1.SAFETY PRECAUTIONS The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications / Illustrated marks), and keep them. [Explanation of indications] Indication Explanation...
Page 4
CAUTION To disconnect the appliance from the main power supply A switch or circuit breaker that can disconnect all poles must be included in the fixed wiring. Be sure to use an approved circuit breaker or switch. DANGER • The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual.
Page 5
• Exchange to parts specified in service manual, which meet the specification or listed in parts list of service manual. Failure to use specified parts may result in electrical shock, smoke, and/or fire." • When checking the electric parts, removing the cover of the electric parts box of Indoor Unit and/or front panel of Outdoor Unit inevitably to determine the failure, put a sign “Do not enter”...
3. REFRIGERANT R410A This air conditioner adopts the new refrigerant HFC 7. Be sure to carry out installation or removal according (R410A) which does not damage the ozone layer. to the installation manual. The working pressure of the new refrigerant R410A is Improper installation may cause refrigeration trouble, 1.6 times higher than conventional refrigerant (R22).
Page 8
Table 3-2-1 Thicknesses of annealed copper pipes Thickness (mm) Nominal diameter Outer diameter (mm) R410A 6.35 0.80 0.80 9.52 0.80 0.80 12.70 0.80 0.80 15.88 1.00 1.00 2. Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm.
Page 9
d) Flare Processing Make certain that a clamp bar and copper pipe have been cleaned. ØD By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R410A or conventional flare tool. Flare processing dimensions differ according to the type of flare tool.
Page 11
3-3. Tools 3-3-1. Required Tools The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened. The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc.
3-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Page 13
1. Be sure to make setting so that liquid can be charged. 2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down. It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
Page 14
2. Characteristics required for flux 3-5-3. Brazing • Activated temperature of flux coincides with the As brazing work requires sophisticated techniques, brazing temperature. experiences based upon a theoretical knowledge, it must be performed by a person qualified. • Due to a wide effective temperature range, flux is hard to carbonize.
4. CONSTRUCTION VIEWS Hanging bolt pitch A Unit external dimension B 25 or less C (Outside) (Only the position of a 1/100 or more check cover.) downward Hanging Flexible drain hose bolt (Accessory) 300 or less Drain-up piping Check cover Refrigerant pipe connecting port (Liquid side)
8. CONTROL BLOCK DIAGRAM Indoor Unit Control Unit M.C.U. Heat Exchanger Sensor (Tcj) Functions Heat Exchanger Sensor (Tc) • Cold draft preventing Function Room Temperature Sensor (Ta) • 3-minute Delay at Restart for Compressor Infrared Rays Signal Receiver • Fan Motor Starting Control and Indication Indoor Fan Motor Control...
9-1. Outline of Air Conditioner Control This air conditioner is a capacity-variable type air • Detection of inverter input current and current conditioner, which uses DC motor for the indoor fan release operation motor and the outdoor fan motor. And the •...
9-2. Operation Description Item Operation flow and applicable data, etc. Description 1-1. Operation control 1. Basic operation Receiving the user’s operation condition setup, the operation statuses of indoor/outdoor units are controlled. 1) The operation conditions are selected by the remote controller as shown in the below. 2) A signal is sent by ON button of the remote controller.
Item Operation flow and applicable data, etc. Description 1. Basic 1-2.When power supply is reset operation 1) Based on EEPROM data and DIPSW, setting of the indoor fan speed and other setting are loaded. During this loading (approx 30 seconds), operation cannot be accepted. Air speed (rpm) 1-3.
Item Operation flow and applicable data, etc. Description 1. Basic 1-4. Cooling/Heating operation operation The operations are performed in the following parts by controls according to cooling/heating conditions. 1) Receiving the operation ON signal of the remote controller, the cooling or heating operation signal starts being transferred from the indoor controller to the outdoor unit.
