hit counter script
Mitsubishi Electric PZ-62DR-E Instruction Book

Mitsubishi Electric PZ-62DR-E Instruction Book

Lossnay remote controller
Hide thumbs Also See for PZ-62DR-E:

Advertisement

Lossnay Remote Controller
MODEL
PZ-62DR-E
Instruction Book
Prior to use, thoroughly read the instructions in this manual to use the product correctly.
Retain for future reference.
Make sure to hand this manual to any future users.
To ensure safety and proper operation of the remote controller, the remote controller should only be
installed by qualified personnel.
2105875H16901

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric PZ-62DR-E

  • Page 1 2105875H16901 Lossnay Remote Controller MODEL PZ-62DR-E Instruction Book Prior to use, thoroughly read the instructions in this manual to use the product correctly. Retain for future reference. Make sure to hand this manual to any future users. To ensure safety and proper operation of the remote controller, the remote controller should only be...
  • Page 2 Product features Feature 1 Large, easy-to-see display Lossnay Full-dot LCD display with large characters for easy viewing Feature 2 Simple button arrangement Feature 3 Large, easy-to-press buttons Buttons are arranged according to usage to allow for intuitive navigation. Frequently used buttons are larger than other buttons to prevent unintended pressing of other buttons.
  • Page 3: Table Of Contents

    Contents Safety precautions ........4 Names and functions of controller components ..6 Controller interface ............6 Display ...............8 Read before operating the controller ..10 Menu structure............10 Icon explanations............. 11 Basic operations .......... 12 Power ON/OFF ............12 Power ON/OFF during Night-purge operation ..12 Fan speed..............13 Ventilation mode ............13 Navigating through the menu ......
  • Page 4: Safety Precautions

    Safety precautions • Thoroughly read the following safety precautions before using the unit. • Observe these precautions carefully to ensure safety. WARNING Indicates a risk of death or serious injury. CAUTION Indicates a risk of serious injury or structural damage. •...
  • Page 5 This controller is designed for exclusive use with off the detergent with a wet cloth, and wipe off water the Lossnay by Mitsubishi Electric. The use of this with a dry cloth. controller for other systems or for other purposes may cause malfunctions.
  • Page 6: Names And Functions Of Controller Components

    Names and functions of controller components Controller interface Function buttons Eng-6...
  • Page 7 The functions of the function buttons 1 ON/OFF button change depending on the screen. Press to turn ON/OFF the Lossnay unit. Refer to the button function guide that appears at the bottom of the LCD for the functions they serve on a given screen.
  • Page 8: Display

    Names and functions of controller components Display * All icons are displayed for explanation. Lossnay Outdoor 2°C Return 2 °C Auto Supply 15°C Mode Eng-8...
  • Page 9 1 Remote controller name Page 30 Lossnay is always displayed. Appears when the night-purge function is available. 2 Clock Page 18 (See the Installation Manual.) Current time appears here. Appears when performing operation to protect the equipment. 3 Fan speed Page 13 Fan speed setting appears here.
  • Page 10: Read Before Operating The Controller

    Read before operating the controller Menu structure Main display Main menu User options Press the button. Fan speed timer Page 22 Move the cursor to the Timer desired item with the On/Off timer ,and Page 24 buttons, and press the Auto-Off timer Page 26 button.
  • Page 11: Icon Explanations

    Icon explanations Controller operation The table below Timer summarizes the square Main icons used in this manual. The administrator password must be entered on the password input screen to change settings. There is no settings that can skip this process. Timer : Press to move the cursor left.
  • Page 12: Basic Operations

    Basic operations Power ON/OFF Button operation Press the button. The ON/OFF lamp will light up in green, and the operation will start. Press the button again. The ON/OFF lamp will go out, and the operation will stop. Power ON/OFF during Night-purge operation Button operation Press the button during the night-purge...
  • Page 13: Fan Speed

