Toshiba RAV-SM1104UT-E Data Book

Toshiba RAV-SM1104UT-E Data Book

4 series, digital inverter 8-10hp
Hide thumbs Also See for RAV-SM1104UT-E:

Advertisement

Digital Inverter
4series 8-10HP
Outdoor Unit
RAV-SM2244AT8(Z)(ZG)-E
RAV-SM2804AT8(Z)(ZG)-E
RAV-SM2244AT7(Z)(ZG)
RAV-SM2804AT7(Z)(ZG)
Engineering
Data Book
E09-351

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAV-SM1104UT-E

  • Page 1 E09-351 Digital Inverter Engineering 4series 8-10HP Data Book Outdoor Unit RAV-SM2244AT8(Z)(ZG)-E RAV-SM2804AT8(Z)(ZG)-E RAV-SM2244AT7(Z)(ZG) RAV-SM2804AT7(Z)(ZG)
  • Page 2: Table Of Contents

    Engineering Data Contents Specifications <Twin type> ........... 2 <Triple type>...
  • Page 3: Specifications

    Engineering Data Specifications 1-1. Indoor Unit 1-1-1. Indoor unit (4-way Cassette Type) <Twin type> Indoor unit 1 RAV-SM1104UT-E RAV-SM1404UT-E RAV-SM1104UT-E RAV-SM1404UT-E Model Indoor unit 2 RAV-SM1104UT-E RAV-SM1404UT-E RAV-SM1104UT-E RAV-SM1404UT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7 RAV-SM2804AT7 Cooling capacity (min. - max.) (kW) 20.0 (9.8-22.4)
  • Page 4 Engineering Data 1-1-2. Indoor unit (Duct Type) <Twin type> Indoor unit 1 RAV-SM1102BT-E RAV-SM1402BT-E RAV-SM1102BT-E RAV-SM1402BT-E Model Indoor unit 2 RAV-SM1102BT-E RAV-SM1402BT-E RAV-SM1102BT-E RAV-SM1402BT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7 RAV-SM2804AT7 Cooling capacity (min. - max.) (kW) 20.0 (9.8-22.4) 23.0 (9.8-27.0) 20.0 (9.8-22.4) 23.0 (9.8-27.0) Heating capacity (min.
  • Page 5 Engineering Data 1-1-3. Indoor unit (Ceiling Type) <Twin type> Indoor unit 1 RAV-SM1102CT-E RAV-SM1402CT-E RAV-SM1102CT-E RAV-SM1402CT-E Model Indoor unit 2 RAV-SM1102CT-E RAV-SM1402CT-E RAV-SM1102CT-E RAV-SM1402CT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7 RAV-SM2804AT7 Cooling capacity (min. - max.) (kW) 20.0 (9.8-22.4) 23.0 (9.8-27.0) 20.0 (9.8-22.4) 23.0 (9.8-27.0) Heating capacity (min.
  • Page 6: Triple Type

    Engineering Data 1-1-4. Indoor unit (4-way Cassette Type) <Triple type> Indoor unit 1 RAV-SM804UT-E RAV-SM804UT-E RAV-SM804UT-E RAV-SM804UT-E Indoor unit 2 RAV-SM804UT-E RAV-SM804UT-E RAV-SM804UT-E RAV-SM804UT-E Model Indoor unit 3 RAV-SM804UT-E RAV-SM804UT-E RAV-SM804UT-E RAV-SM804UT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7 RAV-SM2804AT7 Cooling capacity (min. - max.) (kW) 20.0 (9.8-22.4) 23.0 (9.8-27.0)
  • Page 7 Engineering Data 1-1-5. Indoor unit (Duct Type) <Triple type> Indoor unit 1 RAV-SM802BT-E RAV-SM802BT-E RAV-SM802BT-E RAV-SM802BT-E Indoor unit 2 RAV-SM802BT-E RAV-SM802BT-E RAV-SM802BT-E RAV-SM802BT-E Model Indoor unit 3 RAV-SM802BT-E RAV-SM802BT-E RAV-SM802BT-E RAV-SM802BT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7 RAV-SM2804AT7 Cooling capacity (min. - max.) (kW) 20.0 (9.8-22.4) 23.0 (9.8-27.0)
  • Page 8 Engineering Data 1-1-6. Indoor unit (Ceiling Type) <Triple type> Indoor unit 1 RAV-SM802CT-E RAV-SM802CT-E RAV-SM802CT-E RAV-SM802CT-E Indoor unit 2 RAV-SM802CT-E RAV-SM802CT-E RAV-SM802CT-E RAV-SM802CT-E Model Indoor unit 3 RAV-SM802CT-E RAV-SM802CT-E RAV-SM802CT-E RAV-SM802CT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7 RAV-SM2804AT7 Cooling capacity (min. - max.) (kW) 20.0 (9.8-22.4) 23.0 (9.8-27.0)
  • Page 9 Engineering Data 1-1-7. Indoor unit (High wall Type) <Triple type> Indoor unit 1 RAV-SM802KRT-E RAV-SM802KRT-E RAV-SM802KRT-E RAV-SM802KRT-E Indoor unit 2 RAV-SM802KRT-E RAV-SM802KRT-E RAV-SM802KRT-E RAV-SM802KRT-E Model Indoor unit 3 RAV-SM802KRT-E RAV-SM802KRT-E RAV-SM802KRT-E RAV-SM802KRT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7 RAV-SM2804AT7 Cooling capacity (min. - max.) (kW) 20.0 (9.8-22.4) 23.0 (9.8-27.0)
  • Page 10: Double Twin Type

