Step Component
Comp-IPDU
P.C. board
AMP Air Conditioning
Procedure
WARNING
Do not detach the inverter for 5 minutes after
turning off the breaker as doing so may cause
electric shocks.
1) Perform Step 1 of ①, Step 2 and Step 3 of ⑤,
Step 2 of ⑦.
2)
assembly box (A).
3) Remove the screws for inverter assembly box
(A) and inverter cover (A).
(M4×10, 2)
4) Remove the connector connected between
the Comp-IPDU P.C. board and another
component.
CN201 ...Compressor lead (red)
CN202 ...Compressor lead (white)
CN203 ...Compressor lead (black)
CN05, CN11.... Connection with reactor terminal (A) (black)
CN05, CN12 ... Connection with reactor terminal (A) (red)
CN03 .....
CN04 .....
CN21 .....Connection with fan IPDU P.C. board (CN502) (3P: white)
CN851 ...Connection with fan IPDU P.C. board (CN505) (5P: red)
CAUTION
Disengage the lock on the housing to unplug
the connector.
5)
screws and support (2 positions).
6) Remove the screws on the Comp-IPDU P.C.
board.
(Flange screws M3×14, 2)
(Binding head screws M4×15, 4)
7) Mount a new Comp-IPDU P.C. board.
Flange screws
(2 positions)
Support
Fixing screws
159
Remarks
Noise filter P.C. board
Inverter assembly box (A)
Inverter cover (A)
screws (2 positions)
Comp-IPDU P.C. board
Fixing screws
Binding head
screws
(4 positions)
Support