Item Operation flow and applicable data, etc. Description 1. Basic 1-5. AUTO operation operation Remote controller Control outline command • COOL/HEAT operation mode is automatically selected by Ta, Ts Ta: Room temp. and To for operation. Ts: Setup temp. • The operation is performed as To: Outside temp.
Item Operation flow and applicable data, etc. Description 1) Operation with (HH), (H+), (H), (L+), (L) or [AUTO] mode is carried HH > H+ > H > L+ > L > UL 2. Indoor fan motor out by the command from the remote controller. control 2) When the air speed mode [AUTO] is selected, the air speed varies by the difference between Ta and Ts.
Page 27
Item Operation flow and applicable data, etc. Description 2. Indoor fan Revolution speed of indoor fan (rpm) motor ■ M07G3DV, M10G3DV control External static pressure selection COOL HEAT 10Pa 20Pa 35Pa 45Pa 1020 1120 1200 1260 1020 1120 1200 1260 1020 1120 1160...
Page 28
Item Operation flow and applicable data, etc. Description 5) Self-clean operation [Self-clean ] is displayed. 2. Indoor fan motor When performing self-clean operation after stopping the cooling control operation, the mode becomes LL (M07, M10, M13), L (M16). Cool air discharge preventive control In D and E zones, the priority is given to air volume 1) In heating operation, the indoor fan is controlled based on the...
Item Operation flow and applicable data, etc. Description The cooling or heating capacity depending on the load is adjusted. 1) The difference between set 3. Capacity control temperature on remote According to difference between the setup value of temperature and the controller (Ts) and room room temperature, the capacity is adjusted by the compressor revolution.
Item Operation flow and applicable data, etc. Description High-temp. release control 4. Release protective 1) The heating operation is performed as follows based on the control by detected temperature of Tc sensor or Tcj sensor. temperature of indoor • When [M] zone is detected, the commanded frequency is heat decreased from the real operation frequency.
7. Intermittent Operation Control for Indoor Fans of the Indoor Unit at Thermo-off Side in Heating Operation While heating operation is executed in two rooms, if room temperature reached the setup temperature in one room and thermo-off occurred, the following operations start. (Refer to the figure below.) 1.
8. Additional Operation Item Operation flow and applicable data, etc. Description 8-1. QUIET mode When the [QUIET] button is pressed, the fan of the Quiet mode is the system which, control the indoor unit will be restricted the revolving speed at speed revolving speed of indoor fan to work L until the [QUIET] button is pressed once again (cancel constantly at speed L.
Item Operation flow and applicable data, etc. Description Cooling mode The principles of comfort sleep mode are: 8-4. COMFORT SLEEP • The preset temperature will increase as ECO • Quietness for more comfortable. mode operation (Item 8-3.) • Save energy by changing room •...
Item Operation flow and applicable data, etc. Description 11. Frequency <In case of wired remote controller> Command frequency is approximately [S7] fixed Refer to 14-1.Test run setup. operation (Test run) <In case of wireless remote controller> 1) When TEMPORARY button is pushed for 10 seconds or more, “Pi!”...
Item Operation flow and applicable data, etc. Description 1. Purpose 12. Self-Cleaning function The Self-Cleaning operation is to minimize the growth of mold, bacteria etc. by running the fan and drying so as to keep the inside of the air conditioner clean. Unit now performing cooling or dry operation Self-Cleaning operation When the cooling or dry operation shuts...
Item Operation flow and applicable data, etc. Description • Self-Cleaning diagram 12. Self-Cleaning function Operation display FCU fan (Self-Cleaning fan speed) rpm is depend on presetting. PRE, DEF display ON or OFF Compressor depend on presetting per room temperature. ON or OFF CDU fan depend on presetting per room temperature.
Item Operation flow and applicable data, etc. Description Setting the remote controller 1. Purpose 15. Remote-A or B selection To separate using of remote control for each indoor unit This operation is to operate only one in case of 2 air conditioner are installed nearly. indoor unit using one remote controller.
