E09-351 Digital Inverter Engineering 4series 8-10HP Data Book Outdoor Unit RAV-SM2244AT8(Z)(ZG)-E RAV-SM2804AT8(Z)(ZG)-E RAV-SM2244AT7(Z)(ZG) RAV-SM2804AT7(Z)(ZG)
Engineering Data 1-2. Outdoor Unit Model Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7 RAV-SM2804AT7 3 phase 380-415V 50Hz 3 phase 380V 60Hz Power supply (Power exclusive to outdoor is required.) (Power exclusive to outdoor is required.) Type Hermetic compressor Hermetic compressor Compressor Motor (kW) 3.75...
Engineering Data Construction views (External views) 2-1. Outdoor unit Drain hole Mounting bolt hole Drain hole Knockout (for drain) (Ø28 x 88 bearing hole) (Ø12 x 17 long hole) (Ø25 bearing hole) Air inlet B legs port Air inlet Knockout port (for drain) Mounting bolt hole...
Engineering Data Gravity position Digital Inverter Outdoor unit Model Name X(mm) Y(mm) Z(mm) Weight (kg) RAV-SM2244AT7 RAV-SM2244AT7Z RAV-SM2244AT7ZG RAV-SM2244AT8-E RAV-SM2244AT8Z-E RAV-SM2244AT8ZG-E RAV-SM2804AT7 RAV-SM2804AT7Z RAV-SM2804AT7ZG RAV-SM2804AT8-E RAV-SM2804AT8Z-E RAV-SM2804AT8ZG-E (Unit:mm)
Engineering Data Sound Characteristics (NC Curve) RAV-SM2244AT8-E, RAV-SM2244AT7 RAV-SM2804AT8-E, RAV-SM2804AT7 Sound Cooling Heating Sound Cooling Heating pressure level pressure level (dB(A)) (dB(A)) Cooling Cooling Heating Heating Approximate threshold of Approximate threshold of hearing for continuous noise hearing for continuous noise Octave band center frequency (Hz) Octave band center frequency (Hz)
Engineering Data Capacity Correction Connecting pipe length and lift difference between indoor units vs. capacity correction value Cooling –10 –20 –30 Pipe length (m) Heating –10 –20 –30 Pipe length (m)
Page 38
Engineering Data Refrigerant Pipe Length (Twin, Triple, Double Twin system) Simultaneous twin, triple Allowable pipe length (m) Height difference (m) Pipe diameter (mm) Total length Branch Branch Number of Indoor - outdoor H Main pipe Branch piping • piping piping Outdoor unit bent Indoor –...
Page 39
Engineering Data Piping connection with different diameter – Piping connection with different diameter is possible under the below restraint conditions. – Maximum pipe length is determined by the combination of liquid pipe diameter and gas pipe diameter. Liquid pipe Ø12.7 (standard) Normal piping size Gas pipe Ø22.2 (1-size smaller)
Engineering Data Line up Combination pattern Digital inverter 8/10HP 10HP RAV-SM2244AT8(Z,ZG)-E RAV-SM2804AT8(Z,ZG)-E RAV-SM2244AT7(Z,ZG) RAV-SM2804AT7(Z,ZG) Twin system series 4 RAV-SM1104UT-Ex2 RAV-SM1404UT-Ex2 series 3 4-way cassette series 2 Duct series 2 RAV-SM1102BT-Ex2 RAV-SM1402BT-Ex2 Ceiling series 2 RAV-SM1102CT-Ex2 RAV-SM1402CT-Ex2 Triple system series 4 RAV-SM804UT-Ex3 RAV-SM804UT-Ex3 series 3...
Page 41
Engineering Data Branch kit "1:2" Branch kit RBC-TWP101E "1:3" Branch kit RBC-TRP100E "1:4" Branch kit set RBC-DTWP101E Option parts of outdoor unit Optional connector cable TCB-KBOS1E...
Branching pipe for simultaneous operation system case. • In the concurrent twin system, when TOSHIBA has specified Pipe diameter and thickness (mm) that branching pipe is to be used, it can be reused. Reference outside...
Page 43
Engineering Data Are there scratches or dents on the existing pipes? Existing pipes: Cannot be used. • Use new pipes. Is it possible to operate the existing air conditioner? • After the existing air conditioner is operated in cooling mode for approx. 30 minutes or longer,* recover the refrigerant.
Page 44
Digital Inverter 4series 8-10HP Engineering Data Book Jul. 2009...