    Engineering Data 1-1-8. Indoor unit (4-way Cassette Type) <Double twin type> Indoor unit 1 RAV-SM564UT-E RAV-SM804UT-E RAV-SM564UT-E RAV-SM804UT-E Indoor unit 2 RAV-SM564UT-E RAV-SM804UT-E RAV-SM564UT-E RAV-SM804UT-E Model Indoor unit 3 RAV-SM564UT-E RAV-SM804UT-E RAV-SM564UT-E RAV-SM804UT-E Indoor unit 4 RAV-SM564UT-E RAV-SM804UT-E RAV-SM564UT-E RAV-SM804UT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7...
  • Page 11 Engineering Data 1-1-9. Indoor unit (Compact 4-way Cassette (600 × 600) Type) <Double twin type> Indoor unit 1 RAV-SM562MUT-E RAV-SM562MUT-E Indoor unit 2 RAV-SM562MUT-E RAV-SM562MUT-E Model Indoor unit 3 RAV-SM562MUT-E RAV-SM562MUT-E Indoor unit 4 RAV-SM562MUT-E RAV-SM562MUT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2244AT7 Cooling capacity (min.
  • Page 12 Engineering Data 1-1-10. Indoor unit (Slim Duct Type) <Double twin type> Indoor unit 1 RAV-SM564SDT-E RAV-SM564SDT-E Indoor unit 2 RAV-SM564SDT-E RAV-SM564SDT-E Model Indoor unit 3 RAV-SM564SDT-E RAV-SM564SDT-E Indoor unit 4 RAV-SM564SDT-E RAV-SM564SDT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2244AT7 Cooling capacity (min. - max.) (kW) 20.0 (9.8-22.4) 20.0 (9.8-22.4)
  • Page 13 Engineering Data 1-1-11. Indoor unit (Duct Type) <Double twin type> Indoor unit 1 RAV-SM562BT-E RAV-SM802BT-E RAV-SM562BT-E RAV-SM802BT-E Indoor unit 2 RAV-SM562BT-E RAV-SM802BT-E RAV-SM562BT-E RAV-SM802BT-E Model Indoor unit 3 RAV-SM562BT-E RAV-SM802BT-E RAV-SM562BT-E RAV-SM802BT-E Indoor unit 4 RAV-SM562BT-E RAV-SM802BT-E RAV-SM562BT-E RAV-SM802BT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7 RAV-SM2804AT7...
  • Page 14 Engineering Data 1-1-12. Indoor unit (Ceiling Type) <Double twin type> Indoor unit 1 RAV-SM562CT-E RAV-SM802CT-E RAV-SM562CT-E RAV-SM802CT-E Indoor unit 2 RAV-SM562CT-E RAV-SM802CT-E RAV-SM562CT-E RAV-SM802CT-E Model Indoor unit 3 RAV-SM562CT-E RAV-SM802CT-E RAV-SM562CT-E RAV-SM802CT-E Indoor unit 4 RAV-SM562CT-E RAV-SM802CT-E RAV-SM562CT-E RAV-SM802CT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7 RAV-SM2804AT7...
  • Page 15 Engineering Data 1-1-13. Indoor unit (High wall Type) <Double twin type> Indoor unit 1 RAV-SM562KRT-E RAV-SM802KRT-E RAV-SM562KRT-E RAV-SM802KRT-E Indoor unit 2 RAV-SM562KRT-E RAV-SM802KRT-E RAV-SM562KRT-E RAV-SM802KRT-E Model Indoor unit 3 RAV-SM562KRT-E RAV-SM802KRT-E RAV-SM562KRT-E RAV-SM802KRT-E Indoor unit 4 RAV-SM562KRT-E RAV-SM802KRT-E RAV-SM562KRT-E RAV-SM802KRT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7...
  • Page 16: Outdoor Unit