Item Operation flow and applicable data, etc. Description There are 2 ways to set external static pressure setting. 17. External static 1) By DIP SW 501-1, -2 [FC [5D]=0000 (factory default) is necessary.] pressure Set the external static pressure setting with the DIP SW501-1, -2 on the indoor unit P.C. board as shown in settings the table below.
9-3. Auto Restart Function This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of a power supply being accidentally shut down. The operation will resume without warning three minutes after power is restored. This function is not set to work when shipped from the factory.
9-3-2. How to Cancel the Auto Restart Function To cancel auto restart function, proceed as follows : Repeat the setting procedure : the unit receives the signal and beeps three times. The unit will be required to be turned on with the remote controller after the main power supply is turned off. •...
The customized settings control temperature air flow strength, air flow direction and other settings to provide you alternate contact with “ONE-TOUCH” OF THE BUTTON. If you prefer other settings you can select from the many other operation functions of your Toshiba unit Press : Start the operation.
Page 42
4. DRY OPERATION (COOLING ONLY) For dehumidification, a moderate cooling performance is controlled automatically. 1. Press : Select Dry . MODE 2. Press : Set the desired temperature. 5. Hi-POWER OPERATION To automatically control room temperature and airflow for faster cooling or heating operation (except in DRY mode).
Page 43
9. PRESET OPERATION Set your preferred operation for future use. The setting will be memorized by the unit for future operation (except air flow direction). 1. Select your preferred operation. 2. Press and hold for 3 seconds to memorize the setting. The P mark displays. 3.
9-4-3. Name and Functions of Indications on Remote Controller [Display] All indications, except for the clock time indicator, are displayed by pressing the button. Transmission mark TIMER and clock time indicator This transmission mark indicates when the The time setting for timer operation or the clock remote controller transmits signals to the indoor time is indicated.
The customized settings control temperature, air flow strength and other settings to provide you alternate contact with “ONE-TOUCH” of the button. If you prefer other settings you can select from the many other operating functions of your Toshiba unit. Press : Start the operation.
Page 46
Setting Everyday Timer Air conditioner operating conditions Temp. Outdoor Temperature Room Temperature Press Operation Press : Set the ON timer. Heating Less than 28°C Press button during the Cooling 21°C ~ 32°C Press : Set the OFF timer. ( or ) mark flashing. 17°C ~ 32°C •...
10-2. Accessory parts INSTALLATION MANUAL (EXCERPT) Part name Q’ty Shape Usage Installation Manual This manual (Be sure to hand over to customers) Insulating pipe For insulating pipe connecting section Washer M10 × Ø34 For hanging down the unit Hose band For connecting drain pipe Flexible hose For adjustment of drain pipe centering...
10-3. Selection of installation place Avoid installing in the following places Select a location for the indoor unit where the cool or warm air will circulate evenly. Avoid installation in the following kinds of locations. • Saline area (coastal area) •...
Installation under high-humidity atmosphere In some cases including the rainy season, especially inside of the ceiling may become high-humidity atmosphere (dew-point temperature: 23 °C or higher). 1. Installation to inside of the ceiling with tiles on the roof 2. Installation to inside of the ceiling with slated roof 3.
Page 50
10-4. Installation CAUTION Strictly comply with the following rules to prevent damage of the indoor units and human injury. • Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged) •...
Installation of hanging bolt REQUIREMENT • Consider the piping / wiring after the unit is hung to determine the location of the indoor unit installation and orientation. • Hang the unit in a horizontal position. • After the location of the indoor unit installation has been determined, install When unit is hanged to slant, it may cause overflow of drainage.
Page 52
Changing from under air intake to back air intake Remove the suction board cover attached to the back, and screw it to the bottom of unit. Suction board Remove the top and bottom fan case screws, and fasten the fan case with the suction board. Installation location of receiving unit The sensor of indoor unit with wireless remote controller can receive a signal by distance within approx.