    Fan speed Button operation Press the button to go through the fan speeds Lossnay in the following order. Auto Mode Operation is not possible during external fan speed operation. A fan speed that is skipped because of a fan skip setting is not displayed (refer to page 41).
  • Page 14: Navigating Through The Menu

    Navigating through the menu Main menu list Reference Setting and display items Setting details page User options Fan speed timer Use to set the operation at pre-set fan speed and time period. After pre-set operation, the unit goes back to the fan speed that was set before the pre-set operation.
  • Page 15: Restrictions For The Sub Remote Controller

    Reference Setting and display items Setting details page Commissioning External control Set the “Auto” fan speed to operate according to the input input from the CO sensor. Service Input Use to register the maintenance information. — maintenance • Model names and serial numbers info.
  • Page 16: Navigating Through The Main Menu

    Navigating through the Main menu Button operation Accessing the Main menu Main Main menu Press the button. User options Commissioning Maintenance The Main menu will appear. Main display: Cursor Item selection Main Main menu Press to move the cursor down. User options Commissioning Press...
  • Page 17 Saving the settings Select the desired item, and press the Main Main menu User options button. Commissioning Maintenance The screen to set the selected item will appear. Main display: Cursor Exiting the Main menu screen Lossnay Press the button to exit the Main menu and return to the Main display.
  • Page 18: Initial Setting

    Initial setting Clock Button operation Select “Initial setting” from the Main menu (refer Commissioning menu 1/2 to page 16), and press the button. Initial setting Airflow Auto bypass External input Service Main menu: Clock setting is required before making the Cursor Page following settings.
  • Page 19: Contrast

    Contrast Button operation Select “Initial setting” from the Main menu > Commissioning menu 1/2 Commissioning, and press the button. Initial setting Airflow Auto bypass External input Service Main menu: Cursor Page Move the cursor to the “Contrast” with the Initial setting menu button, and press the button.
  • Page 20: Language Selection

    Language selection Button operation Select “Initial setting” from the Main menu > Commissioning menu 1/2 Commissioning, and press the button. Initial setting Airflow Auto bypass External input Service Main menu: Cursor Page Move the cursor to the “Language selection” with Initial setting menu button, and press the button.
  • Page 21 Move the cursor to the language you desire with Language selection through buttons, and press the English Français button to save the setting. Deutsch Español Italiano Português Svenska Р Select: Cursor Cursor Language selection English Français A screen will appear that indicates the setting Deutsch Español Italiano...
  • Page 22: User Options

    User options Fan speed timer Main The Lossnay unit can be operated at pre-set fan speed and time period. After pre-set operation, the unit goes back to the fan speed that was set before the pre-set operation. When on/off or fan speed button is pushed while fan speed timer is running, the Lossnay unit goes out from Fan speed timer.
  • Page 23 Lossnay will appear on the Main display when the Fan speed timer is enabled. After finishing the timer, the icon will disappear, and fan speed will change back into the previous status. Mode Eng-23...
  • Page 24: Timer

    Timer Main On/Off timer Button operation Select “Main menu> User options> Timer” from User options the Main menu (refer to page 16), and press the Fan speed timer Timer button. Weekly timer Night-purge setting Main menu: Cursor The On/Off timer will not work in the following cases: when On/Off timer is disabled, during an error, when the clock is not set, when the system is...
  • Page 25 Change the setting with the button. Timer On/Off timer: No (disable)/Yes (enable) On/Off timer No / • On: Operation start time • (settable in 5-minute increments) Repeat No / * Press and hold the button to rapidly advance Select: the numbers. Cursor Time Off: Operation stop time...
  • Page 26 Timer Main Auto-Off timer Button operation Bring up the Timer setting screen. Timer On/Off timer (Refer to page 24) Repeat Select “Auto-Off”, and press the button. Auto-Off Stop in --- min Setting display: Cursor The Auto-Off timer will not work in the following cases: when On/Off timer is disabled, during an error, when the clock is not set, when the system is...
  • Page 27 Press the button to save the settings. Auto-Off timer Auto-Off Stop in Select: Cursor Time A confirmation screen will appear. Auto-Off timer Auto-Off Stop in Navigating through the screens Changes saved • To go back to the Main menu ..button Main menu: •...
  • Page 28: Weekly Timer

