hit counter script
Toshiba RAV-SP804ATP-E Installation Manual
Toshiba RAV-SP804ATP-E Installation Manual

Toshiba RAV-SP804ATP-E Installation Manual

Outdoor unit
Hide thumbs Also See for RAV-SP804ATP-E:

Advertisement

AIR CONDITIONER (SPLIT TYPE)

Installation manual

Outdoor Unit
Model name:
RAV-SP804ATP-E
RAV-SP804ATJP-E
For commercial use
English

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAV-SP804ATP-E

  • Page 1: Installation Manual

    AIR CONDITIONER (SPLIT TYPE) Installation manual Outdoor Unit For commercial use Model name: RAV-SP804ATP-E RAV-SP804ATJP-E English...
  • Page 2: Table Of Contents

    14 APPENDIX ..........17 RAV-SP804ATP-E 1.45...
  • Page 3 Toshiba Carrier Corporation or, alternatively, he or she Agent Qualifications and knowledge which the agent must have...
  • Page 4 - 3 - Definition of Protective Gear Warning Indications on the Air Conditioner Unit When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and “safety” work clothing. Warning indication Description In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below.
  • Page 5: Precautions For Safety

    PRECAUTIONS FOR SAFETY Selection of installation location • If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the measures.
  • Page 6: Electrical Wiring

    - 5 - Electrical wiring Explanations given to user • Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air • Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know conditioner.
  • Page 7: Accessory Parts

    ACCESSORY PARTS INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER Accessory Parts CAUTION Part name Q’ty Shape Usage Hand this directly to the customer. (For other languages that do not appear in this New Refrigerant Air Conditioner Installation Installation manual This manual •...
  • Page 8: Installation Conditions

    - 7 - INSTALLATION CONDITIONS Tools/equipment How to use tools/equipment Flare tool Flare machining of pipes Usable if dimensions are adjusted. Before installation Electrical wiring Bender Bending pipes R22 (Conventional tools) • Be sure to fix the power wires and indoor/outdoor Be sure to prepare to the following items before Refrigerant recovery equipment Refrigerant recovery connecting wires with clamps so that they do not come...
  • Page 9 Installation Location Necessary Space for Installation • A location where high-frequency equipment Consider the wind direction during the (including inverter equipment, private power operational season of the air conditioner, and (Unit: mm) generator, medical equipment, and communication install the unit so that the discharge port is set WARNING equipment) is used (Installation in such a location may at a right angle relative to the wind direction.
  • Page 10 - 9 - Obstacle in front Obstacles in both front and rear of unit Installation of Outdoor Unit Set the out margin of the anchor bolt to 15 mm or less. Open above and to the right and left of the unit. •...
  • Page 11: Refrigerant Piping

    REFRIGERANT PIPING Refrigerant Piping Connection Projection margin in flaring : B (Unit : mm) CAUTION Knockout of Pipe Cover TAKE NOTE OF THESE 4 IMPORTANT POINTS Supplied protective bush BELOW FOR PIPING WORK Knockout procedure Keep dust and moisture away from inside the Rigid (Clutch type) connecting pipes.
  • Page 12 - 11 - Tightening of Connecting Part Refrigerant Pipe Length CAUTION Align the centers of the connecting pipes and fully Single tighten the flare nut with your fingers. Then fix the Allowable pipe length (m) Height difference (Indoor-outdoor H) (m) Do not put the crescent wrench on the cap or cover.
  • Page 13: Air Purging

    AIR PURGING Use the vacuum pump, vacuum pump adapter, and gauge Cap tightening torque manifold correctly referring to the manuals supplied with each tool before using them. Check that the vacuum pump oil is filled up to the specified 14 to 18 N•m Ø9.5 mm line of the oil gauge.
  • Page 14: Electrical Work

    - 13 - ELECTRICAL WORK Stripping length power cord and connecting For the air conditioner, connect a power wire with the following specifications. wire 1 2 3 Model RAV- SP80 • Remove the service panel, and you can see electric Power supply 220-240 V~, 50 Hz WARNING...
  • Page 15: Earthing

    EARTHING FUNCTIONS TO BE IMPLEMENTED LOCALLY WARNING Night operation control When the pipe corresponds to any of the following, do not use it. Install a new pipe instead. • Low-noise operation is available during nighttime • Be sure to connect the earth wire. (grounding work) •...
  • Page 16: Troubleshooting

    - 15 - TROUBLESHOOTING Recovering Refrigerant • Use refrigerant recovery switch SW801 on the P.C. board of the outdoor unit to recover refrigerant when the indoor or outdoor unit is moved. Only a qualified service person can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition to using the check codes displayed on the wired remote controller of the indoor unit.
  • Page 17 Verifying an abnormal state in the past although the abnormal state no longer occurs * The LEDs and DIP SW801 SW800 switches are located Set bit 1 of DIP switch SW803 to ON. on the lower left of Jot down the states of LED800 to LED804. (Display mode 1) the P.C.
  • Page 18: Appendix

    Basic conditions needed to reuse existing When refrigerant cannot be recovered using a • In the concurrent twin system, when TOSHIBA has pipes refrigerant recovery unit. specified that branching pipe is to be used, it can be •...
  • Page 19: Specifications

    Is it possible to operate the existing air conditioner? Sound power level (dB) Model Weight (kg) Cooling Heating RAV-SP804ATP-E • After the existing air conditioner is operated in cooling RAV-SP804ATJP-E mode for approx. 30 minutes or longer,* recover the refrigerant. * Under 70 dBA •...
  • Page 20: Declaration Of Conformity

    R410A Global Warming Potential (GWP) of Gas 1 975 Manufacturer: TOSHIBA CARRIER (THAILAND) CO., LTD. 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, CAUTION Amphur Muang, Pathumthani 12000, Thailand Paste the enclosed refrigerant label adjacent to the charging and/or recovering location.
  • Page 21 WARNINGS ON REFRIGERANT LEAKAGE Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer.
  • Page 22 1114550501...

This manual is also suitable for:

Rav-sp804atjp-e

Table of Contents