    Engineering Data 1-2. Outdoor Unit Model Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E RAV-SM2244AT7 RAV-SM2804AT7 3 phase 380-415V 50Hz 3 phase 380V 60Hz Power supply (Power exclusive to outdoor is required.) (Power exclusive to outdoor is required.) Type Hermetic compressor Hermetic compressor Compressor Motor (kW) 3.75...
  • Page 17: Construction Views (External Views)

    Engineering Data Construction views (External views) 2-1. Outdoor unit Drain hole Mounting bolt hole Drain hole Knockout (for drain) (Ø28 x 88 bearing hole) (Ø12 x 17 long hole) (Ø25 bearing hole) Air inlet B legs port Air inlet Knockout port (for drain) Mounting bolt hole...
  • Page 18: Gravity Position

    Engineering Data Gravity position Digital Inverter Outdoor unit Model Name X(mm) Y(mm) Z(mm) Weight (kg) RAV-SM2244AT7 RAV-SM2244AT7Z RAV-SM2244AT7ZG RAV-SM2244AT8-E RAV-SM2244AT8Z-E RAV-SM2244AT8ZG-E RAV-SM2804AT7 RAV-SM2804AT7Z RAV-SM2804AT7ZG RAV-SM2804AT8-E RAV-SM2804AT8Z-E RAV-SM2804AT8ZG-E (Unit:mm)
  • Page 19: Wiring Diagram

    Engineering Data Wiring diagram Model : RAV-SM2244AT8(Z)(ZG)-E, RAV-SM2804AT8(Z)(ZG)-E, RAV-SM2244AT7(Z)(ZG), RAV-SM2804AT7(Z)(ZG) Posister (Red) (Red) (Red) (Red) CN851 CN05 CN10 (Red) (White) (Red) CN06 CN16 (Black) (White) (Red) CN07 CN17 Compressor CN101 (Black) Noise Filter (Black) CN18 IPDU board (White) P.C. board (Gray) MCC-1596 (Red)
  • Page 20: Outdoor Unit Refrigerating Cycle Diagram

    Engineering Data Outdoor Unit refrigerating cycle diagram RAV-SM2244AT8(Z)(ZG)-E, SM2804AT8(Z)(ZG)-E RAV-SM2244AT7(Z)(ZG), SM2804AT7(Z)(ZG) Solenoid valve TO sensor Check joint High-pressure side Muffler Pressure Ø45×230 L valve switch TL sensor Check TD sensor Liquid tank F45×420 L 4-way valve TS sensor Check joint Low- Packed pressure side...
  • Page 21: Sensible Capacity Table

