and 1 of 2. 2) Remove the flange nut fixing the fan motor Fan motor and the propeller fan. Propeller fan • Flange nut is loosened by turning clockwise.
Page 118
FILE NO. SVM-19004 Part name Procedures Remarks Fan guard 1. Detachment 1) Perform work of item 1 of 1 and 1 of 2. Requirement: Perform the work on a corrugated cardboard, cloth, etc. to prevent scratches to the product. 2) Remove the front cabinet, and place it down so that the fan guard side faces downwards.
Page 119
FILE NO. SVM-19004 Part name Procedure Remarks Control board 1. Disconnect the leads and connectors connected to assembly the other parts from the control board assembly. 1) Leads • 3 leads (black, white, orange) connected to terminal block. • Lead connected to compressor : Disconnect the connector (3P).
Page 120
FILE NO. SVM-19004 12-4. Outdoor unit (RAS-16, 18J2AVG-EE) Part name Procedures Remarks Common procedure 1. Detachment NOTE Upper cabinet Wear gloves for this job. Otherwise, you may injure your hands on the parts, etc. 1) Stop operation of the air conditioner, and turn off the main switch of the breaker for air conditioner.
Page 121
FILE NO. SVM-19004 Part name Procedures Remarks Inverter assembly 1) Perform work of item 1 in 1. Inverter cover 2) Remove screw (ST2TØ4 × 10L 2 pcs.) of the upper part of the front cabinet. P.C. board • If removing the inverter cover in this (Soldered surface) condition, P.C.
Page 122
FILE NO. SVM-19004 Remarks Part name Procedures Control board assembly 1. Disconnect the leads and connectors connected to the other parts from the control board assembly. 1) Leads • 3 leads (black, white, orange) connected to terminal block. • Lead connected to compressor : Disconnect the connector (3P).
Page 123
FILE NO. SVM-19004 Part name Procedures Remarks Side cabinet 1. Side cabinet (right) 1) Perform step 1 in 2 and all the steps in 3. 2) Remove the fixing screw (S 2TØ4 × 10L 4 pcs.) used for securing the side cabinet to the bottom plate and valve fixing panel 2.
Page 124
FILE NO. SVM-19004 Part name Procedures Remarks Compressor 1) Perform work of item 1 of 1 and 2, 3, 4, 5. 2) Extract refrigerant gas. 3) Remove the partition board. (ST2TØ4 × 10L 3 pcs.) 4) Remove the sound-insulation material. 5) Remove terminal cover of the compressor, and disconnect lead wire of the compressor from Compressor...
Page 125
FILE NO. SVM-19004 Part name Procedures Remarks 1. Detachment Electronic expansion valve coil 1) Perform step 1 in 1 , all the steps in 2 and 1 in 5 . 2) Turn the coil by 180 degrees then remove by pull it upward. Attachment 1) Insert the coil at position which perpendicular with pipe of PMV then turn...
Page 126
FILE NO. SVM-19004 Part name Remarks Procedures TS sensor (Suction pipe temperature sensor) " • Attachment Install the senser onto the straight pipe part of the suction pipe. Be careful for the lead direction of the sensor. TD sensor (Discharge pipe temperature sensor) •...
FILE NO. SVM-19004 13. EXPLODED VIEWS AND PARTS LIST 13-1. Indoor Unit ELECTRICAL PARTS ASSEMBLY Location Part Location Part Description Description 43T00685 FRONT PANEL ASSY 43T39367 MOTOR BAND FRONT 43T09563 GRILLE OF AIR INLET ASSY (FOR RAS-16J2KVG-EE) 43T80349 AIR FILTER 43T39369 MOTOR BAND FRONT 43T03398...
Page 128
43T6W519 PC BOARD (RAS-07J2KVG-EE) 43T6V673 TERMINAL(5P-TF) 43T6W522 PC BOARD (RAS-10J2KVG-EE) 43T6V674 TEMPERATURE SENSOR 43T6W525 PC BOARD (RAS-13J2KVG-EE) 43T62340 CORD-CLAMP 43T6W528 PC BOARD (RAS-16J2KVG-EE) 43T6W441 PC BOARD ASSY:WRS-LED 43T6W529 PC BOARD (RAS-18J2KVG-EE) 43T6W516 PC BOARD (RAS-05J2KVG-EE) 43T60480 HOUSING-WiFi - 128 -...
Page 129
FILE NO. SVM-19004 13-3. Outdoor Unit RAS-05, 07, 10J2AVG-EE Location Part Location Part Description Description 43T42335 BASE PLATE ASSEMBLY 43T46436 VALVE; PACKED 9.52 DIA 43T00733 UPPER CABINET ASSEMBLY 43T46469 BODY PMV 43T00682 FRONT CABINET ASSEMBLY 43T63360 COIL PMV 43T00448 FIXING PLATE VALVE 43T46470 4 WAY VALVE 43T39334...
Page 130
FILE NO. SVM-19004 13-4. Outdoor Unit RAS-13J2AVG-EE Location Part Location Part Description Description 43T42335 BASE PLATE ASSEMBLY 43T46436 VALVE; PACKED 9.52 DIA 43T00733 UPPER CABINET ASSEMBLY 43T46469 BODY PMV 43T00683 FRONT CABINET ASSEMBLY 43T63360 COIL PMV 43T00448 FIXING PLATE VALVE 43T46470 4 WAY VALVE 43T39334...
Page 131
FILE NO. SVM-19004 13-5. Outdoor Unit RAS-16J2AVG-EE 63,64,65 36,40 38,41 Location Part Location Part Description Description 43T42327 BASE PLATE ASSEMBLY 43T46461 VALVE; PACKED 12.7 DIA 43T00459 LEFT CABINET 43T46469 BODY PMV 43T00690 RIGHT CABINET ASSEMBLY 43T63360 COIL PMV 43T00452 UPPER CABINET 43T46470 4 WAY VALVE 43T00688...
Page 132
FILE NO. SVM-19004 13-6. Outdoor Unit RAS-18J2AVG-EE 37,41 63 HOLDER SENSOR (TE) 36,40 64 HOLDER SENSOR (TD) 65 HOLDER SENSOR (TS) Location Part Location Part Description Description 43T42327 BASE PLATE ASSEMBLY 43T46461 VALVE; PACKED 12.7 DIA 43T00459 LEFT CABINET 43T46469 BODY PMV 43T00690 RIGHT CABINET ASSEMBLY...
Page 133
FILE NO. SVM-19004 13-7. Outdoor Unit (Part-E) RAS-05, 07, 10, 13J2AVG-EE TE Sensor (Ø6) TO Sensor (Ø6) TS Sensor (Ø6) TD Sensor (Ø4) Location Part Location Part Description Description 43T67306 HEATSINK 43T60459 FUSE 43T6W531 PC BOARD (FOR RAS-05J2AVG-EE) 43T60465 TEMPERATURE SENSOR 43T6W532 PC BOARD (FOR RAS-07J2AVG-EE) 43T50353...
Page 134
FILE NO. SVM-19004 13-8. Outdoor Unit (Part-E) RAS-16, 18J2AVG-EE TE Sensor (Ø6) TO Sensor (Ø6) TS Sensor (Ø6) TD Sensor (Ø4) Location Part Location Part Description Description 43T62351 HEATSINK (RAS-16J2AVG-EE) 43T50336 TEMPERATURE SENSOR 43T67310 HEATSINK (RAS-18J2AVG-EE) (RAS-18J2AVG-EE) 43T6W511 PC BOARD (RAS-18J2AVG-EE) 43T50353 TEMPERATURE SENSOR 43T6W535...