    Weekly timer Main Button operation Select “Main menu> User options> Weekly timer” User options from the Main menu (refer to page 16), and press Fan speed timer Timer button. Weekly timer Night-purge setting Main menu: The Weekly timer will not work in the Cursor following cases: when the On/Off timer is enabled, when the...
  • Page 29 The weekly timer setting screen will appear and Weekly timer the current settings will be displayed. Mon Tue Wed Thu Fri Sat Sun Up to eight operation patterns can be set for each day. Move the cursor to the desired day of the week Input display: Select Page...
  • Page 30: Night Purge Setting

    During the summer season, this function draws cooler outside air into the room at night. Note • The setting items and contents are different by the connected Lossnay unit. • When using PZ-62DR-E and AE-200E together, set all conditions from AE-200E. Select “Night-purge setting” from the Main menu User options Fan speed timer >...
  • Page 31 Selecting the days to activate the Night-purge Night-purge setting function. Night-purge No / Mon Tue Wed Thu Fri Sat Sun On/Off Use the button to move the cursor to “Mon- Sun” and then use the button to select the day Select : (flashing display).
  • Page 32: Detailed Function Setting

    Detailed function setting Airflow Main Adjust the output of the fan speed. Note • Each fan speed can set from 25% to 100% of output by 5% pitches. • The supply fan speed and exhaust fan speed can be set independently. Button operation Accessing the «Airflow»...
  • Page 33 Fan speed selection Airflow Add. All Supply / Exhaust Press the button to move the cursor. 25 % / 25 % 5 % / Press the button to select a fan speed. 75 % / 75 % % / 1 Speed select: Cursor Output selection...
  • Page 34 Output settings for other fan speeds Airflow Add. All Supply / Exhaust Press the button to return to 2. 5 % / Select other fan speed at 2. 75 % / 75 % % / 1 Reperform 3-4 Confirm: Speed select: Cursor Adjust Press the...
  • Page 35: Auto Bypass

    Auto bypass Set the threshold of temperature of the switching map for heat exchange ventilation / bypass ventilation. Button operation Accessing the «Auto bypass» screen Commissioning menu Initial setting Airflow Auto bypass Select “Auto bypass” from the Main menu > External input Service Commissioning, and press the...
  • Page 36: External Input

    External input Main Lossnay can be operated at 16 steps fan speed according to CO sensor output. The function is available to set the upper/lower limit of CO concentration. * The function only can be set if the Lossnay is connected with CO sensor.
  • Page 37: Function Setting

    Function setting Function description Make the Lossnay unit’s function settings from the remote controller as necessary. Refer to the Lossnay unit Installation Manual for information about the factory settings of Lossnay • units, function setting numbers, and setting values. When changing the Lossnay unit’s function settings, record all the changes made to keep track of the •...
  • Page 38 The Function Setting screen will appear. Function setting Press the button to move the cursor to M-NET address Function No. one of the following: M-NET address, function Data setting number, or setting value. Then, press Function / Conf button to change the settings to the Select: desired settings.
  • Page 39: Initializing

    Initializing Function description You can initialize the remote controller to restore it to the factory default state. The following are initialized. Fan speed timer, Timer, Weekly timer, Operation locked, Main/Sub, Clock, Contrast, Display details, Model name input, Serial No. input, Dealer information input, Error history, Administrator password, Language selection.
  • Page 40 Select “OK” with the button. Initializing Factory reset? Reboot after initializing Cancel After initialization is executed, the remote Initializing controller reboots automatically. Under initializing Reboot after initializing “Language selection” screen will appear again. Language selection English Français Deutsch Español Italiano Português Svenska Русский...
  • Page 41: Restriction