Page 53
How to Install the Signal Receiving Unit To prevent electric shocks, embed the wires in the wall and do not expose them. When installing wires on the wall, be sure to cover them with insulating materials. Note: • To avoid malfunction of the remote controller, do not assemble or run remote control wiring together with the power cables, and do not enclose them in the same metal conduit.
10-5. Drain piping CAUTION Following the Installation Manual, perform the drain piping work so that water is properly drained. Apply a heat insulation so as not to cause a dew condensation. Inappropriate piping work may result in water leakage in the room and wet furniture. •...
Page 55
Remove the drain pump connector CN504. * For gravitational drainage, remove the white connector (CN504) on the P.C. board in the electrical control box. CN504 White Move the plug to the upper pipe from the lower pipe on the side that will be used. Insert the flexible drain hose into the lower drain pipe and fix it with the hose band.
Heat insulating process • As shown in the figure, cover the flexible hose and hose band with the attached heat insulator up to the bottom of the indoor unit without gap. • Cover the drain pipe seamlessly with a heat insulator locally procured so that it overlaps with the attached heat insulator of the drain connecting section. Wrap the attached heat insulator seamlessly from the surface of the indoor unit.
Fan characteristics RAS-M07G3DV, M10G3DV Series Standard Air Volume = 570m Upper limit of external static pressure (45Pa) High (45Pa) Lower limit of external static pressure (45Pa) High (35Pa) Low (45Pa) Low (35Pa) High (20Pa) Low (20Pa) High (10Pa) Low (10Pa) Air Volume (m RAS-M13G3DV Series Standard Air Volume = 610m...
Page 58
Connecting method of the duct Connect a duct to the outside of the flange. In addition, the duct must be covered with insulation Duct: Insulation material Flange (locally procured) material so that the flange (locally procured) will not be exposed Aluminum tape (locally procured) Flange Indoor unit...
10-7. Refrigerant piping • Use two wrenches to connect the indoor unit pipe. CAUTION When the refrigerant pipe is long, provide support brackets at intervals of 2.5 to 3 m to clamp the refrigerant pipe. Otherwise, abnormal sound may be generated. Use the Work using double spanner flare nut attached with the indoor unit or •...
10-8. Electrical connection 1. The supply voltage must be the same as the rated voltage of the air conditioner. 2. Prepare the power source for exclusive use with the air conditioner. NOTE • Wire type : More than H07RN-F or 60245 IEC66 (1.5 mm or more).
10-9. Others External static pressure settings Auto Restart Setting Change the external static pressure setting with the DIP switch on the indoor This product is designed so that, after a power failure, it can restart unit P.C. board. automatically in the same operating mode as before the power failure. Information The product was shipped with Auto Restart function in the off position.
11. HOW TO DIAGNOSE THE TROUBLE The pulse motor circuits are mounted to both indoor and outdoor units. Therefore, diagnose troubles according to the trouble diagnosis procedure as described below. (Refer to the check points in servicing written on the wiring diagrams attached to the indoor/outdoor units.) Table 11-1 Troubleshooting Procedure...
11-2. Primary Judgment To diagnose the troubles, use the following methods. 1) Judgment by flashing LED of the signal receiving unit 2) Self-diagnosis by service check remote controller 3) Judgment of trouble by every symptom Firstly use the method 1) for diagnosis. Then, use the method 2) or 3) to diagnose the details of troubles. 11-3.
Page 64
11-4. Self-Diagnosis by Remote Controller (Check Code) 1. If the lamps are indicated as shown B to E in Table 11-3-1, execute the self-diagnosis by the remote controller. 2. When the remote controller is set to the service mode, the indoor controller diagnoses the operation condition and indicates the information of the self-diagnosis on the display of the remote controller with the check codes.
Page 65
11-4-2. Caution at Servicing 1. After servicing, press the [ ] button to return to the normal mode. 2. After servicing by the check code, turn off breaker of the power supply, and turn on breaker of the power supply again so that memory in the microcomputer returns the initial status.