    Engineering Data Sensible capacity table Digital Inverter 8,10HP Sensible Heat Capacity: RAV-SM***UT-E indoor air temp. 14.0CWB 15.0CWB 16.0CWB 17.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB outdoor Outdoor 20.0CDB 21.5CDB 23.0CDB 24.5CDB 26.0CDB 27.0CDB 28.0CDB 30.0CDB 32.0CDB air temp. unit size 10.0 20.8 16.6 21.9...
  • Page 22 Engineering Data Digital Inverter 8,10HP Sensible Heat Capacity: RAV-SM***BT-E indoor air temp. 14.0CWB 15.0CWB 16.0CWB 17.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB outdoor Outdoor 20.0CDB 21.5CDB 23.0CDB 24.5CDB 26.0CDB 27.0CDB 28.0CDB 30.0CDB 32.0CDB air temp. unit size 10.0 20.8 14.6 21.9 15.3 23.0 16.1...
  • Page 23 Engineering Data Digital Inverter 8,10HP Sensible Heat Capacity: RAV-SM***CT-E indoor air temp. 14.0CWB 15.0CWB 16.0CWB 17.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB outdoor Outdoor 20.0CDB 21.5CDB 23.0CDB 24.5CDB 26.0CDB 27.0CDB 28.0CDB 30.0CDB 32.0CDB air temp. unit size 10.0 20.8 14.6 21.9 15.3 23.0 16.1...
  • Page 24 Engineering Data Digital Inverter 8,10HP Sensible Heat Capacity: RAV-SM***KRT-E indoor air temp. 14.0CWB 15.0CWB 16.0CWB 17.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB outdoor Outdoor 20.0CDB 21.5CDB 23.0CDB 24.5CDB 26.0CDB 27.0CDB 28.0CDB 30.0CDB 32.0CDB air temp. unit size 10.0 20.8 14.4 21.9 15.1 23.0 15.9...
  • Page 25 Engineering Data Digital Inverter 8,10HP Sensible Heat Capacity: RAV-SM***MUT-E indoor air temp. 14.0CWB 15.0CWB 16.0CWB 17.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB outdoor Outdoor 20.0CDB 21.5CDB 23.0CDB 24.5CDB 26.0CDB 27.0CDB 28.0CDB 30.0CDB 32.0CDB air temp. unit size 10.0 20.8 15.2 21.9 16.0 23.0 16.8...
  • Page 26: Part Load Performance

    Engineering Data Part Load Performance 7-1. Indoor unit: 4-way cassette (Twin, Triple, W-Twin) Outdoor unit: RAV-SM2244AT8-E, RAV-SM2244AT7 Cooling Load (%) Outdoor temperature (°C) 15880* 15880 14110 12350 10580 8820 8640 8640 8640 8640 6130 6130 5120 4220 3420 2690 2670 2670 2670 2670...
  • Page 27 Engineering Data 7-2. Indoor unit: 4-way cassette (Twin, Triple, W-Twin) Outdoor unit: RAV-SM2804AT8-E, RAV-SM2804AT7 Cooling Load (%) Outdoor temperature (°C) 16010* 16010* 16010 14200 12170 10140 8640 8640 8640 8640 6170 6170 6170 4870 3740 2790 2670 2670 2670 2670 21760 19580 17410...
  • Page 28 Engineering Data 7-3. Indoor unit: Duct (Twin, Triple, W-Twin) Outdoor unit: RAV-SM2244AT8-E, RAV-SM2244AT7 Cooling Load (%) Outdoor temperature (°C) 14820* 14820 14110 12350 10580 8820 8640 8640 8640 8640 6140 6140 5620 4540 3600 2770 2760 2760 2760 2760 18920 17030 15140 13240...
  • Page 29 Engineering Data 7-4. Indoor unit: Duct (Twin, Triple, W-Twin) Outdoor unit: RAV-SM2804AT8-E, RAV-SM2804AT7 Cooling Load (%) Outdoor temperature (°C) 15270* 15270* 15270 14200 12170 10140 8640 8640 8640 8640 6190 6190 6190 5350 4010 2900 2760 2760 2760 2760 21760 19580 17410 15230...
  • Page 30 Engineering Data 7-5. Indoor unit: Ceiling (Twin, Triple, W-Twin) Outdoor unit: RAV-SM2244AT8-E, RAV-SM2244AT7 Cooling Load (%) Outdoor temperature (°C) 14820* 14820 14110 12350 10580 8820 8640 8640 8640 8640 6140 6140 5620 4540 3600 2770 2760 2760 2760 2760 18920 17030 15140 13240...
  • Page 31 Engineering Data 7-6. Indoor unit: Ceiling (Twin, Triple, W-Twin) Outdoor unit: RAV-SM2804AT8-E, RAV-SM2804AT7 Cooling Load (%) Outdoor temperature (°C) 15270* 15270* 15270 14200 12170 10140 8640 8640 8640 8640 6190 6190 6190 5350 4010 2900 2760 2760 2760 2760 21760 19580 17410 15230...
  • Page 32 Engineering Data 7-7. Indoor unit: High wall (Triple, W-Twin) Outdoor unit: RAV-SM2244AT8-E, RAV-SM2244AT7 Cooling Load (%) Outdoor temperature (°C) 14820* 14820 14110 12350 10580 8820 8640 8640 8640 8640 6140 6140 5620 4540 3600 2770 2760 2760 2760 2760 18920 17030 15140 13240...
  • Page 33 Engineering Data 7-8. Indoor unit: High wall (Triple, W-Twin) Outdoor unit: RAV-SM2804AT8-E, RAV-SM2804AT7 Cooling Load (%) Outdoor temperature (°C) 15270* 15270* 15270 14200 12170 10140 8640 8640 8640 8640 6190 6190 6190 5350 4010 2900 2760 2760 2760 2760 21760 19580 17410 15230...
  • Page 34 Engineering Data 7-9. Indoor unit: Compact 4-way cassette (W-Twin) Outdoor unit: RAV-SM2244AT8-E, RAV-SM2244AT7 Cooling Load (%) Outdoor temperature (°C) 14820* 14820 14110 12350 10580 8820 8640 8640 8640 8640 6140 6140 5620 4540 3600 2770 2760 2760 2760 2760 18920 17030 15140 13240...
  • Page 35 Engineering Data 7-10. Indoor unit: Slim duct (W-Twin) Outdoor unit: RAV-SM2244AT8-E, RAV-SM2244AT7 Cooling Load (%) Outdoor temperature (°C) 14820* 14820 14110 12350 10580 8820 8640 8640 8640 8640 6140 6140 5620 4540 3600 2770 2760 2760 2760 2760 18920 17030 15140 13240 11350...
  • Page 36: Sound Characteristics (Nc Curve)