    Restriction To enable the operation lock function, Operation lock and fan speed skip function and/or fan speed skip function set the item “Operation locked” to “Yes”. Button operation Select “Restriction” from the Main menu> Commissioning menu Commissioning (refer to page 16), and press the Restriction Error information button.
  • Page 42 The screen to make the settings for the operation Restriction lock function will appear. Operation locked No / On/Off Locked Move the cursor to the desired item with the Locked Mode Locked button out of the following items <page 1/2> Select: Cursor Cursor...
  • Page 43: Maintenance Interval

    Maintenance interval Set the maintenance interval of the filters and Lossnay PM12:3 Fri Lossnay core. After the fan operation time exceeds the product maintenance interval, the maintenance sign ( ) will be displayed on the «Main display» screen. Mode Button operation Accessing the «Maintenance interval»...
  • Page 44 Indication of Maintenance interval Maintenance interval Filter No / hour Press the button to move the cursor. Lossnay core No / hour Press the button to change the setting value. Select: Cursor Cursor Press the button to go to the next screen. [Filter], [Lossnay core]: Select [Yes/No] to show the maintenance sign on the «Main display»...
  • Page 45: Troubleshooting

    Troubleshooting Error information When an error occurs, the following screen will appear. Check the error status, stop the operation, and consult your dealer. Button operation Error code, error unit, M-NET address, unit Error information 51 1 Error code model name, and serial number will appear. LC ( Lossnay ) Error unit M-NET address 1...
  • Page 46 Press the button or the button to reset Error information 51 1 Error code the error that is occurring. LC ( Lossnay ) Error unit M-NET address 1 LGH-5 RVS-E Model name Errors cannot be reset while the ON/OFF 1234567 Serial No.
  • Page 47 Checking the error information Commissioning menu While no errors are occurring, page 2/2 of the Restriction error information (refer to page 43) can be Error information Error history viewed by selecting “Error information” from the Run time Maintenance interval Main menu > Commissioning. Main menu: Errors cannot be reset from this screen.
  • Page 48 Error history You can check the past error history. Error state cannot be reset from this screen. Button operation Press the button to change the page. Error history Error Unt# dd/mm/yy Up to 4 pages, 12 cases can be stored in the 3 / 4/ 21 12:34 error history.
  • Page 49 Run time You can check the powered time and fan operation time of the product. Button operation Accessing the «Run time» screen Commissioning menu Restriction Error information Press the button to move the cursor. Error history Run time Press the button to go to the next screen.
  • Page 50: Maintenance

    Maintenance Maintenance information will appear on the Main display when it is Lossnay time to clean the filter and/or Lossnay core etc. . Clean, or replace the filter and/or Lossnay core etc. when this sign appears. Auto Refer to the Lossnay unit Instruction Manual for details.
  • Page 51 Select “OK” with the button. Maintenance Filter Lossnay core Reset cleaning sign? Cancel A confirmation screen will appear. Maintenance Cleaning sign reset Navigating through the screens • To go back to the Main menu ..button Main menu: • To return to the previous screen ..button Lossnay When the...
  • Page 52 Cleaning the controller Note • Do not touch the controller with benzine, thinner, ethanol, hypochlorous acid, chemical cloth, etc. There is a risk of discoloration. • When removing dirt, soak a cloth in a neutral detergent diluted with water, squeeze it well, wipe it off, and wipe it off with a dry cloth.
  • Page 53: Specifications

    Specifications Controller specifications Specification Product size 120(W) x 120(H) x 19(D) mm (4 3/4 x 4 3/4 x 3/4 [in]) (not including the protruding part) Net weight 0.25 kg (9/16 lb.) Rated power supply voltage 12 VDC (supplied from Lossnay units) Power consumption 0.3 W Usage environment...

Table of Contents