Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
P05
P05
P07
P07
Detected
indoor address
P10
P10
P12
P13
P13
AMP Air Conditioning
Location
of
Description
System status
detection
I/F
Inverter DC
All stop
voltage (Vdc)
trouble
(compressor)
IPDU
Heat sink
All stop
I/F
overheating
trouble
Indoor
Indoor overflow
All stop
unit
trouble
Indoor
Indoor fan motor
Stop of
unit
trouble
corresponding
unit
I/F
Outdoor liquid
All stop
backflow
detection trouble
Check code detection
condition(s)
Inverter DC voltage is too
high (overvoltage) or too
low (undervoltage).
Temperature sensor built into
IGBT (TH) is overheated.
Float switch operates.
Float switch circuit is open-
circuited or disconnected
at connector.
Motor speed
measurements
continuously deviate from
target value.
Overcurrent protection is
activated.
<During heating operation>
When system is in heating
operation, outdoor PMV 1
continuously registers
opening of 100 pulse or less
while under super heat control.
124
114
www.ampair.co.uk | sales@ampair.co.uk
Check items (locations)
Check for trouble in outdoor
P.C. board (A3-IPDU).
Check for trouble in outdoor
power supply wiring.
Check power supply
voltage.
Check outdoor fan system
trouble.
Check heat sink cooling
duct for clogging.
Check IGBT and heat sink
for thermal performance for
troubled installation.
(e.g. mounting screws and
thermal conductivity)
Check for trouble in A3-
IPDU.
(troubled IGBT built-in
temperature sensor (TH))
Check float switch
connector.
Check operation of drain
pump.
Check drain pump circuit.
Check drain pipe for
clogging.
Check for trouble in indoor
P.C. board.
Check connection of fan
connector and wiring.
Check for trouble in fan
motor.
Check for trouble in indoor
P.C. board.
Check impact of outside air
treatment (OA).
Check full-close operation
of outdoor PMV.
Check for trouble in PD or
PS sensor.
Check gas balancing
circuit (SV2) for clogging.
Check trouble in outdoor
P.C. board (I/F).
Check capillary of oil
separator oil return circuit
for clogging.
Check for leakage of check
valve in discharge pipe
convergent section.