Page 66
Block distinction Operation of diagnosis function Judgment and action Check Check Block Cause of operation conditioner Remarks code code status Outdoor Inverter over-current All off Displayed when Even if trying operation again, all P.C. board protective circuit error is detected. operations stop immediately.
Page 67
Block distinction Operation of diagnosis function Judgment and action Check Check Block Cause of operation conditioner Remarks code code status Others Return serial signal Operation Flashes when 1. Repeat Start and Stop with interval of (including has been sent when continues trouble is approx.
11-5. Judgment of Trouble by Every Symptom 11-5-1. Indoor Unit (Including Remote Controller) (1) Power is not turned on (Does not operate entirely) <Primary check> 1. Is the supply voltage normal? 2. Is the normal voltage provided to the outdoor unit? 3.
Page 69
(2) Power is not turned on though Indoor P.C. board is replaced <Confirmation procedure> Turn on power supply. Is wired correctly to white and black lead Does operation lamp flash? Correct wiring. wires of terminal board? To item of “Power is not turned on”. –...
Page 70
(3) Only the indoor motor fan does not operate <Primary check> 1. Is it possible to detect the power supply voltage (AC220–240V) between 1 and 2 on the terminal block? 2. Does the indoor fan motor operate in cooling operation? (In heating operation, the indoor fan motor does not operate for approximately 10 minutes after it is turnedon, to prevent a cold air from blowing in.) Power off.
Page 71
(4) Troubleshooting for remote control The unit does not beep at all. Press [ OPERATION lamp on indoor button. unit is not indicated. Is transmission mark indicated? Press RESET button on remote control with Is the signal tip of pencil. receiving unit exposed to direct sunlight? Does indoor unit...
Page 72
11-6. How to Check Simply the Main Parts 11-6-1. How to Check the P.C. Board (Indoor Unit) (1) Operating precautions 1) When removing the P.C. board, be sure to shut off the power supply breaker. 2) When removing the P.C. board, hold the edge of the P.C. board and do not apply force to the parts. 3) When connecting or disconnecting the connectors on the P.C.
Page 73
(3) Check procedures Table 11-6-1 Procedure Check points Causes Turn off the power supply breaker Check whether or not the fuse (F01) Impulse voltage was applied or the and remove the P.C. board is blown. indoor fan motor short-circuited. assembly from electronic parts base.
Page 74
11-6-2. P .C . Board Layout Wired remote controller Power supply LED of communication LED microprocessor D504 (Green) D501 (Red) DC fanmotor HA(T10) CN210 (White) CN61 (Yellow), DC12V TA sensor CN104 (Yellow), DC5V Drain pump CN504 (White), DC12V TC sensor Power supply CN101 (Black), DC5V CN67 (Black), AC220V...
Page 75
11-6-3. Indoor Unit (Other Parts) Part name Checking procedure Room temp. (TA) sensor Disconnect the connector and measure the resistance value with tester. Heat exchanger (TC) sensor (Normal temp.) Temperature 20°C 25°C 30°C 40°C 10°C Sensor TA, TC (kΩ) 20.7 12.6 10.0 Remote controller...
12. HOW TO REPLACE THE MAIN PARTS WARNING CAUTION Be sure to stop operation of the air conditioner before Be sure to put on gloves during working time; work and then turn off switch of the breaker. otherwise an injury will be caused by a part, etc. Part name Procedure Remarks...
Page 77
Part name Procedure Remarks Electric parts box 1. Detachment Electric parts box cover cover 1) Perform step 1 of “2Terminal cover” as required. (You may be able to perform this procedure without removing the electric parts box cover.) Screws 2) Slightly loosen the screw holding the electric parts box cover in place.
