Toshiba RAS-M10PKVP-E Service Manual page 143

Air conditioner (split type)
Hide thumbs Also See for RAS-M10PKVP-E:
Table of Contents

Advertisement

No. Part name
∗ Attachment
12
4-way valve
coil
Mount 4-way valve coil so that the label side directs upper
side of the cabinet.
Detail A
Label
Label
Label
4-way valve coil
4-way valve coil
4-way valve coil
13
PMV
1. Detachment
Coil: Blue
1) Perform work of Detachment 1 of 1 .
Coil: Green
2) Turn the coil clockwise (counterclockwise) and then
Coil: Red
remove it from PMV main unit. (All 4 pcs.)
Coil: Yellow
2. Attachment
1) Mount the PMV coil so that the coil lead wire taking-out
part directs downward.
CAUTION
Coil: Mount yellow coil only so that lead wire taking-out part
directs upward.
2) Match the positioning projection of coil with the concave
part of PMV unit surely and fix it.
Procedure
4-way valve unit
4-way valve unit
4-way valve unit
– 143 –
Remarks
Detail A
Detail B
Taking-off direction
Turn clockwise
Turn clockwise
Turn clockwise
(counterclockwise)
(counterclockwise)
(counterclockwise)
PMV sideways
Projection of PMV coil
Concave part of PMV