    Engineering Data Sound Characteristics (NC Curve) RAV-SM2244AT8-E, RAV-SM2244AT7 RAV-SM2804AT8-E, RAV-SM2804AT7 Sound Cooling Heating Sound Cooling Heating pressure level pressure level (dB(A)) (dB(A)) Cooling Cooling Heating Heating Approximate threshold of Approximate threshold of hearing for continuous noise hearing for continuous noise Octave band center frequency (Hz) Octave band center frequency (Hz)
  • Page 37: Capacity Correction

    Engineering Data Capacity Correction Connecting pipe length and lift difference between indoor units vs. capacity correction value Cooling –10 –20 –30 Pipe length (m) Heating –10 –20 –30 Pipe length (m)
  • Page 38 Engineering Data Refrigerant Pipe Length (Twin, Triple, Double Twin system) Simultaneous twin, triple Allowable pipe length (m) Height difference (m) Pipe diameter (mm) Total length Branch Branch Number of Indoor - outdoor H Main pipe Branch piping • piping piping Outdoor unit bent Indoor –...
  • Page 39 Engineering Data Piping connection with different diameter – Piping connection with different diameter is possible under the below restraint conditions. – Maximum pipe length is determined by the combination of liquid pipe diameter and gas pipe diameter. Liquid pipe Ø12.7 (standard) Normal piping size Gas pipe Ø22.2 (1-size smaller)
  • Page 40: Line Up

    Engineering Data Line up Combination pattern Digital inverter 8/10HP 10HP RAV-SM2244AT8(Z,ZG)-E RAV-SM2804AT8(Z,ZG)-E RAV-SM2244AT7(Z,ZG) RAV-SM2804AT7(Z,ZG) Twin system series 4 RAV-SM1104UT-Ex2 RAV-SM1404UT-Ex2 series 3 4-way cassette series 2 Duct series 2 RAV-SM1102BT-Ex2 RAV-SM1402BT-Ex2 Ceiling series 2 RAV-SM1102CT-Ex2 RAV-SM1402CT-Ex2 Triple system series 4 RAV-SM804UT-Ex3 RAV-SM804UT-Ex3 series 3...
  • Page 41 Engineering Data Branch kit "1:2" Branch kit RBC-TWP101E "1:3" Branch kit RBC-TRP100E "1:4" Branch kit set RBC-DTWP101E Option parts of outdoor unit Optional connector cable TCB-KBOS1E...
  • Page 42: Existing Piping

    Branching pipe for simultaneous operation system case. • In the concurrent twin system, when TOSHIBA has specified Pipe diameter and thickness (mm) that branching pipe is to be used, it can be reused. Reference outside...
  • Page 43 Engineering Data Are there scratches or dents on the existing pipes? Existing pipes: Cannot be used. • Use new pipes. Is it possible to operate the existing air conditioner? • After the existing air conditioner is operated in cooling mode for approx. 30 minutes or longer,* recover the refrigerant.
  • Page 44 Digital Inverter 4series 8-10HP Engineering Data Book Jul. 2009...