Page 78
NOISE FILTER 1. Detachment 1) Perform the procedure in 1 of “3 Electric parts box cover.” 2) Remove the binding band from clamp. The claw of 3) The claw of the noise filter (two places) is noise filter removed and remove from the signal receiving unit lead wire.
Page 79
Part name Procedure Remarks Control P.C. 1. Detachment board 1) Perform the procedure in 1 of “3Electric parts Electric parts box box cover.” 2) Disconnect the connectors from other components from the control P.C. board. NOTE) Unlock the lock of the housing to disconnect the connectors.
Page 80
Part name Procedure Remarks Fan case 1. Detachment (lower), Fan 1) For the back air intake, perform the procedure case (upper) in 1 of “1Suction panel.” Fan case (upper) 2) Remove the screw on the rear of the fan case Fan case (lower) screw (lower).
Page 81
Part name Procedure Remarks Fan motor, Multi 1. Detachment blade fan 1) For the back air intake, perform the procedure in 1 of “1Suction panel.” 2) Perform the procedure in steps 1-1), 1-2), 1-3) Clamp of “3Electric parts box cover.” Binding band 3) Disconnect the following connector of the control P.C.
Page 82
Part name Procedure Remarks Fan motor, Multi NOTE) blade fan Arrange the multi blade fan so that screws position at the right side against the drain pan. NOTE) Fix multi blade fan with torque wrench 4.9 N•m or more. 3) Perform the procedure in steps 2-3) and 2-4) of “8Fan case (lower/upper)”...
Page 83
Part name Procedure Remarks Under panel, 1. Detachment Drain pan 1) Take off the drain cap and drain the drain water accumulated in the drain pan. Drain cap and drain In case of natural drain model, drain the drain hose Screws water by taking off hose band and drain hose.
Page 84
Part name Procedure Remarks Drain pump, 1. Detachment Float switch, 1) Perform the procedure in steps 1-1), 1-2), 1-3) Drain hose of “3Electric parts box cover” and 1 of Drain pump Float switch “0Under panel, Drain pan.” Screws * For only drain 2) Disconnect the following connectors and pump connected cables from the control P.C.
Page 85
Part name Procedure Remarks Heat exchanger 1. Detachment 1) Recover refrigerant, and then remove Sensors refrigerant pipes at indoor unit side. Binding band 2) Perform the procedure in steps 1-1), 1-2), 1-3) of “3Electric parts box cover” and 1 of “0Under panel, Drain pan.”...
14. Appendix Lite-Vision plus Remote Controller (RB-RWS20-E) setup 1. Test run setup <Procedure> Perform setting while the air conditioner stops. Push the [ MENU] button to display the menu screen. ∨] button at the Push and hold the [ MENU] button and the [ Field setting menu same time to display the “Field setting menu”.
Page 90
Using the Service monitor with the [ MONITOR] button during the test mode Room A 12:00 Test Cool Mode Fan Speed Push the [ MONITOR] button Monitor Function Code Data 0024 Return Refer to “3. Monitor function” for details. 2. Function selection setup Perform the advanced settings for the air conditioner.
Page 91
Function selection item No. (FC) list Item Contents At shipment from factory 0000: None 0001: 150H Filter sign lighting time 0002: 2500H 0003: 5000H 0000: None 0004: 10000H 0005: Clogging sensor used 0000: Standard Filter stain level 0000: Standard 0001: Heavy stain (Half of standard time) 0000: No shift 0001: +1°C Heating suction temp.
4. Alarm history The error contents in the past can be called. ∧] / [ ∨] button to select “3. Alarm history” on Push the [ Field setting menu the “Field setting menu” screen, then push the “ Set” 1.Test mode F2] button.
Page 94
Toshiba Carrier Air Conditioning (China) Co., Ltd. Building 1, No.60, 21st Avenue, Baiyang Street, Hangzhou Economic and Technological Development Area, China Revision record First issue ― ― Sep.2014 Revision 1 Change of knockout hole diameter Page 14 Mar.2015...